background image

 

1592023040 XM668D GB r1.1 2011.07.05.doc 

XM668D  

          

6/14 

 

second  possibility,  it  can  be  used  only  in  centralized plants  and  it  is  available 
only  with  electronic  expansion  valve

  by  selecting  [

CrE=Y

]  parameter.  The  third 

kind  of  regulation  has  been  thought  to  be  used  with  vales  called  evaporator  valves 
[

CrE=EUP

], in this configuration the  valve is placed at the end  of the  evaporator.  In 

any  case,  the  regulation  is  performed  via  PI  regulator  that  gives  the  opening 
percentage to the valve.

 

 
Standard regulation: [CrE=n] 

In  this  case,  the 

HY

  parameter  is  the  differential  for standard  ON/OFF  regulation.  In 

this case the 

int

 parameter is neglected. 

 

 
Continuous regulation: [CrE=Y] 

In  this  case,  the 

HY

  parameter  is  the  proportional  band  of  PI  in  charge  of  room 

temperature  regulation  and  we  advise  to  used  at  least  [

HY  =  5.0°C/10°F

].  The 

int

 

parameter is the integral time of the same PI regulator.  Increasing 

int

 parameter the 

PI regulator become slowly in reaction and of course is true vice versa. To disable the 
integral part of regulation you should set [

int=0

]. 

 
Evaporator valves: [CrE=EUP] 

In  this  case,  the  system  performs  a  regulation  of  the  temperature  without  thinking 
about  the  superheat  (in  fact  the  valve  is  at  the  end  of  the  evaporator).  The 

HY

 

parameter  is  the  proportional  band  for  the  temperature  regulation  and 

int

  is  the 

integral time for the regulation. In this situation there is no superheat regulation. 

12.3

 

DEFROST 

Defrost starting 
In any case, the device check the temperature read by configured defrost probe 
before starting defrost procedure, after that: 

-

 (If  RTC  is  present)Two  defrost  modes  are  available  through  the 

tdF

  parameter: 

defrost with electrical heater and hot gas defrost. The defrost interval is controlled 
by parameter 

EdF

: (

EdF=rtC

) defrost is made in real time depending on the hours 

set  in  the  parameters 

Ld1 

to 

Ld6

  in  workdays  and  in 

Sd1 

to 

Sd6

  on  holidays; 

(

EdF=in

) the defrost is made every 

idF

 time. 

-

 Defrost  cycle  starting  can  be  operated  locally  (manual  activation  by  means  of  the 

keyboard  or  digital  input  or  end  of  interval  time)  or  the  command  can  come  from 
the  Master  defrost  unit  of  the  LAN.  In  this  case  the  controller  will  operate  the 
defrost cycle following the parameters it has programmed but, at the end of the drip 
time,  will  wait  that  all  the  other  controllers  of  the  LAN  finish  their  defrost  cycle 
before  to  re-start  the  normal  regulation  of  the  temperature  according  to 

dEM

 

parameter. 

-

 Every  time  any  of  the  controller  of  the  LAN  begin  a  defrost  cycle  it  issue  the 

command  into  the  network  making  all  the  other  controllers  start  their  own  cycle. 
This  allows  a  perfect  synchronization  of  the  defrost  in  the  whole  multiplexed 
cabinet according to 

LMd

 parameter. 

-

 

Differential defrost:

 Selecting 

dPA

 and 

dPb

 probes and by changing the 

dtP

 and 

ddP

 parameters the defrost can be started when the difference between 

dPA

 and 

dPb

 probes is lower than 

dtP

 for all 

ddP

 time. This is useful to start defrost when a 

low thermal exchange is detected. If [

ddP=0

] this function is disabled. 

-

  

Defrost ending 

-

 When defrost is started  via 

rtC

, the maximum duration of defrost is obtained  from 

Md

  parameter  and  the  defrost  end  temperature  is  obtained  from 

dtE

  parameter 

(and 

dtS

 if two defrost probes are selected).  

-

 If 

dPA

  and 

dPb

  are  present  and  [

d2P=Y

]

,

  the  instrument  stops  the  defrost 

procedure  when 

dPA

  is  higher  than 

dtE

  temperature  and 

dPb

  is  higher  than 

dtS

 

temperature. 

 
At the end of defrost the drip time is controlled through the 

Fdt

 parameter.  

12.4

 

FANS 

CONTROL WITH RELAY 

The fan control mode is selected by means of the 

FnC

 parameter: 

C-n

 = running with the solenoid valve, OFF during the defrost;  

C-Y

 = running with th1e solenoid valve, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-Y

 = continuous mode, ON during the defrost. 

