Instruction Manual

D103195X012

Inline and Vent Diffusers

December 2011

3

Principle of Operation

Inline and vent diffusers are custom designed to match a wide range of valve outlet and/or pipeline size. Furthermore

these diffusers are selected to match the application specific conditions including temperature, pressure, and flow

capacity. The flexibility of the diffuser types and placement provide a range of installation possibilities. The diffuser is

not required to be installed adjacent to the control valve.

The 6010 is an inline diffuser that fits between two different sizes of pipe to meet both downstream and upstream pipe

sizes with an integral outlet head. The 6011 is a pipe-style inline diffuser that extends into existing pipe using a wafer

flange connection. The Whisper Disk is a flat plate-style inline diffuser that is available with a raised-face flanged

connection. The 6012, 6013, 6014, and 6015 are vent diffusers that are designed to reduce noise during process

venting applications.

Piping Considerations

Upstream piping should be the same nominal diameter as the diffuser inlet connection and vice versa.

The drilled hole pattern of the Whisper Disk inline diffuser must be within the inside diameter of the mating flange

schedule.

Reducers or elbows are not recommended downstream unless they are at least four to five downstream pipe

diameters downstream of the diffuser outlet.

Installation

Before installation, all piping to the diffuser must be blown clean, so that no particles, such as welding beads, dirt or

other foreign matter, are left in the pipeline. Keep foreign matter away from the line openings while preparing the

diffuser for installation.

CAUTION

Cleanliness of the upstream piping is critical. Debris in the piping can damage the diffuser and severely restrict flow, causing

overpressure.

Inspect the inside of the diffuser and clean if necessary.

Arrange a lifting sling around the diffuser to safely place it into the mounting position.

Note

To avoid flow interaction and reduce noise in 6012, 6013, 6014, and 6015 vent diffuser applications, do not install diffusers in close
proximity to support structures and ensure that adjacent diffusers are installed at different heights.

Summary of Contents for Fisher 6010

Page 1: ...Operation 3 Piping Considerations 3 Installation 3 Maintenance 4 Servicing 4 Troubleshooting 4 Parts Ordering 5 Figure 1 Typical Fisher Inline and Vent Diffusers W1155 2 W1162 2 W4888 6011 6010 WHISPER DISK W7353 X0002 6014 WhisperFlo VENT DIFFUSER 6012 X0347 Instruction Manual D103195X012 Inline and Vent Diffusers December 2011 ...

Page 2: ...Inline and vent diffusers are not hydrostatically tested Introduction Scope of Manual This instruction manual includes operation installation and maintenance information for the following diffusers D 6010 6011 and Whisper Disk Inline Diffusers See figure 1 D 6012 and 6013 drilled hole vent diffusers See figures 2 and 3 D 6014 and 6015 WhisperFlo disc style vent diffusers See figures 4 and 5 Do not...

Page 3: ...iping Considerations Upstream piping should be the same nominal diameter as the diffuser inlet connection and vice versa The drilled hole pattern of the Whisper Disk inline diffuser must be within the inside diameter of the mating flange schedule Reducers or elbows are not recommended downstream unless they are at least four to five downstream pipe diameters downstream of the diffuser outlet Insta...

Page 4: ...rtant to inspect the diffuser for damaged or cracked welds exclusive of the Whisper Disk diffuser Your local Emerson Process Management Instrument and Valve Services office can help determine the correct course of action if damage is present The diffuser is normally welded or bolted in line and not removed unless it requires cleaning or replacement due to damage or wear In the event the diffuser i...

Page 5: ... to the serial number when contacting your Emerson Process Management sales office for technical assistance WARNING Use only genuine Fisher replacement parts Components that are not supplied by Emerson Process Management should not under any circumstances be used in any Fisher valve because they may void your warranty might adversely affect the performance of the valve and could cause personal inj...

Page 6: ...Instruction Manual D103195X012 Inline and Vent Diffusers December 2011 6 Figure 2 Fisher 6012 Vent Diffuser W8682 1 Figure 3 Fisher 6013 Vent Diffuser W8683 1 ...

Page 7: ...Instruction Manual D103195X012 Inline and Vent Diffusers December 2011 7 Figure 4 Fisher 6014 Vent Diffuser W8798 1 Figure 5 Fisher 6015 Vent Diffuser W8799 1 ...

Page 8: ...hich are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice E 2004 2011 Fisher Controls International LLC All rights reserved Fisher and WhisperFlo are marks owned by one of the companies in the Emerson Process Management business division of Emerson Electric Co Emerson Process Management Emerson and the Emerso...

Reviews: