background image

 

 

1592023220 XM660K_XM670K GB r5.4 2021.09.01 

XM660K - XM670K  

          4/9 

 

Display 

Causes 

Notes 

 

OTHERS 

 

EE 

EEPROM serious problem. 

Output OFF. 

Err 

Error with upload/download parameters. 

Repeat the operation. 

End 

Parameters have been correctly 

transferred.  

 

dEF 

Defrost is progress 

 

cLn 

Cleaning function active 

 

11.1

 

ALLARM RECOVERY 

Probe alarms 

P1

P2,

 

P3

 and 

P4

 start some seconds after the fault in the related probe; they automatically 

stop some seconds after the probe restarts normal operation. Check connections before replacing the 

probe. 

Temperature alarms 

HA

LA,

 

HA2

 and 

LA2

 automatically stop as soon as the temperature returns to 

normal values. 

Alarms 

EA

 and 

CA 

(with 

i1F

 = 

bAL

)

 

recover as soon as the digital input is disabled. Alarm 

CA

 (with 

i1F

 

PAL

) recovers only by 

switching off and on

 the instrument. 

 

12.

 

CONTROLLING LOADS 

12.1

 

TEMPERATURE PROBE REFERENCE FOR REGULATION 

Up to 5 temperature probe can be used for the temperature regulation. 

It’s possible to set the probes used for temperature regulation. Up to 

4 Temperature inputs Pb1, Pb2, Pb3, 

Pb4,  can be used. To support above function, the parameters rPA, rPb, rP3, rP4, are used. 

Which temperature probe methods of combine is set by par. rPd among the following: Average, Minimum, 

Maximum, First, or Mix. 

 

rPd = rPA: 

temperature detected by the probe set in the parameter rPA

 

rPd = rAb: 

mix between rPA and rPb defined by rPE parameter 

rPd = AUr: 

average temperature of all the probes defined as Regulation Probe in the parameters rPA, 

rPb, rP3, rP4 

rPd  =  LoE

:  minimum  value  among  all  the  temperature  probes  defined  as  Regulation  Probe  in  the 

parameters rPA, rPb, rP3, rP4 

rPd  =  HiE: 

maximum  value  among  all  the  temperature  probes  defined  as  Regulation  Probe  in  the 

parameters rPA, rPb, rP3, rP4 

12.1.1

 

Sensors failure 

In case of multiple temperature sensor regulation: (rPd = rAb, Aur, LoE, HiE), and with sensor failure, the 

remaining sensors are used for the regulation. 

In case of all sensor failure, the regulation will be performed according to Con and COF parameters 

12.2

 

DUAL TEMP MODE OPERATION 

Controller can have up to 4 pre-set regulation. 

The preset regulation is set in the parameter MAP. 

By  digital  input  or  supervising  system  is  possible  to  enable  the  second  regulation  mode,  set  in  the 

parameter MP1. 

In this way a dual temp case can be easily set and controlled. 

12.2.1  Second map function by digital input configuration 

By setting on digital input among i1F, i2F, i3F as the “nt” the map set in the parameter 

MP1is loaded when 

the digital input is enabled.  

 

12.3

 

THE SOLENOID VALVE 

 

The regulation is performed according to the temperature measured by the thermostat probe that can be 

physical probe or virtual probe obtained by a weighted average between two probes (see parameters 

table description) with a positive differential from the set point. If the temperature increases and reaches 

set point plus differential the solenoid valve is opened and then it is closed when the temperature reaches 

the set point value again.  

In case of fault in the thermostat probe the opening and closing time of solenoid valve is configured by 

Con

” and “

CoF

” parameters.

 

12.4

 

PUMP DOWN BEFORE DEFROST 

The following parameters has been added: 

Pdt

 pump down type (nu; FAn; F-C) 

With 

Pdt = nu, 

 the pump down is not enabled. 

With 

Pdt = Fan

, when a defrost trigger is given: 

a.

 

Compressor relay will be open. 

b.

 

EEV valve (if present): 

i.

 

will be closed with CrE = n, y 

ii.

 

will be open with CrE =EUP or EU5 

c.

 

Fan will be forced on for Pdn time 

 

With 

Pdt = F-C,

 when a defrost trigger is given: 

a.

 

EEV valve (if present): 

i.

 

will be closed with CrE = n, y 

ii.

 

will be open with CrE =EUP or EU5 

b.

 

Compressor relay and Fan will be forced on for Pdn time 

 

Pdn

 pump down duration (0 to 255 min) 

12.5

 

DEFROST 

 

Defrost starting 

In any case, the device check the temperature read by configured defrost probe before starting 

defrost procedure, after that: 

-

 

(If RTC is present)Two 

defrost modes are available through the “

tdF

” parameter: defrost with electrical 

heater and hot gas defrost. The defrost interval is controlled 

by parameter “

EdF

”: (EdF = rtc) defrost is 

made in real time depending on the hours set in the parameters 

Ld1..Ld6

 in workdays and in 

Sd1…Sd

6

 

on 

holidays; (EdF = in) the defrost is made every “

IdF

” time;

 

-

 

defrost cycle starting can be operated locally (manual  activation by means of the keyboard or digital 

input or end of interval time) or the command can come from the Master defrost unit of the LAN. In this 

case the controller will operate the defrost cycle following the parameters it has programmed but, at 

the end of the drip time, will wait that all the other controllers of the LAN finish their defrost cycle before 

to re-start the normal regulation of the temperature according to 

dEM

 parameter; 

-

 

Every time any of the controller of the LAN begin a defrost cycle it issue the command into the network 

making all the other controllers start their own cycle. This allows a perfect synchronisation of the defrost 

in the whole multiplexed cabinet according to 

LMd

 parameter; 

-

 

Selecting 

dPA

 and 

dPb

 probes and by changing the 

dtP

 and 

ddP

 parameters the defrost can be started 

when the difference between dPA and dPb probes is lower than dtP for all ddP time. This is useful to 

start defrost when a low thermal exchange is detected. If 

ddP=0

 this function is disabled;

 

 

Minimum defrost time 

The “

ndt

” (0÷MnF) Minimum Defrost Time, set the minimum defrost duration, when the defrost is ended 

by evaporator temperature probe. 

The 

ndt

 time is taken in account everytime the defrost is trigged, independently form the value of end 

defrost temperature probe and end defrost digital input status. 

 

Defrost ending 

-

 

When defrost is started via rtc, the maximum duration of defrost is obtained from 

Md

 parameter and 

the  defrost  end  temperature  is  obtained  from 

dtE

  parameter  (and 

dtS

  if  two  defrost  probes  are 

selected).  

-

 

If 

dPA

 and 

dPb

 are present and 

d2P=y

 the instrument stops the defrost procedure when 

dPA

 is higher 

than 

dtE

 temperature and 

dPb

 is higher than 

dtS

 temperature; 

 

At the end of defrost the drip time is controlled through the “

Fdt

” parameter. 

 

12.5.1

 

Kind of defrost 

The kind of defrost is set by parameter tdF among the following possibilities 

 

tdF = Air

natural defrost

. Defrost is made by opening the compressor/solenoid relay. The fan during 

defrost depends on the parameter Fnc. Defrost relay is off. The valve is closed 

tdF = EL: defrost with electrical heater

:  Defrost is made by opening the compressor/solenoid relay. 

The fan during defrost depends on the parameter Fnc. Defrost relay is on. The valve is 

closed 

tdF = in: hot gas defrost

. Defrost is made by closing  the compressor/solenoid relay. The fan during 

defrost depends on the parameter Fnc. Defrost relay is on. The valve opening percentage 

during the defrost  is set by the par. oPd. 

 

12.6

 

ON DEMAND DEFROST 

Description

 

Controller can perform on demand defrost. It is based on the behavior of evaporator temperature. 

Controller monitors the evaporator temperature and triggers a defrost if some conditions are satisfied.  For 

defrost efficiency its’ important to place the “end defrost probe”, usually P2, in the coldest place of the 

evaporator, usually immediately after the expansion valve.  

***NOTE

: Because of different type of evaporators and consequentially behaviors, it’s warmed suggested 

to test and validate this algorithm in a climatic chamber before applying it in the field. 
 