 
An  additional  parameter 

FSt

  provides  the  setting  of  temperature,  detected  by  the 

evaporator probe,  above which the fans are always OFF. This can be used to make 
sure circulation of air only if his temperature is lower than set in 

FSt

 

CONTROL WITH ANALOG OUTPUT (if present) 
 

 

 
The  modulating  output  [

trA=rEG

]  works  in  proportional  way  (excluding  the  first 

AMt

 

seconds  where  the  fans  speed  is  the  maximum.  10seconds  is  the  minimum  value). 
The regulation set point is relative to regulation set point and is indicated by 

ASr

, the 

proportional  band  is  always  located  above  [

SET+ASr

]  value  and  its  value  is 

PbA

The  fans  are  at  minimum  speed 

AMi

  when  the  temperature  read  by  fan  probe  is 

[

SET+ASr

]  and  the  fan  is  at  maximum  speed  (

AMA

)  when  the  temperature  is 

[

SET+ASr+PbA

].  

12.5

 

ANTI SWEAT HEATERS 

The  anti-sweat  heater  regulation  can  be  performed  with  on  board  relay  (if 

oA6=AC

or with the analog output (if present by setting 

trA=AC

). However the regulation can 

be performed in two ways: 

 

Without real dew-point information: in this case the default value for dew-
point is used (

SdP

 parameter).  

 

Receiving  dew-point  from 

XWEB5000

  system:  the 

SdP

  parameter  is 

overwritten  when  valid  value  for  dew-point  is  received  from  XWEB.  In 
case of XWEB link is lost, 

SdP

 is the value that will be used for safety. 

 
The  best  performance  can  be  obtained  using  probe  4.  In  this  case,  the  regulation 
follows the chart: 
 

 

Probe 4 should be placed on the showcase glass

. For each cabinet can be used 

only  one  probe  4  (P4)  sending  its  value  to  the  others  section  that  are  connected  to 
the LAN.  

 
HOW TO WORK WITH PROBE 4 THROUGH THE LAN: 

Param. 

XM6x8D_1 

Without probe 4 

XM 

with 

probe 4 

XM 

Without probe 4 

Adr 

n  

n + 1 

n + 2 

LCP 

LCP = n 

LCP = Y 

LCP = n 

P4C 

LAN or not 

connect the probe 

P4C = NTC, PtC or 

PtM 

LAN or not connect 

the probe 

trA 

trA = AC if the device has the analog output 

oA6 

oA6 = AC if the device will use the AUX relay for regulation 

 
HOW TO WORK WITHOUT PROBE 4: 

 

Param. 

XM6x8D 

Without probe 4 

P4C 

nP 

AMt 

% of ON 

In this case, the regulation is performed by 

switching on and off the auxiliary relay on a 

60 minutes time base. The ON time will be 

the 

AMt

 value, so that the relay will be ON for 

AMt

 minutes and OFF for 

[60-AMt]

 minutes. 

 
In case of P4 error or if P4 is absent the output is at 

AMA

 value for the 

AMt

 time then 

the  output  is  at  0  value  for  the  time  [

255–AMt

]  time  performing  a  simple  PWM 

modulation.

 

Summary of Contents for Dixell XM668D

Page 1: ...on is with Dixell CX660 keyboard Figure 1a Figure 1b The CX660 keyboard shall be mounted on vertical panel in a 29x71 mm hole and fixed using the special bracket supplied as shown in fig 1a 1b The temperature range allowed for correct operation is 0 to 60 C Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity The same recommendations apply to probes Let air circulat...

Page 2: ...pressing UP ARROW button the user will be able to enter a fast selection menu and to read the value of the following parameters dPP measured pressure only on master device dP5 value of temperature obtained from pressure temperature conversion rPP pressure value read from remote location only for slave devices Examples of error messages dPP Err the local transducer read a wrong value the pressure i...

Page 3: ...S TO PR2 To enter Pr2 programming menu 1 access the Pr1 menu by pressing both SET DOWN keys for 3 sec the first parameter label will be showed 2 press DOWN key untill the Pr2 label will be showed then press SET key 3 The blinking PAS label will be showed wait some seconds 4 Will be showed 0 with blinking 0 insert the password 321 using the keys UP and DOWN and confirming with SET key GENERAL STRUC...

