Quick Start Guide
D103784X012
DVC6005 Digital Valve Controllers
March 2018
13
Refer to figure 11. The travel indicator assembly can have a starting position of 7:30 or 10:30. Determine the desired
starting position then proceed with the next step. Considering the top of the remote travel sensor as the 12 o'clock
position, in the next step attach the travel indicator, so that the pin is positioned as follows:
D
If increasing pressure from the digital valve controller output A rotates the digital valve controllers
potentiometer shaft clockwise (as viewed from the back of the instrument)
, mount the travel indicator assembly
such that the arrow is in the 10:30 position, as shown in figure 11.
D
If increasing pressure from the digital valve controller output A rotates the digital valve controllers
potentiometer shaft counterclockwise (as viewed from the back of the instrument)
, mount the travel indicator
assembly such that the arrow is in the 7:30 position, as shown in figure 11.
Figure 11. FIELDVUE DVC6035 Travel Indicator Installation
STARTING POSITION OF THE TRAVEL INDICATOR ASSEMBLY IF
INCREASING PRESSURE FROM OUTPUT A DRIVES THE INDICATOR
CLOCKWISE. THE POTENTIOMETER SHAFT WILL ROTATE
COUNTERCLOCKWISE AS VIEWED FROM THE BACK OF THE
INSTRUMENT.
STARTING POSITION OF THE TRAVEL INDICATOR ASSEMBLY
IF INCREASING PRESSURE FROM OUTPUT A DRIVES THE
INDICATOR COUNTERCLOCKWISE. THE POTENTIOMETER
SHAFT WILL ROTATE CLOCKWISE AS VIEWED FROM THE
BACK OF THE INSTRUMENT.
ACTUATOR SHAFT MOVEMENT
ACTUATOR SHAFT MOVEMENT
DVC6035 FEEDBACK
ARM MOVEMENT
DVC6035 FEEDBACK
ARM MOVEMENT
NOTE: DVC6035 TRAVEL COUNTS (COUNTERCLOCKWISE) = 600
200
NOTE: DVC6035 TRAVEL COUNTS (CLOCKWISE) = 3400
200
Note
ValveLink software and the Field Communicator use the convention of clockwise and counterclockwise when viewing the
potentiometer shaft from the back of the FIELDVUE instrument (figure 11).
5. Attach the travel indicator, to the shaft connector or spacer as described in the mounting kit instructions.