Instruction Manual Supplement
D103266X012
DVC5000 Digital Valve Controller
May 2018
12
Command 15: Read Primary Variable Output Information
This command returns the upper/lower range values for the measured Valve Travel.
The range values can be changed via Command 35.
Byte
Format
Description
Returned Value
Request
Data bytes
None
Response
Data
Bytes
0
Enum
PV Alarm Selection Code (see Common Table 6, Alarm
Selection Codes). The Alarm Selection Code indicates the
action taken by the device under error conditions. For
Actuators, the action taken by the positioner is indicated.
250 (Not Used)
1
Enum
PV Transfer Function Code (see Common Table 3, Transfer
Function Codes). The Transfer Function Code must return
“0”, Linear, if transfer functions are not supported by the
device.
250 (Not Used)
2
Enum
AI Upper and Lower Range Values Units Code
57 (%)
3-6
Float
AI Upper Range Value
42C80000
7-10
Float
AI Lower Range Value
00000000
1114
Float
PV Damping Value
250 (Not Used)
15
Enum
Write Protect Code
0 or 1
16
Enum
Reserved
Code
Class
Description
Response
Codes
None