background image

 

 

1592023220 XM660K_XM670K GB r5.4 2021.09.01 

XM660K - XM670K  

          7/9 

 

PROBE CONFIGURATION 
 

P1C 

Probe 1 configuration: 

(nP 

 Ptc 

 ntc 

 CPC -  PtM) 

nP=

 not present; 

PtC=

 Ptc;  

ntc=

 NTC; 

CPC=

 

NTC-US; 

PtM=

 Pt1000;

 

OF1 

Probe 1 calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offset of the thermostat probe. 

P2C 

Probe 2 configuration: 

(nP 

 Ptc 

 ntc 

 CPC -  PtM) 

nP=

 not present; 

PtC=

 Ptc;  

ntc=

 NTC; 

CPC=

 

NTC-US; 

PtM=

 Pt1000; 

OF2 

Probe 2 calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offsets of the evaporator probe. 

P3C 

Probe 3 configuration: 

(nP 

 Ptc 

 ntc 

 CPC -  PtM) 

nP=

 not present; 

PtC=

 Ptc;  

ntc=

 NTC; 

CPC=

 

NTC-US; 

PtM=

 Pt1000;

 

OF3 

Probe 3 calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offset of the probe 3. 

P4C 

Probe 4 configuration: 

(nP 

 Ptc 

 ntc 

 CPC -  PtM) 

nP=

 not present; 

PtC=

 Ptc;  

ntc=

 NTC; 

CPC=

 

NTC-US; 

PtM=

 Pt1000;; 

OF4 

Probe 4 calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offset of the probe 4. 

 

SERVICE 

 OTHERS 

LCL 

Light on during cleaning mode 

(n, y)

 

FCL 

Fan on during cleaning mode 

(n, y) 

MAP  Map  used  during  standard  operation  (1°M,  2°M,  3°M,  4°M

)  It  sets  the  map  used  by  the 

controller among the four possible maps 

MP1  Alternate Map enabled by digital input or Modbus command

 (1°M, 2°M, 3°M, 4°M) It sets 

the alternate map enabled by digital input or Modbus command among the four possible maps

 

CLt 

Coling  time  percentage: 

it

 

shows  the  effective  cooling  time  calculated  by  XM600  during 

regulation;

 

tMd 

Time to next defrost: 

it

 

shows time before the next defrost if interval defrost is selected;

 

LSn 

L.A.N. section number 

 (1 ÷ 8)  Shows the number of sections available in the L.A.N. 

Lan 

L.A.N.  serial  address 

  (1  ÷  LSn)    Identifies  the  instrument  address  inside  local  network  of 

multiplexed cabinet controller. 

Adr  

RS485 serial address 

(1÷247)

Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

br 

It sets the baud rate among: (

96 = 9.6 bit/s; 192 = 19.2 bit/s)

 

EMU  Previous versions emulation (

2V8 , 3V8 , 4V2) It allows the controller to be used in a LAN of 

controllers with previous versions: 

2V8 

= it emulates version 2.8 

3V8 

= it emulates version 3.8 

4V2 

= it emulates version 4.2 

rEL  

Release software:

 (read only) Software version of the microprocessor. 

SrL 

Software subrelease: 

(read only) for internal use

 

Ptb  

Parameter table:

 (read only) it shows the original code of the Dixell parameter map. 

Pr2  

Access to the protected parameter list 

(read only). 

14. 

DIGITAL INPUTS

 

The XM600 series can support up to 3 free of voltage contact configurable digital inputs (depending on 

the models). They are configurable via i#F parameter 

14.1

 

GENERIC ALARM (EAL) 

As soon as the digital input 1, 2, or 3 

is activated the unit will wait for “

d1d

” or “

d2d

” or “

d3d

 time delay 

before signalling the “

EAL

” alarm message. The outputs status doesn’t

 change. The alarm stops just after 

the digital input is de-activated. 

14.2

 

SERIOUS ALARM MODE (BAL) 

When the digital input is activated, the unit will wait for 

d1d

” or “

d2d

” or “

d3d

” 

delay before signalling the 

BAL

 alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital 

input is de-activated. 

14.3

 

PRESSURE SWITCH (PAL) 

If d

uring the interval time set by “

d1d

” or “

d2d

” or “

d3d

” 

parameter, the pressure switch has reached the 

number of 

activation of the “

nPS

” parameter, the “

CA

” pressure alarm message will be displayed. The 

compressor and the regulation are stopped. When the digital input is ON the compressor is always OFF. 

If the nPS activation in the d#d time is reached, switch off and on the instrument to restart normal 

regulation. 

14.4

 

DOOR SWITCH INPUT  (dor) 

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no

 = 

normal (any change); 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. Since 

the door is opened, after the delay time set through parameter “

d#d

”, the door alarm is enabled, the 

display shows the message “

dA

” and 

the regulation restarts after rrd time.

 The alarm stops as soon as 

the external digital input is disabled again. With the door open, the high and low temperature alarms are 

disabled. 

14.5

 

START DEFROST (DEF) 

It executes a defrost if there are the right conditions. After the defrost is finished, the normal regulation 

will restart only if the digital input is disabled otherwise the instrument will wait until the “

Mdf

” safety time 

is expired. 

14.6

 

RELAY AUX ACTUATION (AUS) 

This function allows to turn ON and OFF the auxiliary relay by using the digital input as external switch. 

14.7

 

RELAY LIGHT ACTUATION (LIG) 

This function allows to turn ON and OFF the light relay by using the digital input as external switch. 

14.8

 

REMOTE ON/OFF (ONF) 

This function allows to switch ON and OFF the instrument. 

14.9

 

FHU 

 NOT USED 

This function allows to change the kind of regulation from cooling to heating and viceversa. 

14.10

 

ENERGY SAVING INPUT (ES) 

The  Energy  Saving  function  allows  to  change  the  set  point  value  as  the  result  of  the  SET+  HES 

(parameter) sum. This function is enabled until the digital input is activated. 

14.11

 

MAP SWITCHING (NT) 

In this configuration, the digital input activates the map selected by the MP1 parameter.  

The “MAP CHANGE” ModBus command has higher priority compared to the digital input.

 

14.12

 

CLEANING FUNCTION ACTIVATION (CLN) 

In this configuration, the digital input activates the CLEANING function. It can be activated only if the 

device is ON.  

This function has the following characteristics: 

 

the display visualizes the “CLn” label

 

 

The light status depends on the LCL parameter (no/yes), however the light can be modified both 

via button and ModBus command. 

 

The  fans  status  depends  on  the  FCL  parameter  (no/yes),  furthermore  they  are  not  thermo-

regulated (par.FST). 

The “CLEANING MODE” ModBus command 

has higher priority compared to the digital input. 

14.13

 

DEFROST END (DEN) 

The digital input ends the defrost cycle in progress. The drip time will follow the defrost end. A further 

defrost request with the digital input active won’t be managed.  

 

14.14

 

DIGITAL INPUTS POLARITY  

The digital input

s polarity depends on “

I#P

 parameters: 

CL

 : the digital input is activated by closing the 

contact; 

OP

 : the digital input is activated by opening the contact. 

 

15. 

USE OF THE PROGRAMMING “HOT KEY“ –

 64 K

 

 

The XM units can UPLOAD or DOWNLOAD the parameter list 

from its own E2 internal memory to the 

“Hot Key” 

and vice-

versa through a TTL connector. 

 

15.1

 

DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT)

 

1.

 

Turn OFF the instrument by means of the ON/OFF key, insert the 

“Hot Key” 

and then turn the unit 

ON. 

2.

 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the controller memory, the 

doL

”  message  is  blinking.  After  10  seconds  the  instrument  will  restart  working  with  the  new 

parameters. At the end of the data transfer phase the instrument displays the following messages: 

end

“ for right programming. The instrument starts regularly with the new programming.

 

err

” for 

failed programming.  In this case turn the unit off and then on if you want to restart the download 

again or remove the “

Hot key

” to abort the operation.

 

15.2

 

UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)

 

1.

 

When the XM unit  is ON, insert the “

Hot key

” and push 

“UP”

 key. 

2.

 

The UPLOAD begins; the “

uPL

” message is blinking.

 

3.

 

Remove the 

“Hot Key”.

 

 

At the end of the data transfer phase the instrument displays the following messages: 

 

end

 

“ for right programming.

 

 

err

” for failed programming. In this case push “SET” key if you want to restart the programming 

again or remove the not programmed “

Hot key

 

16.

 

TECHNICAL DATA 

CX660 and CH660 keyboard 

Housing: 

self extinguishing PC+ABS.

 

Case:

 

CX660 

facia 35x77 mm; depth 18mm; 

CH660 

facia 38x80 mm; depth 18mm 

Mounting:

 panel mounting in a 29x71 mm panel cut-out  

Protection: 

IP20; 

Frontal protection:

 IP65 

Power supply: 

from

 XM600K 

power module

 

Display

: 3 digits, red LED, 14,2 mm high 

Optional output: 

buzzer

 

 

Power modules  

Housing: 

8 DIN 

Power supply: 

depending on the model  110Vac 

 10% - 230Vac 

 10% 

 

Overvoltage Category: 

III

 

Rated power: 

9VA max.

 

Rated Impulse Voltage: 

2500V 

Software class: 

Terminal connections: 

Screw terminal block 

 1,6 mm

2

 heat-resistant wiring and 5.0mm Faston, wire 

section <= a 2.5mm2 

Data storing

: on the non-volatile memory (EEPROM) 

Type of action: 

1B 

Pollution Degree: 

2

 

Ambient operating temperature: 

-10T60°C 

Shipping and storage temperature:

 -40T85°C 

Relative humidity:

 20

85% (no condensing) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable) 

Measuring and regulation range:  

 

NTC / NTC-US probe: 

-40÷110°C (-58÷230°F).  

 

PTC probe:

 -50÷150°C (-67 ÷ 302°F) 

 

Pt1000 probe:

 -100 ÷ 100°C (-148 ÷ 212°F) 

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit 

Digital inputs

: 3 free of voltage  

Inputs

: up to 4 NTC/PTC/Pt1000 probes 

Serial output:

 RS485 with ModBUS - RTU and LAN 

Relay outputs: 

Total current on loads MAX. 16A

 

Solenoid Valve:

 relay SPST 5(3) A, 250Vac  

defrost:

 relay SPST 16 A, 250Vac  

fan:

 relay SPST 8 A, 250Vac

 

light: 

relay SPST 16 A, 250Vac  

alarm (XM670K): 

SPDT relay 8 A, 250Vac

 

Aux (XM670K):

 SPST relay 8 A, 250Vac 

Optional output (AnOUT) DEPENDING ON THE MODELS: 

 

PWM / Open Collector outputs:

 PWM or 12Vdc max 40mA 

 

Analog output: 

4÷20mA

 

or 0÷10V 

Purpose of control: 

operating control 

Construction of control: 

incorporated control, intended to be used in Class I or Class II equipment. 

 

 

Summary of Contents for Dixell XM660K

Page 1: ...TKEY connector can be used to connect X REP display Depending on the model 4 INSTALLATION AND MOUNTING This device can operate without any user interface but normal application is with Dixell CX660 or CH660 keyboard CX660 CH660 Fig A The CX660 or CH660 keyboard shall be mounted on vertical panel in a 29x71 mm hole and fixed using the special bracket supplied as shown in Fig A The temperature range...

Page 2: ... SET POINT FOR AIR TEMPERATURE REGULATION The thermostat set point is the value that will be used to regulate the air temperature The regulation output is controlled by the electronic valve or by the relay BEGIN Press SET button for 3 sec the measurement units will blink together Value modification or With the arrows it s possible to change the value within the LS and US parameters value EXIT By p...

Page 3: ... The LSn and LAn parameter are only to show the actual settings read only See the following example of configuration DAILY DEFROST FROM RTC CbP y EdF rtC IdF Parameter for safety reason force the value of Idf at 1 respect to the interval between two Ld parameters The IdF timer is reinitialized after defrost and at every power on DEFROST START at the time selected by the parameters Ld1 to Ld6 or Sd...

Page 4: ...work making all the other controllers start their own cycle This allows a perfect synchronisation of the defrost in the whole multiplexed cabinet according to LMd parameter Selecting dPA and dPb probes and by changing the dtP and ddP parameters the defrost can be started when the difference between dPA and dPb probes is lower than dtP for all ddP time This is useful to start defrost when a low the...

Page 5: ...om temperature If rPb nP the regulation is performed with real value of rPA rP3 Regulation probe 3 nP P1 P2 P3 P4 P6 third probe used to regulate room temperature with rPd rAb Aur LoE HiE rP4 Regulation probe 4 nP P1 P2 P3 P4 P6 fourth probe used to regulate room temperature with rPd rAb Aur LoE HiE rPd Temperature Regulation Strategy rPA rAb Aur LoE HiE rPA temperature detected by the probe set i...

Page 6: ...saving nt second map enabling cLn clean function dEn defrost off CP1 compressor 1 safety CP2 compressor 2 safety d1d Time interval delay for digital input alarm 0 255 min Time interval to calculate the number of the pressure switch activation when i1F PAL If I1F EAL or bAL external alarms d1d parameter defines the time delay between the detection and the successive signalling of the alarm If i1F d...

Page 7: ...N LIG This function allows to turn ON and OFF the light relay by using the digital input as external switch 14 8 REMOTE ON OFF ONF This function allows to switch ON and OFF the instrument 14 9 FHU NOT USED This function allows to change the kind of regulation from cooling to heating and viceversa 14 10 ENERGY SAVING INPUT ES The Energy Saving function allows to change the set point value as the re...

Page 8: ...AL tEr Pr2 Probe for temperature alarm ALC Ab Pr1 Temperature alarm configuration relative absolute Label M1 M2 M3 M4 Menù Parameter description ALU 10 10 10 10 Pr1 High temperature alarm setting ALL 30 30 30 30 Pr1 Low temperature alarm setting AHy 1 0 Pr2 Differential for temperature alarm ALd 15 15 15 15 Pr1 Temperature alarm delay rA2 nP Pr2 Probe for temperature alarm 2 A2U 150 150 150 150 Pr...

Page 9: ...tion LCL y Pr2 Light on during cleaning mode FCL y Pr2 Fan on during cleaning mode MAP 1 M Pr2 Map selection MP1 1 M Pr2 Map selection loaded by digital input Adr 1 Pr1 Modbus address br 96 Pr2 Baud Rate selection for ModBus 9600 or 19200 EMU nu Pr2 Emulation previous version 2V8 3V8 4V2 rEL 5 4 Pr2 Release code firmware only read SrL Pr2 Sub release firmware only read Ptb Pr2 Map EEPROM ID Pr2 32...