Instruction Manual Supplement

D104490X012

DVC6200 Digital Valve Controller

January 2020

4

2.2gWhen prompted to run an Auto Travel Calibration select 

No

.

2.3  Place the instrument In Service and close the tag. Then disconnect the digital valve controller.

3. Manually Replace Positioner

  WARNING

Refer to the Installation Warning on page 2.

3.1  Disconnect any operating lines that provide air pressure, electric power, or a control signal to the actuator. Be sure

the actuator cannot suddenly open or close the valve. Remember to note where each line goes for reassembly.

3.2  Confirm the valve assembly is safely locked in position. Do not proceed if the valve assembly has not been safely

locked in position.

3.3  Carefully remove the existing positioner without disturbing the mechanism locking the valve in position

.

3.4  Mount the replacement digital valve controller by following the mounting instructions for sliding-stem valve

assemblies in the DVC6200 Quick Start Guide (

D103566X012

)

.

CAUTION

Valve movement may occur if air is supplied to the digital valve controller during calibration. The Single Point Calibration
process cannot be started if air is supplied to the instrument.

3.5  Attach pneumatic and electrical operating lines to the replacement digital valve controller but 

Do Not Turn On Air

Supply

.

D

 Measure and record the valve assembly’s Observed Travel (%). Observed Travel is the current position of the

valve as a percentage of the actual travel.

4. Run Single Point Calibration

4.1  In ValveLink software, connect to the replacement digital valve controller. Open the tag for your replacement

digital valve controller.

4.2  Initiate 

Single Point 

from the 

Calibration

 menu. Set the device Out of Service if prompted.

4.3  Read the 

Start Screen

 and confirm you have completed the required initial steps for Single Point Calibration. Click

Next

 if you have completed the required steps listed.

4.4  Review the travel configuration information pre-populated by Setup Wizard and/or enter the correct values in the

blanks on the 

Configuration Screen

. Click 

Next

 when all the values are entered correctly.

4.5  Review the tuning information pre-populated by Setup Wizard and/or enter the correct values in the blanks on the

Tuning Screen

. Click 

Next

 when all the values are entered correctly.

4.6  Read the 

Warning Screen

 (figure 1) that describes how to adjust the travel sensor. Click 

OK

 when finished reading

the screen.

Summary of Contents for Fisher FIELDVUE DVC6200 HW2

Page 1: ...cannot be shut down Do not proceed if the valve has a bypass or the process can be shut down The valve will need to be locked at its present position This can be accomplished by using a handwheel or other mechanism If the valve assembly or valve application will not allow you to safely lock the valve in position until this procedure is complete do not proceed with this procedure This procedure can...

Page 2: ...Do not proceed with this procedure until you have obtained a mounting kit compatible with the replacement DVC6200 and the control valve assembly 1 2 Block the valve into position either with a handwheel or other mechanism If you cannot safely lock the valve in position until this procedure is complete do not proceed with this procedure 1 3 Disconnect the operating lines that provide air pressure t...

Page 3: ... if the Tvl Dev Press Fallback setting is exceeded for more than the Tvl Dev Press Fallback Time D Relay Type The relay type is printed on the label affixed to the relay body d A double acting or single acting d B single acting reverse d C single acting direct Note The Single Point Calibration procedure cannot be completed with Pressure Control Do not proceed with this procedure if the Travel Pres...

Page 4: ...alibration process cannot be started if air is supplied to the instrument 3 5 Attach pneumatic and electrical operating lines to the replacement digital valve controller but Do Not Turn On Air Supply D Measure and record the valve assembly s Observed Travel Observed Travel is the current position of the valve as a percentage of the actual travel 4 Run Single Point Calibration 4 1 In ValveLink soft...

Page 5: ...is resupplied Once the travel setpoint matches travel click Next 4 9 Reintroduce instrument air pressure to the digital valve controller The air pressure supplied will be shown on the dial graphic on the Air Screen Once you ve confirmed instrument air has been supplied click Next WARNING Refer to the Installation Warning on page 2 4 10 On the resulting Finish Screen adjust the Travel Setpoint to r...

Page 6: ...ons which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice E 2020 Fisher Controls International LLC All rights reserved Fisher FIELDVUE and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co Emerson Automation Solutions Emerson and th...