background image

 

 

Operating instruction 

EC3-D7x Digital Superheat Controller 

EC3-D72 with TCP/IP communication capability 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 18.07.2017 

EC3-D7x_OI_ML_R06_865019.docx 

G e n e r a l   i n f o r m a t i o n :  

EC3-D72  is the superheat controller with TCP/IP connection for stepper motor 
driven Electrical Control Valves EX4-6 from EMERSON and is optimized to operate 
with the Copeland Digital Scroll series utilizing a 0-10V input from a third-party 
controller. The controller synchronizes the PWM digital compressor solenoid valve 
with the superheat controlled by the electrical control valve; EX series.  
The EC3-D73 has the same functionality but can only be set-up via the ECD-002 
display. It has no external communication functionality. 
 

  S a f e t y   i n s t r u c t i o n s :  

 

Read operating instructions thoroughly. Failure to comply can result in device 
failure, system damage or personal injury. 

 

According to EN 13313 it is intended for use by persons having the 
appropriate knowledge and skill. 

 

Do not exceed the specified maximum ratings for pressure, temperature, 
voltage and current. 

 

Before installation or service disconnect all voltages from system and device. 

 

Do not operate system before all cable connections are completed. 

 

Entire electrical connections have to comply with local regulations. 

Note

: The EC3-D7x series contains 

a VRLA battery = valve regulated rechargeable 

lead-acid battery. 

The battery must NOT be disposed of with other commercial waste. 

Instead, it is the user’s responsibility to pass it to a designated collection point for the 
safe recycling of batteries (harmonized directive 2012/19/EU). For further 
information contact your local environmental recycling center. 
 

M o u n t i n g   p o s i t i o n :  

The EC3-D7x  is designed to be mounted onto a standard DIN rail. Mounting 
position: on vertical walls, with stepper motor connector on top side only. 
 

M o u n t i n g   o f   E C D - 0 0 2 :  

 

ECD-002 can be installed at any time also during operation. 

 

ECD-002 can be mounted in panels with 
71x29 mm cutout. 

 

Push controller into panel cut-out.(1) 

 

Make sure that mounting lugs are flush with 
outside of controller housing 

 

Insert Allen key into front panel holes and turn 
clockwise. Mounting lugs will turn and gradually 
move towards panel (2) 

 

Turn Allen key until mounting lug barely touches 
panel. Then move other mounting lug to the same 
position (3) 

 

Tighten both sides very carefully until keypad is 
secured. Do not over tighten as mounting lugs 
will break easily.

 

 

 

  E l e c t r i c a l   I n s t a l l a t i o n :  

 

Refer to the electrical wiring diagram for electrical connections. 

 

Do not apply voltage to the controller before completion of wiring. 

 

Ground the metal housing with a 6.3 mm spade connector. 

 

Keep controller and sensor wiring well separated from mains wiring. Minimum 
recommended distance 30 mm. 

 

Use a class II category transformer for 24 VAC power supply. Do not ground the 
24 VAC lines. We recommend using individual transformers for EC3 controller(s) 
and for 3

rd

 party controllers to avoid possible interference or grounding problems 

in the power supply. Connecting any EC3 inputs to mains voltage will permanently 
damage the EC3. 

 

The use of the relay is essential to protect the system in case of power failure if the 
communications interface or the ECD-002 are not utilized. 

 

If the output relay is not utilized, the user must ensure appropriate safety pre-
cautions are in place to protect the system  against damage caused by a power 
failure. 

 

In order to provide system protection in the event of power loss, it is recommended 
to change the battery annually. 

 

Digital input status is dependent to operation of compressor/0-10V input 

System 

Operating 

condition 

Digital Inputs 

0-10V input from third party 

controller 

C1 &  
C2 in stop mode 

“Cooling demand” open (0 V) 
“Comp 2 Running” open (0 V) 

EXV remains closed irrespective 
of voltage input value 

 
C1 in run &  
C2 in stop mode 

 
“Cooling demand” closed (24 V) 
“Comp 2 Running” open (0 V) 

EXV active 
Input = 0V: dig. valve capacity = 
10% default capacity. 
If dig. comp. is in by-pass,  
EXV will: 

- close if capacity is <70% 
- be inhibited if capacity is 
>70% 

C1 &  
C2 in run mode 

“Cooling demand” closed (24 V) 
“Comp 2 Running” closed (24 V) 

EXV active 
EXV always modulates even when 
the dig. compr. is in by-pass mode. 

C1 in stop &  
C2 starts run 
mode  

“Cooling demand” open (0 V) 
“Comp 2 Running” closed (24 V) 

EXV remains closed irrespective 
of voltage input value 

Note 1: C1 = Compressor 1, C2 = Compressor 2 
Note 2: Digital comp. should always be regarded as base load compressor 1. 

 

W i r i n g :  

 

 

 

A

White wire 

B

Black wire 

C

 Blue wire 

D

Brown wire 

E

M12 Plug cable assembly EXV-Mxx for connection to EX4-6

 

F:

 

24 V Triac output to PWM Digital Scroll valve

 

G

Remote control panel, system controller. 

H

Alarm relay, dry contact. Relay coil is not energized at alarm or power off. 

