Instruction Manual
D100279X012
262K Filter
September 2019
2
Table 1. Specifications
Body Size
NPS 3/4
End Connection Styles
3/4 NPT screwed
Flow Coefficients
C
v
:
3.96
Maximum Inlet and Outlet Pressure
Capabilities
Cast Iron:
28 bar at 65
_
C (400 psig at 150
_
F)
Stainless Steel:
41 bar at 65
_
C (600 psig at 150
_
F)
Temperature Capabilities
Cast Iron:
-28 to 208
_
C (-20 to 406
_
F)
Stainless Steel:
-54 to 208
_
C (-65 to 406
_
F)
Clean Out Connection
Screwed
Hazardous Area Classification
Complies with the requirements of ATEX Group II
Category 2 Gas and Dust
Ex h IIC Tx Gb
Ex h IIIC Tx Db
Maximum surface temperature depends on operating
conditions
Gas:
T6...T2
Dust:
T85...T208
1. The pressure/temperature limits in this instruction manual and any applicable standard or code should not be exceeded.
2. A pressure exceeding this value can cause failure of, or leakage from, pressure‐containing components.
Specifications
Specifications for the 262K filter are in table 1.
WARNING
Installation, operation, and maintenance procedures performed by unqualified personnel may result in unsafe operation.
This condition may result in personal injury or equipment damage. Use qualified personnel when installing, operating, and
maintaining this filter.
If a leak develops in the system, the escaping gas may accumulate and become a fire or explosion hazard. Immediately call
qualified service personnel in case of trouble.
Installation
WARNING
Personal injury, equipment damage, or leakage due to escaping gas or bursting of pressure‐containing parts may result if
the filter is installed where its capabilities can be exceeded or where conditions exceed any ratings of the adjacent piping or
piping connections. To avoid this, install a filter where:
D
Service conditions are within unit capabilities.
D
Service conditions are within applicable codes, regulations, or standards.
D
Additionally, physical damage to the filter could result in breakage, causing personal injury and property damage due to
escaping gas. To avoid such injury or damage, install the unit in a safe location.
D
Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.