CAUTION
To avoid circuit damage when working with the unit, use appropriate electrostatic
discharge precautions, such as wearing a grounded wrist strap.
CAUTION
During this procedure, all power will be removed from the FloBoss and devices
powered by the FloBoss. Ensure that all connected input devices, output devices,
and processes will remain in a safe state when power is removed from the FloBoss
and also when power is restored to the FloBoss.
NOTE
For a Measurement Canada FloBoss 407, resealing of the case must be performed
by authorized personnel only.
1.
Perform the RAM backup procedure. Refer to Section 2.5.2 on page 2-21.
2.
Disconnect the PWR input connector (terminal block) from the termination board.
NOTE
The FloBoss 407 requires a minimum of 12.5 volts to start up. However, a newer
FloBoss 407 can be restarted below 12.5 volts by depressing the LV START switch
(see Figure 2-10 on page 2-20) while applying power.
3.
Disconnect all connected field wiring, including MVS, built-in inputs, and I/O
modules. This can be done by unplugging the terminal blocks.
4.
Disconnect all communication card and RJ11 wiring if necessary.
5.
Disconnect the ribbon cable at P3 on the termination board.
6.
Disconnect operator interface port wiring on the termination board at P2.
7.
Disconnect the processor board power connector from the termination board at P1.
8.
Remove the five screws securing the termination board, and lift the board out of the case.
9.
Place the new termination board in the case and install the securing screws to the case.
10.
Connect the ribbon cable at P3 on the processor board.
11.
Connect the communication card wiring if required.
12.
Connect the field wiring.
13.
Connect the operator interface port wiring on the termination board at P2.
14.
Connect the processor board power connector to the termination board at P1.
15.
Plug the processor board power supply cord into P1 on the termination board.
16.
Refer to Section 2.5.3, After Installing Components on page 2-22.
Summary of Contents for Fisher FLOBOSS 407
Page 6: ...FloBoss 407 Instruction Manual vi Rev 5 00 This page is intentionally left blank ...
Page 22: ...FloBoss 407 Instruction Manual 1 16 Rev 5 00 This page intentionally left blank ...
Page 134: ...FloBoss 407 Instruction Manual 4 24 Rev 5 00 This page is intentionally left blank ...
Page 184: ...FloBoss 407 Instruction Manual C 8 Rev 5 00 This page is intentionally left blank ...
Page 190: ...FloBoss 407 Instruction Manual G 6 Rev 5 00 This page is intentionally left blank ...
Page 199: ...FloBoss 407 Instruction Manual Rev 5 00 I 9 This page intentionally left blank ...