Page 4: ...0 CPP mA 10 CHd mA 10 Sr step s 0 Manual settings Par Par Par Par Par 1 Alco EX4 EX5 EX6 5 75 50 10 500 2 Alco EX7 10 160 75 25 500 3 Alco EX8 500 step s 10 260 80 50 500 4 Danfoss ETS 25 50 7 262 10 10 300 5 Danfoss ETS 100 10 353 10 10 300 6 Danfoss ETS 250 400 11 381 10 10 300 7 Sporlan SEI 5 to 11 0 159 16 5 200 8 Sporlan SER 1 5 to 20 0 159 12 5 200 9 Sporlan SEI 30 0 319 16 5 200 10 Sporlan ...

Page 5: ...cond 18 MOP Maximum operating pressure threshold from MOP parameter The valve output decreases its opening of dML quantity every second 19 LSH Low superheating from LSH parameter and SHd delay The valve will be closed the alarm will be showed after SHd delay 20 HSH High superheating from HSH parameter and SHd delay Only display CLOCK ALARM 21 rtC Clock settings lost Defrost will be performed with ...

Page 6: ...detected If ddP 0 this function is disabled Defrost ending When defrost is started via rtC the maximum duration of defrost is obtained from Md parameter and the defrost end temperature is obtained from dtE parameter and dtS if two defrost probes are selected If dPA and dPb are present and d2P Y the instrument stops the defrost procedure when dPA is higher than dtE temperature and dPb is higher tha...

Page 7: ...l inputs 3 free of voltage Relay outputs Total current on loads MAX 16A Solenoid Valve relay SPST 5A 250Vac Defrost relay SPST 16A 250Vac Fan relay SPST 8A 250Vac Light relay SPST 16A 250Vac Alarm SPDT relay 8A 250Vac Aux SPST relay 8A 250Vac Outputs for valve bipolar or unipolar valves Optional output AnOUT DEPENDING ON THE MODELS PWM Open Collector outputs PWM or 12Vdc max 40mA Analog output 4 t...

Page 8: ...efrost start 0 0 to 23h50min 143 nU 144 Holidays defrost start Sdn to 23h50min these parameters set the beginning of the eight programmable defrost cycles on holidays Ex when Sd2 3 4 the second defrost starts at 3 40 on holidays nU not used Format hours 10min resolution 10min Sd2 13 0 Holidays Second defrost start Sd1 to 23h50min 143 nU 144 Sd3 21 0 Holidays Third defrost start Sd2 to 23h50min 143...

Page 9: ...d LSH SHY 0 1 C to 25 5 C 1 F to 45 F SHd 3 0 Delay of superheat alarm signaling 0 0 to 42min00sec 252 If a superheat alarm occurs the delay time SHd will have to expire before the controller shows an alarm Format min 10sec resolution 10sec FrC 0 Integration additive constant Fast recovery 0 to 100s Permits to increase integral time when SH value is below the set point If FrC 0 fast recovery funct...

Page 10: ...e changes the display will be updated of 1 C 1 F when delay time expires Format min 10sec resolution 10sec rPA P1 Regulation probe A nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 First probe used to regulate room temperature If rPA nP the regulation is performed with real value of rPb rPb nP Regulation probe B nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 Second probe used to regulate room temperature If rPb nP the regulation is...

Page 11: ...during the defrost Fnd 10 Fan delay after defrost 0 to 255min The time interval between the ending of the defrost and the starting of the evaporator fans FSt 10 0 Fan stop temperature 55 0 C to 50 0 C 67 F to 122 F Evaporator probe temperature above which the fan is always OFF FHY 1 0 Fan stop differential 0 1 C to 25 5 C 1 F to 45 F When stopped fan restarts when fan probe reaches FSt FHY value o...

Page 12: ...0min 144 After powering on the instrument time interval between the detection of the temperature alarm condition and the alarm signaling Format hours 10min resolution 10min EdA 20 Alarm delay at the end of defrost 0 to 255min At the end of the defrost cycle time interval between the detection of the temperature alarm condition and the alarm signaling dot 20 Temperature alarm exclusion after door o...

Page 13: ...en LiG light switched off AUS AUX switched off LEA both light and AUX switched off If nU then not used function LAN MANAGEMENT LMd Y Defrost Synchronization n Y n the section doesn t send a global defrost command Y the section sends a command to start defrost to other controllers dEM Y Defrost end Synchronization n Y n the end of the LAN defrosts are independent Y the end of the LAN defrosts are s...

Page 14: ...ceived from master o5 0 P5 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 5 P6C PtM P6 configuration nP PtC ntC PtM nP not present PtC Ptc ntC ntc PtM Pt1000 o6 0 P6 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 6 SERVICE CLt ON OFF percentage C R O read only It shows the effective cooling time calculated by XM600 during regulation cooling t...

Reviews: