Instruction Manual Supplement

D104490X012

DVC6200 Digital Valve Controller

January 2020

3

2.2  Open the tag for your replacement digital valve controller and run 

Setup Wizard

.

2.2a Initiate the 

Setup Wizard

 

from either the 

Instrument Setup

 

menu or Setup Wizard Icon 

on the toolbar.

2.2b Select the appropriate Travel/Pressure Control Mode and the Relay Type.

D

 Travel/Pressure Control: This defines the operating mode of the instrument as well as the behavior of

the instrument should the travel sensor fail. There are four choices:

d

 Travel Control- The instrument is controlling to a target travel. Fallback is not enabled.

d

 Pressure Control - The instrument is controlling to a target pressure. Fallback is not enabled.

d

 Fallback- Sensor Failure- The instrument will fallback to pressure control if the travel sensor failure

is detected.

d

 Fallback-Sensor / Tvl Deviation - The instrument will fallback to pressure control if the travel sensor

failure is detected, or if the Tvl Dev Press Fallback setting is exceeded for more than the Tvl Dev
Press Fallback Time.

D

 Relay Type: The relay type is printed on the label affixed to the relay body.

d

 A = double-acting or single-acting

d

 B = single-acting, reverse

d

 C = single-acting, direct

Note

The Single Point Calibration procedure cannot be completed with 

Pressure Control

. Do not proceed with this procedure if the

Travel/Pressure Control Mode

 is 

Pressure

.

Travel/Pressure Control Mode

 must be set to 

Travel

 for double-acting actuators.

2.2c Set the desired Pressure Units and the Max Supply Pressure for the application.

2.2d Select the required Actuator Information including: Actuator Make, Actuator Model, Actuator Size, and 

 designate if a Volume Booster or Quick Release Valve is present.

2.2e If prompted, fill out any additional screens (eg: Zero Power Condition, Actuator Style, and Tuning 

 Information)

.

2.2f Select 

Yes

 

when prompted to Use Factory Default Settings.

Note

It is not necessary to run an 

Auto Travel Calibration

 since the digital valve controller will be calibrated with the 

Single Point

Calibration

 feature in future steps and is not currently mounted to a valve assembly.

Summary of Contents for Fisher FIELDVUE DVC6200 HW2

Page 1: ...cannot be shut down Do not proceed if the valve has a bypass or the process can be shut down The valve will need to be locked at its present position This can be accomplished by using a handwheel or other mechanism If the valve assembly or valve application will not allow you to safely lock the valve in position until this procedure is complete do not proceed with this procedure This procedure can...

Page 2: ...Do not proceed with this procedure until you have obtained a mounting kit compatible with the replacement DVC6200 and the control valve assembly 1 2 Block the valve into position either with a handwheel or other mechanism If you cannot safely lock the valve in position until this procedure is complete do not proceed with this procedure 1 3 Disconnect the operating lines that provide air pressure t...

Page 3: ... if the Tvl Dev Press Fallback setting is exceeded for more than the Tvl Dev Press Fallback Time D Relay Type The relay type is printed on the label affixed to the relay body d A double acting or single acting d B single acting reverse d C single acting direct Note The Single Point Calibration procedure cannot be completed with Pressure Control Do not proceed with this procedure if the Travel Pres...

Page 4: ...alibration process cannot be started if air is supplied to the instrument 3 5 Attach pneumatic and electrical operating lines to the replacement digital valve controller but Do Not Turn On Air Supply D Measure and record the valve assembly s Observed Travel Observed Travel is the current position of the valve as a percentage of the actual travel 4 Run Single Point Calibration 4 1 In ValveLink soft...

Page 5: ...is resupplied Once the travel setpoint matches travel click Next 4 9 Reintroduce instrument air pressure to the digital valve controller The air pressure supplied will be shown on the dial graphic on the Air Screen Once you ve confirmed instrument air has been supplied click Next WARNING Refer to the Installation Warning on page 2 4 10 On the resulting Finish Screen adjust the Travel Setpoint to r...

Page 6: ...ons which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice E 2020 Fisher Controls International LLC All rights reserved Fisher FIELDVUE and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co Emerson Automation Solutions Emerson and th...

Reviews: