Instruction Manual Supplement

D104490X012

DVC6200 Digital Valve Controller

January 2020

2

Installation

  WARNING

Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before proceeding
with any procedures:

D

 Always wear protective clothing, gloves, and eyewear to prevent personal injury or property damage.

D

 Do not remove or uncouple the actuator from the valve while the valve is still pressurized.

D

 The valve will need to be locked at its present position. If you cannot safely lock the valve in position until this procedure

is complete, do not proceed with this procedure.

D

 After the valve has been safely locked in position, disconnect any operating lines providing air pressure, electric power,

or a control signal to the actuator. Be sure the actuator cannot suddenly open or close the valve.

D

 Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.

D

 Check with your process or safety engineer for any additional measures that must be taken to protect against process

media.

1. Lock Valve in Place

1.1  Ensure the mounting kit for the replacement DVC6200 is compatible with the valve assembly. Do not proceed

with this procedure until you have obtained a mounting kit compatible with the replacement DVC6200 and the
control valve assembly.

1.2  Block the valve into position either with a handwheel or other mechanism. If you cannot safely lock the valve in

position until this procedure is complete, do not proceed with this procedure.

1.3  Disconnect the operating lines that provide air pressure to the actuator. Bleed any extra air that may be built up in

the instrument. Please note which air connections go to the actuator and which come from supply for future
reassembly.

1.4  Determine and record the following parameters:

D

 Feedback Connection: The magnetic array type that will be used with the replacement digital valve controller

.

Note

This procedure only supports feedback connections using linear sliding-stem arrays. Do not proceed if you are not using a linear
sliding-stem array.

D

 Travel Sensor Motion: States whether increasing drive signal causes the magnetic assembly to move 

toward the

top of the instrument

 or 

away from the top of the instrument

.

D

 Air (Closes/Opens): States whether adding air 

opens

 or 

closes

 the valve.

D

 Actual Travel: The measured distance from the closed position to the fully open position of the valve

.

2. Configure Replacement Digital Valve Controller Prior to Installation

2.1  Open ValveLink software and connect to the replacement digital valve controller

.

Summary of Contents for Fisher FIELDVUE DVC6200 HW2

Page 1: ...cannot be shut down Do not proceed if the valve has a bypass or the process can be shut down The valve will need to be locked at its present position This can be accomplished by using a handwheel or other mechanism If the valve assembly or valve application will not allow you to safely lock the valve in position until this procedure is complete do not proceed with this procedure This procedure can...

Page 2: ...Do not proceed with this procedure until you have obtained a mounting kit compatible with the replacement DVC6200 and the control valve assembly 1 2 Block the valve into position either with a handwheel or other mechanism If you cannot safely lock the valve in position until this procedure is complete do not proceed with this procedure 1 3 Disconnect the operating lines that provide air pressure t...

Page 3: ... if the Tvl Dev Press Fallback setting is exceeded for more than the Tvl Dev Press Fallback Time D Relay Type The relay type is printed on the label affixed to the relay body d A double acting or single acting d B single acting reverse d C single acting direct Note The Single Point Calibration procedure cannot be completed with Pressure Control Do not proceed with this procedure if the Travel Pres...

Page 4: ...alibration process cannot be started if air is supplied to the instrument 3 5 Attach pneumatic and electrical operating lines to the replacement digital valve controller but Do Not Turn On Air Supply D Measure and record the valve assembly s Observed Travel Observed Travel is the current position of the valve as a percentage of the actual travel 4 Run Single Point Calibration 4 1 In ValveLink soft...

Page 5: ...is resupplied Once the travel setpoint matches travel click Next 4 9 Reintroduce instrument air pressure to the digital valve controller The air pressure supplied will be shown on the dial graphic on the Air Screen Once you ve confirmed instrument air has been supplied click Next WARNING Refer to the Installation Warning on page 2 4 10 On the resulting Finish Screen adjust the Travel Setpoint to r...

Page 6: ...ons which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice E 2020 Fisher Controls International LLC All rights reserved Fisher FIELDVUE and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co Emerson Automation Solutions Emerson and th...

Reviews: