AGL_Sol_EV3_E_Rev_01
17
Code Description and comments
G
Programming port:
▪
Used for software updates via Renesas Emulators together with a special PCB board
from Emerson
H
Status LED (green):
▪
Flashing fast:
Fault state
▪
Flashing slow: Standby
▪
Constantly on:
Compressor running / heating
I
Not used
J
Not used
K
Used to select the type of feedback on port B:
▪
Without jumper (variable duty cycle [%]):
0: ......... Tripped
100: .... OK
▪
With jumper (variable duty cycle [%]):
0: .......... Error (general error, miswiring)
25: ....... Wrong compressor code (power cycle needed)
50: ....... Standby
(waiting for enable and 0…10 V signal)
75: ........ SDP mode (Speed-Drop-Protection mode)
100: ...... Running or heating mode
L
Used for selection of the compressor speed range:
▪
Without bridge between pin 1 and 3
o
Limited speed range in normal operation (Mode 0: Full Envelope Protection selected
– see paragraph 4.4
for more details)
▪
Bridge between pin 1 and 3
o
Full speed range in normal operation (Mode 1: High Speed Envelope Protection
selected
– see paragraph 4.4
for more details)
M
7-segment display:
▪
Displaying status, speed, error code, software version
Table 13: Terminals and LED's of the analog control board
5.2
Control and configuration
5.2.1 Selection of drive compressor code
The drive compressor code must be selected by a 6-digit binary coded DIP-switch which has to be
done before connecting to the drive. In case of a wrong configuration the 7-Segment Display shows
the error code E-39. The PWM output shows a duty cycle of 25%. In this case a power cycle is
needed to reset this fault. The DIP-switch will only be analysed once after a power cycle. During the
start-up cycle the 7-segment display will show the compressor as per the DIP-switch configuration
–
see
Table 14
.
ZPV066-4X9
ZPV096-4X9
Package code
44
45
Binary code
001101
101101
Nixie tube
C044
C045
Table 14: Package codes for ZPV/ compressors
The binary code reflects the DIP-switch positions from left to right (from 1 to 6), "1" meaning ON state
for the switch, "0" meaning OFF state for the switch.
Example:
▪
Drive version:
EV3185B-K1-294
▪
Compressor version: ZPV096-4X9
▪
Package code:
45
▪
Binary code:
101101