ATEX (4211 and 4221)
Special Conditions for Safe Use
Intrinsically Safe, Dust
This equipment is intrinsically safe and can be used in potentially explosive atmospheres.
The apparatus must only be connected to a certified associated intrinsically safe equipment and this combination
must be compatible as regards intrinsic safety rules.
The electrical parameters of the associated intrinsically safe equipment must not exceed any of the following values:
Uo
v
30 V, lo
v
150mA, Po
v
1W
Maximal ambient temperature: -40
_
C to +71
_
C.
Temperature classification is as follows: T5 at Ta
v
+ 40
_
C ; T4 at Ta
v
+ 71
_
C
The enclosure of the equipment must not be submitted to mechanical impact or friction.
Refer to table 7 for additional approval information, and figure 27 for ATEX approval nameplates.
Type n, Dust
No special conditions for safe use.
Refer to table 7 for approval information, and figure 27 for ATEX approval nameplates.
Table 7. Hazardous Area Classifications—ATEX
Certificate
Type
Certification Obtained
Entity Rating
Temperature Code
Enclosure Rating
ATEX
4211, 4221
II 1 G D
Intrinsically Safe
Gas
Ex ia IIC T4/T5
Ui = 30 VDC
Ii = 150 mA
Pi = 1.0 W
Ci = 5 nF
Li = 0 mH
T4 (Tamb
v
71
°
C)
T5 (amb
v
40
°
C)
IP66
Dust
Ex tD A20 IP66 T81
°
C (Tamb
v
71
°
C)
Ex tD A20 IP66 T50
°
C (Tamb
v
40
°
C)
- - -
II 3 G D
Type n
Gas
Ex nL IIC T4
- - -
T4 (Tamb
v
71
°
C)
IP66
Dust
EX tD A22 IP66 T81
°
C (Tamb
v
71
°
C)
- - -
Mechanical Connections
Sliding‐Stem Actuator Mounting, 4210, 4211, 4212, and 4215
Use the following general procedures and figures 15, 16, 17, and 18 to mount the transmitter on sliding‐stem
actuators, standard stroke up to 105 mm (4.125 inches) travel.
Refer to figure 15 for key number locations for this example.
1. Install the transmitter on the mounting plate (key 21) with two cap screws (key 32).