Spence ET124 and ET134 Series 

Integrally-Mounted Temperature Regulators

 

 WARNING

Failure to follow these instructions or 

to properly install and maintain this 

equipment could result property damage 

and personal injury or death.
ET124 and ET134 Series regulators 

must be installed, operated and 

maintained in accordance with federal, 

state and local codes, rules and 

regulations and Emerson Process 

Management Regulator Technologies, 

Inc. instructions.
If the valve vents gas or a leak develops 

in the system, service to the unit may be 

required. Failure to correct issue could 

result in a hazardous condition. 
Installation, operation and maintenance 

procedures performed by unqualified 

personnel may result in improper 

adjustment and unsafe operation. Either 

condition may result in equipment 

damage or personal injury. Only a 

qualified person shall install or service 

the ET124 and ET134 Series regulators.

Introduction

Scope of the Manual

This manual provides instructions for the installation, 

troubleshooting, maintenance, valve setting and parts 

ordering for ET124 and ET134 Series regulators. Refer 

to the following documents for the complete details.

•  VCIMD-14980 for Types T124 and T134 

temperature and pressure pilots.

•  VCIMD-14961 for Type E main valve.
•  VCIMD-14935 for Type E2 main valve.

Figure 1.

 ET124 or ET134 Series Regulator

November 2021

Instruction Manual

VCIMD-16109

Product Description

ET124 and ET134 Series are steam pressure 

reducing valves and temperature regulators in a single 

pilot-operated valve. These regulators are combination 

of Type T124 or T134 pressure and temperature pilot 

and a Type E or E2 main valve. Steam pressure on 

the heater is modulated in proportion to temperature 

and load variations. Pressure control provides 

fast, accurate adjustment of heat transfer rate to 

demand requirements.

ET124 and ET134 Series 

Summary of Contents for ET124 Series

Page 1: ...jury Only a qualified person shall install or service the ET124 and ET134 Series regulators Introduction Scope of the Manual This manual provides instructions for the installation troubleshooting maintenance valve setting and parts ordering for ET124 and ET134 Series regulators Refer to the following documents for the complete details VCIMD 14980 for Types T124 and T134 temperature and pressure pi...

Page 2: ...r Cast Iron 250 psi 17 2 bar 1 The pressure temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded Principle of Operation The regulator is operated by its initial steam pressure The main valve is normally closed being held so by initial pressure on the disk and by an internal main spring The pilot is opened by compressing the pressure li...

Page 3: ...ipe to the underside of the pilot diaphragm As the pressure on this diaphragm approaches a balance with the thrust of the pressure limit spring the pilot throttles This in turn allows the main valve to assume a position where just enough steam flows to maintain the set maximum delivery pressure As the temperature of the heated medium rises vapor pressure is generated in the thermostat bulb and tra...

Page 4: ...g wheel until 1 2 in 12 7 mm of thread is exposed Back off pressure adjusting screw to remove all compression from pressure limit spring See Figure 3 Planning the Installation 1 Locate the regulator in a horizontal pipe 2 Prevent water hammer and erratic operation by providing a trap ahead of the regulator 3 Avoid damaging the effects of scale and dirt in pipe lines by using a strainer to protect ...

Page 5: ...ulator from the pressure system and release all pressure from the pilot and main valve before performing maintenance operations 2 Crack open outlet stop valve Crack open inlet stop valve blow down strainer then slowly open inlet valve wide open 3 Turn up pressure adjustment slowly When steam begins to flow open outlet stop valve gradually 4 Continue delivery pressure adjustment until heater output...

Page 6: ...8 Leak in the thermostat bulb may allow heated fluid pressure if sufficiently high to back up into thermal system to hold the pilot closed Complete dismantling at regular intervals for inspection and repair is not recommended Under normal conditions if kept relatively free of dirt a regulator will function year after year with minimum maintenance attention These service points are suggested 1 Afte...

Page 7: ...that called for by the medium flowing through the heater a Arrange to drain condensate by gravity or lift it with a pump 4 Sticky check valve in return line Dismantling Main Valve 1 Remove the pilot and its connection to the main valve 2 Remove the top flange of the valve 3 Connect a source of air water steam pressure which can be adjusted by hand to the underside of the diaphragm as shown in Figu...

Page 8: ...n Electric Co does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson Electric Co product remains solely with the purchaser Parts Ordering When corresponding with your local Sales Office about this equipment always reference the equipment regulator size service and serial number When ordering replacem...

Reviews: