Installation

 

  

WARNING 

 

Overpressuring a regulator or 
associated equipment may cause 
leakage, part damage or personal injury 
due to bursting of pressure containing 
parts or explosion of accumulated gas. 
Do not install a regulator where service 
conditions can exceed the specifications 
listed on the Specifications section, or 
any applicable local, state or federal 
codes and regulations.

 

 

Use qualified personnel when installing, operating and 
maintaining these regulators. Make sure that there

 

is no damage or foreign material in the regulator and 
that all tubing and piping are clean and unobstructed. 
The regulator may be installed in any position. Apply 
pipe compound to the pipeline threads. Connect inlet 
piping or tubing to the 1/4 NPT connection marked 
“In” and outlet piping or tubing to one of the 1/4 NPT 
connections marked “Out”. Install a pressure gauge or 
pipe plug in the unused outlet connections.

 

If continuous operation of the system is required 
during inspection or maintenance, install a three-valve 
bypass around the regulator.

 

 

  

WARNING 

 

 

A regulator may vent  some  gas  to 
the atmosphere. In hazardous gas 
service, vented gas may  accumulate,

 

causing personal injury or equipment 
damage due to  fire  or  explosion. Vent a 
regulator in hazardous gas service to  a 
remote, safe location.

 

 

The optional stainless steel spring case of the 
Type 1301F regulator has one 1/4 NPT internal 
connection. The Type 1301G regulator spring case

 

has one 1/8 NPT internal connection with a screen. To 
remotely vent the spring case, remove the screen, if 
present, and connect 1/4 or 1/8 NPT piping or tubing 
to the spring case connection. The piping or tubing 
should vent the spring case to a safe location, have as

 

few bends as possible, and have a screened vent on its

 

exhaust end.

 

Each regulator is factory-set for the pressure setting 
specified on the order. If no setting is specified, outlet 
pressure is factory-set at the midpoint of the regulator 
spring range. If pressure adjustment is necessary, refer

 

to the Startup section. In all cases, check the spring 
setting to make sure it is correct for the application.

 

 

Overpressure Protection

 

The 1301 Series regulators have an outlet pressure 
rating lower than their inlet pressure rating. If actual 
inlet pressure can exceed the outlet pressure rating, 
outlet overpressure protection is necessary. However, 
overpressuring any portion of the regulators beyond 
the limits in Specifications section may cause leakage, 
damage to regulator parts or personal injury due to 
bursting of pressure-containing parts.

 

Some type of external overpressure protection should be 
provided if inlet pressure will be high enough to damage 
downstream equipment. Common methods of external 
overpressure protection include relief valves, monitoring 
regulators, shutoff devices and series regulation.

 

If the regulator is exposed to an overpressure 
condition, it should be inspected for any damage that 
may have occurred. Regulator operation below these 
limits does not preclude the possibility of damage from 
external sources or from debris in the pipeline.

 

 

Startup

 

With installation completed and downstream 
equipment adjusted, slowly open the upstream and 
downstream block valves while using pressure gauges 
to monitor pressure.

 

If adjustment is necessary, loosen  the  locknut 
(key 18, Figures 3 and 4), and turn the adjusting 
screw (key 15, Figures 3 and 4) clockwise to 
increase the set pressure or counterclockwise to 
decrease the set pressure. Monitor pressure with 
gauges during adjustment. When adjustment is 
complete, tighten the locknut. If the desired outlet 
pressure is not within the range of the regulator 
spring, install a spring with a desired range 
according to the Maintenance  section.

 

 

Shutdown

 

First, close the upstream shutoff valve, and then, 
close the downstream shutoff valve. Next, open  
the vent valve between the regulator and the 
downstream shutoff valve and open the vent valve 
between the regulator and the upstream shutoff 
valve. If vent valves are not installed, safely bleed 
off both inlet and outlet pressures and check that  
the regulator contains no  pressure.

 

 

Maintenance

 

Summary of Contents for Fisher 1301 Series

Page 1: ...in equipment damage or personal injury Use qualified personnel when installing operating and maintaining the 1301 Series high pressure regulator Introduction Scope of the Manual This Instruction Manual provides instructions for the installation adjustment maintenance and parts ordering of the Types 1301F and 1301G high pressure regulators Product Description Types 1301F and 1301G regulators are di...

Page 2: ...r Liquid Polytetrafluoroethylene PTFE Disk 1000 psig 69 0 bar Nylon PA Disk Water 1000 psig 69 0 bar Other Liquids 2000 psig 138 bar Outlet Pressure Ranges See Table 1 Maximum Emergency Outlet Pressure 1 Type 1301F 250 psig 17 2 bar Type 1301G 550 psig 37 9 bar Wide Open Flow Coefficients for Relief Valve Sizing Cg 5 0 Cv 0 13 C1 38 5 IEC Sizing Coefficients XT 0 938 FD 0 50 FL 0 85 Recovery Coeff...

Page 3: ... 6 17 1301G 200 to 500 13 8 to 34 5 Silver 1K156027142 0 331 8 41 0 88 22 4 1 All springs can be backed off to 0 psig 0 bar Principle of Operation The 1301 Series regulators are direct operated Downstream pressure is registered internally through the body to the underside of the diaphragm When downstream pressure is at or above set pressure the disk is held against the orifice and there is no flow...

Page 4: ...d outlet pressure is factory set at the midpoint of the regulator spring range If pressure adjustment is necessary refer to the Startup section In all cases check the spring setting to make sure it is correct for the application Overpressure Protection The 1301 Series regulators have an outlet pressure rating lower than their inlet pressure rating If actual inlet pressure can exceed the outlet pre...

Page 5: ...e halves are a matched set and need to be kept together 10 Unscrew the orifice key 5 Examine seating edge of orifice Replace with a new part if worn or nicked Assembly This procedure assumes that the regulator was completely disassembled If not start these instructions at the appropriate step Key numbersused are shown in Figure 3 for the Type 1301F regulator and in Figure 4 for the Type 1301G regu...

Page 6: ...l com 6 22 10 NOTE OPTIONAL THIRD OUTLET Figure 3 Type 1301F High Pressure Regulator Assembly 15 2 18 11 9 19 8 16 7 21 1 12 4 13 17 14 5 3 BP6341 A CN7095_C Figure 4 Type 1301G High Pressure Regulator Assembly Figure 5 Exploded View of The DiaphragmHead Assembly and Yoke 15 18 2 9 11 8 19 7 16 17 1 12 13 4 14 5 3 6 22 10 CD3923_F 19 8 7 13 17 4 40 S 20 ...

Page 7: ...pring 1D387325072 1K155725072 1B798525062 1K155828982 1 Body 1 4 NPT Connection 302 Stainless steel Inconel X750 NACE 1D387137022 15A3522X012 Brass 2 outlet port 39A1342X012 11 Spring Zinc plated steel Brass 3 outlet port CF8M Stainless steel 2 outlet port ERAA00584A0 32B4291X022 Type 1301F 0 to 75 psig 0 to 5 2 bar Blue 1D387227022 CF8M Stainless steel 3 outlet port 1 4 x 1 2 in Flanged Connectio...

Page 8: ...eel Use with key 32 Not shown 1C631224052 Use with Stainless steel yoke only 1J926035072 34 Bracket Mounting Washer 22 Valve Disk Collar Use with key 32 Not shown T12861T0012 304 Stainless steel 1D468635032 35 NACE Tag 316 Stainless steel NACE 1D4686X0012 Use with NACE unit Not shown 24 Handwheel Not shown 36 Tag Wire Type 1301F 1L217544992 Use with key 35 Not shown 26 Vent Screen Not shown 38 Bod...

Reviews: