67D Series

4

a regulator may vent some gas to the 

atmosphere.  in hazardous or flammable

gas service, vented gas may accumulate 

and cause personal injury, death, or   

property damage due to fire or explosion. 

Vent a regulator in hazardous gas service 

to a remote, safe location away from air                            

intakes or any hazardous area.  The vent 

line or stack opening must be protected 

against condensation or clogging.

Before installing a Type 67D, 67DR, 67DS, 67DSR, 

67DF, 67DFR, 67DFS, or 67DFSR regulator, be 

sure the installation complies with the following 

installation guidelines:

  1.  Regulator operation within ratings does not           

       preclude the possibility of damage from debris in  

       the lines or from external sources.  Regulators  

       should be inspected for damage periodically and  

       after any overpressure condition.

  2.  Only personnel qualified through training and  

       experience should install, operate, and maintain  

       the regulator.  Make sure that there is no damage  

       to or foreign material in the regulator.  Also            

       ensure that all tubing and piping is free of debris.

  3.  Install the regulator so that flow is from the IN to  

       the OUT connection as marked on the regulator body.

  4.  A clogged spring case vent hole may cause the  

       regulator to function improperly.  To keep this vent  

       hole from being plugged (and to keep the spring  

       case from collecting moisture, corrosive chemicals,  

       or other foreign material) orient the vent to the    

       lowest possible point on the spring case or 

       otherwise protect it. 

Table 1.  Outlet Pressure Ranges and Control Spring Data

TyPeS

ouTleT PReSSuRe 

RangeS, PSig (bar)

ConTRol SPRing DaTa

Part number

Color

Material

Wire Diameter, inch (mm) Free length, inch (mm)

67D, 67DR,  

67DF, 67DFR

0 to 20

0 to 35 

 0 to 60 

0 to 125

 (0 to 1,4)

 (0 to 2,4)

 (0 to 4,1)

 (0 to 8,6)

GE07809T012

T14059T0012

T14058T0012

T14060T0012

Green stripe

Unpainted

Blue stripe

Red stripe

Music Wire

0.135

0.156

0.170

0.207

 

(3,43)

 (3,96)

 (4,32)

 (5,26)

1.43

1.43

1.43

1.43

 (36,2)

 (36,2)

 (36,2)

 (36,2)

0 to 35 

 0 to 60 

0 to 125

 (0 to 2,4)

 (0 to 4,1)

 (0 to 8,6)

T14113T0012

T14114T0012

T14115T0012

Silver stripe

Blue

Red

Inconel

®

0.156

0.172

0.207

 (3,96)

 (4,37)

 (5,26)

1.43

1.43

1.43

 (36,2)

 (36,2)

 (36,2)

67DS, 67DSR, 

67DFS, 

67DFSR

0 to 20

0 to 35 

 0 to 60 

0 to 125

0 to 150

 (0 to 1,4)

 (0 to 2,4)

 (0 to 4,1)

 (0 to 8,6)

 (0 to 10,3)

10C1729X012

T14113T0012

T14114T0012

T14115T0012

10C1730X012

Green

Silver stripe

Blue

Red

Black

Inconel

®

0.135

0.156

0.172

0.207

0.250

 (3,43)

 (3,96)

 (4,37)

 (5,26)

 (6,35)

1.50

1.43

1.43

1.43

1.77

 (38,1)

 (36,2)

 (36,2)

 (36,2)

 (44,9)

installation

 

 

 

note

if the regulator is shipped mounted on 

another unit, install that unit according to 

the appropriate instruction Manual.

!

WaRning

Personal injury, property damage, 

equipment damage, or leakage due to 

escaping gas or bursting of pressure-

containing parts may result if this 

regulator is overpressured or is installed 

where service conditions could exceed 

the limits given in the Specifications 

section, or where conditions exceed any 

ratings of the adjacent piping or piping 

connections.  To avoid such injury or 

damage, provide pressure-relieving or 

pressure-limiting devices (as required 

by the appropriate code, regulation, or 

standard) to prevent service conditions 

from exceeding those limits. 

The internal relief valve of the 

Type 67DR, 67DSR, 67DFR, or 67DFSR 

does not provide full overpressure 

protection.  The internal relief valve is 

designed for minor seat leakage only.  if 

maximum inlet pressure to the regulator 

exceeds maximum pressure ratings of 

the downstream equipment or exceeds 

maximum allowable outlet pressure of 

the regulator, additional overpressure 

protection is required. 

Inconel

®

 is a mark owned by Special Metals Corporation

Summary of Contents for Fisher 67D Series

Page 1: ... unit may be required Failure to correct trouble could result in a hazardous condition Installation operation and maintenance procedures performed by unqualified Introduction Scope of the Manual This manual provides instructions for the installation maintenance and parts ordering information for 67D Series regulators Instructions and parts lists for other equipment mentioned in this instruction ma...

Page 2: ... Standard Bolting 20 to 180 F 29 to 82 C Stainless Steel Bolting 40 to 180 F 40 to 82 C With Fluorocarbon FKM Polyethylene Filter 4 Standard 0 to 180 F 18 to 82 C Polyvinylidene PVDF SST or Glass Filter Optional 0 to 300 F 18 to 149 C With Silicone VMQ 2 Diaphragm Low Temperature Nitrile NBR O rings and Low Temperature Bolting 60 to 180 F 51 to 82 C With Gauges 20 to 180 F 29 to 82 C With Automati...

