idF 

Defrost interval. 

0 to 120hours 

It  sets  the  time  interval  between  the  beginning  of  two 
defrost cycles.  

[EdF = in]:

 it is the interval between 2 defrost;  

[EdF  =  rtC]:

  it  is  the  safety  interval  in  case  of  clock 

alarm 

[RtC – RtF]

.  

[idF = 0]:

 the defrost can be activated only manually, or 

through RS485 or from external contact or from LAN. 

 

MdF 

45 

(Maximum) duration for defrost. 

0 to 255min 

When 

dPA 

and 

dPb 

aren’t  present,  it  sets  the  defrost 

duration,  otherwise  it  sets  the  maximum  duration  for 
defrost. 

 

dSd 

Defrost start delay after request. 

0 to 255min 

Useful when different defrost start times are necessary 
to avoid overloading the plant. 

 

dFd 

rt 

Display during defrost. 

rt; it; SEt; dEF 

rt 

= real temperature for 

Lod

 probe; 

it

 = initial temperature (reading when defrost start); 

SEt 

= set-point value; 

dEF 

= “dEF” label is visualized. 

 

dAd 

30 

Display delay. 

0 to 255min 

Set the maximum time between the end  of defrost and 
the restarting of the real room temperature display. 

 

Fdt 

Drain down time after defrost. 

0 to 255min 

Time  interval  between  reaching  defrost  termination 
temperature  and  the  restoring  of  the  control’s  normal 
operation.  This  time  allows  the  evaporator  to  eliminate 
water drops that might have formed due to defrost.  
The  fan  and  the  thermoregulation  output  are  OFF 
during this time. 

 

dPo 

Defrost at power-on. 

n; Y 

First defrost after start-up: 

= Immediately; 

= after the 

idF

 time. 

 

dAF 

0.0 

Defrost delay after continuous cycle. 

0.0 to 24h00min (144) 

Time interval between the end of the fast freezing cycle 
and the following defrost related to it. 

Format

: hours.10min, 

resolution

: 10min. 

 

 

 

FAN 

 

 

 

FPA 

P2 

Fan probe A 

nP(0); P1(1); P2(2);  

P3(3); P4(4); P6(5) 

First probe used for fan. If 

[FPA = nP]

 the regulation is 

performed with real value of 

FPb

 

FPb 

nP 

Fan probe B. 

nP(0); P1(1); P2(2);  

P3(3); P4(4); P6(5) 

Second  probe  used  for  defrost.  If 

[FPb  =  nP]

  the 

regulation is performed with real value of 

FPb

 

FPE 

100 

Virtual probe percentage (fan management). 

0 to 100% 

It  defines  the  percentage  of  the 

FPA

  respect  to 

FPb

The  value  used  to  regulate  room  temperature  is 
obtained by: 
 

value_for_defrost= (FPA*FPE + FPb*(100-FPE))/100

 

 

FnC 

O-n 

Fan operating mode. 

C-n; C-Y; O-n; O-Y 

C-n 

=  running  with  the  solenoid  valve,  OFF  during  the 

defrost; 

C-Y 

=  running  with  the  solenoid  valve,  ON  during  the 

defrost; 

O-n 

= continuous mode, OFF during the defrost; 

O-Y 

= continuous mode, ON during the defrost. 

 

Fnd 

10 

Fan delay after defrost. 

0 to 255min 

The time interval between the ending of the defrost and 
the starting of the evaporator fans. 

 

FSt 

10.0 

Fan stop temperature. 

[-55.0°C to 50.0°C] 

 [-67°F to 122°F] 

Evaporator  probe  temperature  above  which  the  fan  is 
always OFF. 

 

FHY 

1.0 

Fan stop differential 

[0.1°C to 25.5°C]  

[1°F to 45°F] 

When  stopped,  fan  restarts  when  fan  probe  reaches 

[FSt – FHY]

 value of temperature. 

 

tFE 

Thermostatic fan functioning during defrost 

n; Y 

 

Fod 

Fan activation time after defrost (without 
compressor) 

0 to 255min 

It forces fan activation for the indicated time. 

 

Fon 

Fan ON time 

0 to 15min 

With

  [FnC  =  C-n

  or 

C-Y]

  (fan  activated  in  parallel  with 

compressor), it sets the evaporator fan ON cycling time 
when the compressor is off. With [

Fon = 0]

 and [

FoF ≠ 

0] 

the  fan  is  always  off,  with  [

Fon  =  0]

  and  [

FoF  =  0]

 

the fan is always off. 

 

FoF 

Fan OFF time 

0 to 15min 

With 

[FnC  =  C-n

  or 

C-Y]

  (fan  activated  in  parallel  with 

compressor)  it  sets  the  evaporator  fan  off  cycling  time 
when the compressor is off. With 

[Fon = 0]

 and 

[FoF ≠ 

0] 

the fan are always off, with 

[Fon = 0]

 and 

[FoF = 0]

 

the fan are always off. 

 

trA 

UAL 

Kind of PWM regulation 

UAL; rEG; AC 

UAL 

= the output is at 

FSA

 value (manual value);  

rEG 

=  the  output  is  regulated  with  fan  algorithm 

described in fan section;  

AC 

=  anti-sweat  heaters  control  (require  XWEB5000 

system). 

 

SOA 

Manual value of the analog output 

AMi to AMA 

Value for the output if 

[trA = UAL] 

(0 to 100%). 

 

SdP 

30.0 

Default Dew-Point value (or safety value in case of 
XWEB link lost) 

[-55.0°C to 50.0°C] 

 [-67°F to 122°F] 

Default  value  of  dew-point  used  when  there  is  no 
supervising  system  (XWEB5000).  Used  only  if 

[trA  = 

AC]

 

ASr 

1.0 

Differential for fan / offset for anti sweat heater. 

[-25.5°C to 25.5°C] 

[-45°F to 45°F] 

trA = AC: 

dew-point offset; 

trA = rEG: 

differential for modulating fan regulation. 

 

PbA 

5.0 

Proportional band for modulating output. 

[0.1°C to 25.5°C] 

[1°F to 45°F] 

Differential for anti-sweat heaters. 

 

AMi 

Minimum output for modulating output. 

0 to AMA 

Minimum value for analog output:

 

(0 to 

AMA

). 

 

AMA 

100 

Maximum output for modulating output. 

AMi to 100 

Maximum value for analog output:

 

(

AMi

 to 100). 

 

AMt 

10 

Time with fan at maximum speed or ON time for 
relay on Anti-sweat regulation. 

 [10 to 60s] or 

[10 to 60min] 

trA = AC: 

Anti-sweat heaters cycle period

trA = rEG: 

Time with fan at maximum speed

During  this  time  the  fan  works  at  maximum  speed.  If 
intended  for  fan,  the  basetime  is  on  seconds,  for  anti-
sweat regulation the basetime is on minutes. 

 

 

 

ALARM 

 

 

 

rAL 

tEr 

Probe for room temperature alarm. 

nP; P1; P2; P3; P4; P6; tEr 

It selects the probe used to signal alarm temperature. 

Summary of Contents for Dixell XM668D

Page 1: ...on is with Dixell CX660 keyboard Figure 1a Figure 1b The CX660 keyboard shall be mounted on vertical panel in a 29x71 mm hole and fixed using the special bracket supplied as shown in fig 1a 1b The temperature range allowed for correct operation is 0 to 60 C Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity The same recommendations apply to probes Let air circulat...

Page 2: ...pressing UP ARROW button the user will be able to enter a fast selection menu and to read the value of the following parameters dPP measured pressure only on master device dP5 value of temperature obtained from pressure temperature conversion rPP pressure value read from remote location only for slave devices Examples of error messages dPP Err the local transducer read a wrong value the pressure i...

Page 3: ...S TO PR2 To enter Pr2 programming menu 1 access the Pr1 menu by pressing both SET DOWN keys for 3 sec the first parameter label will be showed 2 press DOWN key untill the Pr2 label will be showed then press SET key 3 The blinking PAS label will be showed wait some seconds 4 Will be showed 0 with blinking 0 insert the password 321 using the keys UP and DOWN and confirming with SET key GENERAL STRUC...

Page 4: ...0 CPP mA 10 CHd mA 10 Sr step s 0 Manual settings Par Par Par Par Par 1 Alco EX4 EX5 EX6 5 75 50 10 500 2 Alco EX7 10 160 75 25 500 3 Alco EX8 500 step s 10 260 80 50 500 4 Danfoss ETS 25 50 7 262 10 10 300 5 Danfoss ETS 100 10 353 10 10 300 6 Danfoss ETS 250 400 11 381 10 10 300 7 Sporlan SEI 5 to 11 0 159 16 5 200 8 Sporlan SER 1 5 to 20 0 159 12 5 200 9 Sporlan SEI 30 0 319 16 5 200 10 Sporlan ...

Page 5: ...cond 18 MOP Maximum operating pressure threshold from MOP parameter The valve output decreases its opening of dML quantity every second 19 LSH Low superheating from LSH parameter and SHd delay The valve will be closed the alarm will be showed after SHd delay 20 HSH High superheating from HSH parameter and SHd delay Only display CLOCK ALARM 21 rtC Clock settings lost Defrost will be performed with ...

Page 6: ...detected If ddP 0 this function is disabled Defrost ending When defrost is started via rtC the maximum duration of defrost is obtained from Md parameter and the defrost end temperature is obtained from dtE parameter and dtS if two defrost probes are selected If dPA and dPb are present and d2P Y the instrument stops the defrost procedure when dPA is higher than dtE temperature and dPb is higher tha...

Page 7: ...l inputs 3 free of voltage Relay outputs Total current on loads MAX 16A Solenoid Valve relay SPST 5A 250Vac Defrost relay SPST 16A 250Vac Fan relay SPST 8A 250Vac Light relay SPST 16A 250Vac Alarm SPDT relay 8A 250Vac Aux SPST relay 8A 250Vac Outputs for valve bipolar or unipolar valves Optional output AnOUT DEPENDING ON THE MODELS PWM Open Collector outputs PWM or 12Vdc max 40mA Analog output 4 t...

Page 8: ...efrost start 0 0 to 23h50min 143 nU 144 Holidays defrost start Sdn to 23h50min these parameters set the beginning of the eight programmable defrost cycles on holidays Ex when Sd2 3 4 the second defrost starts at 3 40 on holidays nU not used Format hours 10min resolution 10min Sd2 13 0 Holidays Second defrost start Sd1 to 23h50min 143 nU 144 Sd3 21 0 Holidays Third defrost start Sd2 to 23h50min 143...

Page 9: ...d LSH SHY 0 1 C to 25 5 C 1 F to 45 F SHd 3 0 Delay of superheat alarm signaling 0 0 to 42min00sec 252 If a superheat alarm occurs the delay time SHd will have to expire before the controller shows an alarm Format min 10sec resolution 10sec FrC 0 Integration additive constant Fast recovery 0 to 100s Permits to increase integral time when SH value is below the set point If FrC 0 fast recovery funct...

Page 10: ...e changes the display will be updated of 1 C 1 F when delay time expires Format min 10sec resolution 10sec rPA P1 Regulation probe A nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 First probe used to regulate room temperature If rPA nP the regulation is performed with real value of rPb rPb nP Regulation probe B nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 Second probe used to regulate room temperature If rPb nP the regulation is...

Page 11: ...during the defrost Fnd 10 Fan delay after defrost 0 to 255min The time interval between the ending of the defrost and the starting of the evaporator fans FSt 10 0 Fan stop temperature 55 0 C to 50 0 C 67 F to 122 F Evaporator probe temperature above which the fan is always OFF FHY 1 0 Fan stop differential 0 1 C to 25 5 C 1 F to 45 F When stopped fan restarts when fan probe reaches FSt FHY value o...

Page 12: ...0min 144 After powering on the instrument time interval between the detection of the temperature alarm condition and the alarm signaling Format hours 10min resolution 10min EdA 20 Alarm delay at the end of defrost 0 to 255min At the end of the defrost cycle time interval between the detection of the temperature alarm condition and the alarm signaling dot 20 Temperature alarm exclusion after door o...

Page 13: ...en LiG light switched off AUS AUX switched off LEA both light and AUX switched off If nU then not used function LAN MANAGEMENT LMd Y Defrost Synchronization n Y n the section doesn t send a global defrost command Y the section sends a command to start defrost to other controllers dEM Y Defrost end Synchronization n Y n the end of the LAN defrosts are independent Y the end of the LAN defrosts are s...

Page 14: ...ceived from master o5 0 P5 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 5 P6C PtM P6 configuration nP PtC ntC PtM nP not present PtC Ptc ntC ntc PtM Pt1000 o6 0 P6 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 6 SERVICE CLt ON OFF percentage C R O read only It shows the effective cooling time calculated by XM600 during regulation cooling t...

Reviews: