background image

The Type B NG is a two-stage pressure reducing 

regulator with an automatic safety device to 

avoid outlet over-pressure (relief valve venting to 

atmosphere) or stopping the gas flow in the event 

of an abnormal drop in inlet or outlet pressure or 

an excess flow condition. 

Rearming is manual by using the push-button and 

depending on models (B6 version only) a valve may 

be associated. A removable vent filter is situated 

in the inlet connection, and a vent screen (see 

schematic, item V). 

The underground model is treated for anti-corrosion 

and is painted.

Maximum allowable pressure: 

5 bar

Operating temperature:  

-20 / 60°C

INSTALLATION

CAUTION

•  To be used with clean, dry and non-corrosive gas. 

•  All regulators, except for underground version, 

must be protected from direct contact of water 

and corrosive atmosphere due to construction 

materials base with zinc, copper and aluminium 

(cabinet installation recommended). 

•  Recommended installation positions : inlet and/

or outlet in vertical position. 

•  To avoid: vent facing upwards, without protector 

or connector, in humid conditions (risk of water 

penetration due to rain or condensation).

TYPE B NG REGULATOR

DESCRIPTION

Before connecting :

•  Do not weld the inlet and outlet connections with 

the regulator in place. 

•  Remove the protective capsules from the inlet 

and outlet connections. 

•  Ensure that the pipeline is perfectly clean. 

•  Place the O-ring(s), (according to model) 

greasing is recommended.

Connection

•  Respect the gas flow direction indicated on the 

regulator body. 

•  Respect the tightening torques by using a 

dynamometric  wrench  (inlet  with  tight  shutoff 

metal = 40 N

m, others according to O-ring used). 

!

WARNING

Do not re-orientate the regulator after tightening 

connections, under no circumstances should 

the regulator be put under any geometrical or 

dimensional consecutive force between inlet 

and outlet sides.
When connecting the vent (residential areas, 

underground) the diameter used should not be 

inferior to 10 mm and should not be obstructed.

COMMISSIONING OR REARMING

 

1

Close the downstream valve (if existent). Open the 

upstream valve. Press on the green button for a 

few seconds, then release. Open the downstream 

valve (if existent).

Gas Type

Density

Volume 

Weight 

kg/m

3

Pressure 

Setpoint

Nominal Flow

B6

B10

Manufactured gas (n)m

3

/h

• Butane air

• Propane air

1.20

1.15

1.552

1.487

11

11

4

4

7

7

Natural gas (n)m

3

/h

• Group L

• Group H

0.64

0.61

0.827

0.789

27

21

6

6

10

10

LP-gas kg/h

• Propane

1.56

2.017

37

7.2

12