Page 3: ...ugh the regulator When demand increases downstream pressure drops slightly allowing the spring to extend moving the stem down and the valve plug away from the orifice This allows flow through the regulator Internal Relief Types 67DR 67DSR 67DFR and 67DFSR If for some reason outside of normal operating conditions the downstream pressure exceeds the setpoint of the regulator the force created by the...

Page 4: ...0 to 1 4 0 to 2 4 0 to 4 1 0 to 8 6 GE07809T012 T14059T0012 T14058T0012 T14060T0012 Green stripe Unpainted Blue stripe Red stripe Music Wire 0 135 0 156 0 170 0 207 3 43 3 96 4 32 5 26 1 43 1 43 1 43 1 43 36 2 36 2 36 2 36 2 0 to 35 0 to 60 0 to 125 0 to 2 4 0 to 4 1 0 to 8 6 T14113T0012 T14114T0012 T14115T0012 Silver stripe Blue Red Inconel 0 156 0 172 0 207 3 96 4 37 5 26 1 43 1 43 1 43 36 2 36 ...

Page 5: ...8 1 With proper installation completed and downstream equipment properly adjusted slowly open the upstream and downstream block valve when used while using pressure gauges to monitor pressure Warning To avoid personal injury property damage or equipment damage caused by bursting of pressure containing parts or explosion of accumulated gas never adjust the control spring to produce an outlet pressu...

Page 6: ...y 4 Place the diaphragm assembly key 16 on the body key 1 as shown in Figure 3 or 4 Push down on the diaphragm assembly to make sure the valve plug key 57 strokes smoothly and approximately 1 16 inch 1 6 mm Note In step 5 if installing a control spring of a different range be sure to delete the spring range originally appearing on the label and indicate the new spring range 5 Stack the control spr...

Page 7: ...x spring case screws key 3 using a crisscross pattern and torque to 15 to 30 inch pounds 1 7 to 3 4 N m Note On Types 67DFS and 67DFSR lubricate the adjusting screw key 18 thread to reduce galling of stainless steel 7 When all maintenance is complete refer to the Startup and Adjustment section to put the regulator back into operation and adjust the pressure setting Tighten the locknut key 19 if us...

Page 8: ...luminum Manual GE34605X012 Auto drain GE34606X012 for Type 67DFS or 67DFSR Stainless steel Manual GE34607X012 Auto drain GE31792X012 6 Filter Element for Types 67DF 67DFR 67DFS and 67DFSR Polyethylene 5 microns standard GE31794X012 Glass fiber 5 microns GE31795X012 Polyvinylidene fluoride PVDF 40 microns GE31794X022 Stainless steel 40 microns GE31809X012 7 Spring Case for Type 67D 67DR 67DF or 67D...

Page 9: ... T14061T0012 Handwheel T14102T0012 Wire seal not shown T14104T0012 Key Description Part Number 18 Adjusting Screw for Type 67D 67DR 67DF or 67DFR continued For spring case with 1 4 NPT vent Square head for closing cap Stainless steel T14101T0012 Handwheel Zinc plated steel T14103T0012 Wire seal not shown Steel T14198T0012 for Type 67DS 67DSR 67DFS or 67DFSR Square head with or without closing cap ...

Page 10: ... 9 2 19 7 45 50 11 58 57 3 66 49 48 5 65 18 19 31 Figure 7 67D Series Optional Panel Mount 40C1728_A Figure 6 Type 67DFS or 67DFSR Assembly GE31805_B GE31784_C position 1 Aligned with inlet standard position 3 position 2 position 4 33 18 20 17 3 16 1 15 L L L L L 12 2 6 9 2 19 7 45 50 11 58 57 3 66 49 48 5 65 18 19 31 ...

Page 11: ...nly Available with the 1 4 inch 6 4 mm Spring Case Vent B2698 Figure 11 Automatic Drain Option for Type 67DF 67DFR 67DFS or 67DFSR Figure 9 Key 16 Diaphragm Assembly RETAINING RING PUSHER POST WITHOUT RELIEF LOWER SPRING SEAT DIAPHRAGM PLATE PUSHER POST WITH RELIEF DIAPHRAGM B2696 L L 2 18 19 31 apply lubricant L ...

Page 12: ...ion visit www fisherregulators com Key Description Part Number 22 Pressure Gauge not shown for Types 67D 67DR 67DF and 67DFR Brass 0 to 30 psig 0 to 2 1 bar 0 to 0 2 MPa 11B8579X022 0 to 60 psig 0 to 4 1 bar 0 to 0 4 MPa 11B8579X032 0 to 160 psig 0 to 11 0 bar 0 to 1 1 MPa 11B8579X042 for All Stainless Steel 0 to 30 psig 0 to 2 1 bar 0 to 0 2 MPa 11B9639X012 0 to 60 psig 0 to 4 1 bar 0 to 0 4 MPa ...

Reviews: