13
PACSystems™ RX3i Central
Processing Unit IC695CPE302
GFK-3038B
threaded holes in the bottom of the backplate and screw them several
turns using a #1 Phillips screwdriver. Tighten to 0.7 N-m (6 in-lbs.).
5.
Mount the Energy Pack on the left side of the module in slot 0 of the rack
(typically a power supply).
a.
Engage the Energy Pack’s mounting hooks (at the top) on the frame of
the leftmost module.
b.
Rotate the bottom of the Energy Pack into place, engaging the bottom
hooks. The latch will snap into place.
c.
Connect cable IC695CBL001 from the connector on the bottom of the
Energy Pack to
…
d.
the corresponding connector on the bottom of CPE302.
6.
If required, connect the CPE302 to the Ethernet network.
7.
Apply power to the rack.
Note
: When the Energy Pack is powered up for the first time, or is
in a system that has been powered down long enough to
completely discharge the Energy Pack, it may require a few
seconds for it to charge to its operating level. T
he CPU’s
STATUS LED will blink green during this time.
Module Initial Startup
You Will Need:
•
PACSystems RX3i CPU Firmware 8.00 or later.
•
PAC* Machine Edition configuration and programming software,
version 8.0 or later.
•
An IC693CBL316 serial or Ethernet cable for connecting the
computer running the PAC Machine Edition
™
programmer to the
RX3i CPU.