I

Digital input “Cooling demand” (0 V/open = Stop; 24 V/closed = Start) 

J

Transformer Class II, 24 VAC secondary / 25 VA  

K

Third party controller (can use the analog output signal from EC3) 

L

Pump down relay, dry contact. Relay is energized during normal operation 

M

Digital input 2: “Comp 2 running”  
(0 V/ open = Comp 2 stop; 24 V /closed = Comp. 2 running) 

N

Discharge Temp. Sensor Copeland® NTC 

O: 

0-10 V Digital Scroll capacity demand signal from system controller  

P:

 

ECN-N60 Temperature sensor 

 

!

Summary of Contents for EC3-D72

Page 1: ...efer to the electrical wiring diagram for electrical connections Do not apply voltage to the controller before completion of wiring Ground the metal housing with a 6 3 mm spade connector Keep controller and sensor wiring well separated from mains wiring Minimum recommended distance 30 mm Use a class II category transformer for 24 VAC power supply Do not ground the 24 VAC lines We recommend using i...

Page 2: ...eave the special function mode Main parameters must be checked and modified if necessary Code Parameter description and choices Min Max Factory setting Field setting H5 Password 1 199 12 u0 System refrigerant 0 15 1 0 R22 1 R134a 2 R507 3 R404A4 R407C 5 R410A 6 R124 7 R744 subcritical application 8 R407A 9 R407F 10 R32 11 R448A 12 R449A 13 R450A 14 R513A 15 R1234ze uP Installed pressure sensor typ...

Page 3: ...that digital input is 0V open turn the power supply ON Four parameters i e refrigerant type u0 pressure sensor type uP valve type ut and control mode can be set only when digital input is open 0V while the power supply is ON 24 V This feature is for added safety to prevent accidental damage of compressors and other system components All other parameters can be modified at any time The EC3 D72 has ...

Page 4: ...g Fully close Pumpdown deactivated Check the system No Fixed differential 10 C Er Data error display out of range Data send to the display is out of range Check temperature and pressure sensor No No data to display Check Cable and plug connection between EC3 D7 and ECD 002 No Note When multiple alarms occur the highest priority alarm is displayed until being cleared then the next highest alarm is ...

Page 5: ...ary connection EXV control loop remains active when input is 24 V and the digital scroll is idle NTC input Coil out temperature sensor EMERSON temperature sensor ECN Nxx ECN Pxx NTC input Discharge temperature sensor Copeland NTC 86 kOhm at 25 C 4 20 mA Analog input EMERSON PT5 Pressure Transmitter 4 20 mA Analog output Deviation from input signal For connection to any 3rd party controller with 12...

Page 6: ...ngsschema durchführen Versorgungsspannung erst nach kompletter Installation anlegen Gehäuse mit einem 6 3 mm Flachstecker erden Signalleitungen und Leitungen mit Netzspannung in getrennten Kabelschächten verlegen Mindestabstand 30 mm Für die 24 V Stromversorgung sind ausschließlich Transformatoren der Klasse II zu verwenden Die 24 V Leitungen dürfen nicht geerdet werden Wir empfehlen die Verwendun...

Page 7: ...h und reglerabhängig 0 Regler auf Werkseinstellung zurücksetzen Reset nur bei offenem Digitaleingang O V möglich 1 Aktuelle TCP IP Adresse anzeigen 2 Dem Regler vorübergehend die Standard TCP IP Adresse 192 168 1 101 zuweisen falls dieser eine andere Adresse besitzt Nach dem Abschalten wird die zuvor eingestellte Adresse wieder aktiviert SEL drücken alle Parameter werden auf Werkseinstellung zurüc...

Page 8: ...einstellung und Datenanzeige auf Webseiten empfohlene Methode Während am Digitaleingang 0V anliegen Versorgungsspannung anschalten Die vier Parameter Kältemittel u0 Drucksensor Typ uP Ventil Typ ut und Kontrollmode können nur eingestellt werden wenn der Digitaleingang offen 0 V und die Versorgungsspannung AN 24 V ist Diese Sicherheitsfunktion verhindert die Beschädigung des Verdichters oder andere...

Page 9: ...Fehler überprüfen Nein Feste Differenz 10 C Er Daten außerhalb des Anzeigebereichs Display kann Daten nicht darstellen Einstellwert der Parameter verändern Nein Keine Daten Kable und Steckerverbindungen zwischen EC3 D7 und ECD 002 prüfen Nein Hinweis Bei mehreren Alarmen gleichzeitig wird der Alarm mit der höchsten Priorität angezeigt nach dessen Beseitigung wird der nächsthöhere angezeigt usw bis...

Page 10: ... DC zum Anschluss eines Hilfskontaktes Bei 24 V bleibt das EX Ventil aktiv auch wenn der Digital Scroll im Leerlauf arbeitet NTC Analogeingang EMERSON Temperatursensor ECN N60 ECN P60 NTC Analogeingang für Sensor Austrittstemperatur Copeland NTC 86 kOhm bei 25 C 4 20 mA Analogeingang EMERSON PT5 Drucktransmitter 4 20 mA Analogausgang Abweichung vom Eingangssignal für externen Regler mit 12 24 VDC ...

Reviews: