Table 1‐3. Process Sensor (Capsular Element) Pressure Ratings
CAPSULE
MATERIAL
CAPSULAR
STANDARD RANGES
SPAN
OPERATING RANGE
OPERATING
LIMIT
Min
Max
Min
Max
N09902
Metric units
Positive pressure
0 to 150 mbar
0 to 400 mbar
0 to 0.6 bar
0.2 to 1 bar
0 to 1 bar
100 mbar
350 mbar
0.35 bar
0.4 bar
0.5 bar
160 mbar
700 mbar
0.7 bar
0.8 bar
1 bar
-350 mbar
-1 bar
-1 bar
-1 bar
-1 bar
350 mbar
1 bar
1 bar
1.4 bar
1.4 bar
510 mbar
1.5 bar
1.5 bar
2 bar
2 bar
0 to 1.4 bar
0 to 1.6 bar
0.4 to 2 bar
0 to 2 bar
0.7 bar
1 bar
0.8 bar
1 bar
1.4 bar
2 bar
1.6 bar
2 bar
-1 bar
-1 bar
-1 bar
-1 bar
1.7 bar
2.4 bar
2 bar
2.4 bar
2.5 bar
3.5 bar
3 bar
3.5 bar
Vacuum
-150 to 0 mbar
-340 to 0 mbar
-400 to 0 mbar
-0.6 to 0 bar
-1 to 0 bar
85 mbar
170 mbar
350 mbar
0.35 bar
0.5 bar
170 mbar
340 mbar
700 mbar
0.7 bar
1 bar
-350 mbar
-480 mbar
-1 bar
-1 bar
-1 bar
350 mbar
480 mbar
1 bar
1 bar
1.4 bar
510 mbar
724 mbar
1.5 bar
1.5 bar
2 bar
Compound
-50 to 100 mbar
-175 to 175 mbar
-150 to 250 mbar
-0.2 to 0.4 bar
100 mbar
175 mbar
350 mbar
0.35 bar
160 mbar
350 mbar
700 mbar
0.7 bar
-350 mbar
-480 mbar
-1 bar
-1 bar
350 mbar
480 mbar
1 bar
1 bar
510 mbar
724 mbar
1.5 bar
1.5 bar
-0.4 to 0.6 bar
-0.6 to 0.8 bar
-1 to 0.6 bar
-1 to 1 bar
0.5 bar
0.7 bar
1 bar
1 bar
1 bar
1.4 bar
2 bar
2 bar
-1 bar
-1 bar
-1 bar
-1 bar
1.4 bar
1.7 bar
2.4 bar
2.4 bar
2 bar
2.5 bar
3.5 bar
3.5 bar
U.S. units
Positive pressure
0 to 60 inch wc
0 to 5 psig
0 to 10 psig
3 to 15 psig
0 to 15 psig
40 inch wc
2.5 psig
5 psig
6 psig
7.5 psig
60 inch wc
5 psig
10 psig
12 psig
15 psig
-10 inch Hg
-14 inch Hg
-30 inch Hg
-30 inch Hg
-30 inch Hg
5 psig
7 psig
15 psig
20 psig
20 psig
7.5 psig
10.5 psig
22.5 psig
30 psig
30 psig
0 to 20 psig
6 to 30 psig
0 to 30 psig
10 psig
12 psig
15 psig
20 psig
24 psig
30 psig
-30 inch Hg
-30 inch Hg
-30 inch Hg
25 psig
30 psig
35 psig
37.5 psig
45 psig
52.5 psig
Vacuum
-5 to 0 inch Hg
-10 to 0 inch Hg
-20 to 0 inch Hg
-30 to 0 inch Hg
2.5 inch Hg
5 inch Hg
10 inch Hg
15 inch Hg
5 inch Hg
10 inch Hg
20 inch Hg
30 inch Hg
-10 inch Hg
-14 inch Hg
-30 inch Hg
-30 inch Hg
5 psig
7 psig
15 psig
20 psig
7.5 psig
10.5 psig
22.5 psig
30 psig
Compound
-30 to 30 inch wc
-5 inch Hg to 2.5 psig
-10 inch Hg to 5 psig
40 inch wc
2.5 psig
5 psig
60 inch wc
5 psig
10 psig
-10 inch Hg
-14 inch Hg
-30 inch Hg
5 psig
7 psig
15 psig
7.5 psig
10.5 psig
22.5 psig
-15 inch Hg to 7.5 psig
-20 inch Hg to 10 psig
-30 inch Hg to 15 psig
7.5 psig
10 psig
15 psig
15 psig
20 psig
30 psig
-30 inch Hg
-30 inch Hg
-30 inch Hg
20 psig
25 psig
35 psig
30 psig
37.5 psig
52.5 psig
1. Minimum or maximum span, or any span in between, may be positioned anywhere within the operating range. For example, if a 0 to 350 mbar (0 to 5 psig) sensing element is used and the
minimum span of 1.75 mbar (2.5 psig) is set, the process indication can be calibrated to a range of -340 mbar to -203 mbar (-10 inch Hg to -6 inch Hg), 0 to 172 mbar (0 to 2.5 psig),
172 to 345 mbar (2.5 to 5 psig), 305 to 480 mbar (4.5 to 7 psig), or any value between minimum and maximum values of operating range.
2. Capsules with the travel stops set may be pressured to this value without permanent zero shift.