Quick Start Guide
D103784X012
DVC6005 Digital Valve Controllers
March 2018
25
F
OUNDATION
fieldbus Devices
Refer to the
instruction manual, available at www.Fisher.com or from your
Business Partner, for additional information.
The remote mount base unit is normally powered over the bus from a power supply. Refer to the F
OUNDATION
fieldbus
site planning guide, available from your Emerson Automation Solutions sales office, for proper wire types,
termination, length, grounding practices, etc.
Note
To avoid the valve going to an unknown position when power is applied, the digital valve controller is shipped from the factory
with the transducer block mode Out of Service.
Wire the remote mount base unit as follows, refer to figure 21.
1. Remove the wiring terminal box cap.
2. Bring the field wiring into the terminal box. When applicable, install conduit using local and national electrical codes
which apply to the application.
3. The instrument is not polarity sensitive. Connect one wire from the controller output to one of the LOOP screw
terminals in the terminal box shown in figure 21. Connect the other wire from the controller output to the other
LOOP screw terminal in the terminal box.
Figure 21. Loop Connections Terminal Box
EARTH GROUND
TALK -
TALK +
SAFETY GROUND
LOOP +
LOOP -
X0438