Parameters & settings: 

The «On Demand Defrost» can be activated with the following settings: 

CrE=”n” , EdF=”Aut”

 

cdt: evaporator temperature differential to trigger a defrost 

(default cdt = 4°K) 

nbd

minimum compressor run before automatic defrost 

(or minimum time of activation of solenoid 

valve) it has to be set properly. It prevents defrost from starting (default nbd = 4.0h) 

Mbd

max compressor run before automatic defrost

 (or max time of activation of solenoid valve): it 

has to be set properly. If reached a defrost is triggered (default Mbd = 16.0h)   

nct

minimum evap. temperature

, it has to be set properly. a defrost is triggered when this 

temperature reached (default nct  = -30°C) 

 

NOTE

: with CrE=

”y” or CrE=”EUP” or CrE=EU5  only «RTC defrost»  and «interval defrost» are allowed. 

 

With EdF=”Aut” & CrE=”y” or CrE=”EUP” or CrE=EU5  the «interval defrost» will be performed, as with 

EdF = in 

 

Exceptions

1.

 

A  defrost  cannot  be  triggered  if  the  compressor  has  not  ran  more  than  minimum  time  (

nbd

 

parameter

) since the last defrost or initial power up. (Resolution hh.m) 

2.

 

If the compressor has ran for more than maximum time since the last defrost or initial power up 

(

Mbd

 

parameter

), a defrost is triggered regardless of coil temperature . 

3.

 

If  the  coil  temperature  reaches  very  low  temperature,  (

nct

 

parameter

),  a  defrost  is  triggered 

regardless of 

cdt

 value.  

12.7

 

FANS 

 

CONTROL WITH RELAY 

The fan control mode is selected by means of the “

FnC

” parameter:

 

C-n

 = running with the solenoid valve, OFF during the defrost;  

C-y

 = running with th1e solenoid valve, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

 

An additional parameter “

FSt

” provides the setting of temperature, detected by the evaporator probe, 

above  which  the  fans  are  always  OFF.  This  can  be  used  to  make  sure  circulation  of  air  only  if  his 

temperature i

s lower than set in “

FSt

”.

 

 

CONTROL WITH ANALOG OUTPUT (if present) 

The regulation probe is set in the parameter 

FAP 

 

 

The  modulating  output  (

trA=rEG

)  works  in 

proportional  way  (excluding  the  first 

AMt 

seconds  where  the  fans  speed  is  the 

maximum). The regulation set point is relative 

to regulation set point and is indicated by 

ASr, 

the proportional band is always located above 

SET+ASr

 value and its value is 

PbA

. The fan 

are  at  minimum  speed  (

AMi)

  when  the 

temperature  read  by  fan  probe  is 

SET+ASr

 

and the fan is at maximum speed (

AMA

) when 

the temperature is 

SET+ASr+PbA

NOTE: 

to use properly this function FAP has to be set as the thermostat probe. 

 

Summary of Contents for Dixell XM660K

Page 1: ...TKEY connector can be used to connect X REP display Depending on the model 4 INSTALLATION AND MOUNTING This device can operate without any user interface but normal application is with Dixell CX660 or CH660 keyboard CX660 CH660 Fig A The CX660 or CH660 keyboard shall be mounted on vertical panel in a 29x71 mm hole and fixed using the special bracket supplied as shown in Fig A The temperature range...

Page 2: ... SET POINT FOR AIR TEMPERATURE REGULATION The thermostat set point is the value that will be used to regulate the air temperature The regulation output is controlled by the electronic valve or by the relay BEGIN Press SET button for 3 sec the measurement units will blink together Value modification or With the arrows it s possible to change the value within the LS and US parameters value EXIT By p...

Page 3: ... The LSn and LAn parameter are only to show the actual settings read only See the following example of configuration DAILY DEFROST FROM RTC CbP y EdF rtC IdF Parameter for safety reason force the value of Idf at 1 respect to the interval between two Ld parameters The IdF timer is reinitialized after defrost and at every power on DEFROST START at the time selected by the parameters Ld1 to Ld6 or Sd...

Page 4: ...work making all the other controllers start their own cycle This allows a perfect synchronisation of the defrost in the whole multiplexed cabinet according to LMd parameter Selecting dPA and dPb probes and by changing the dtP and ddP parameters the defrost can be started when the difference between dPA and dPb probes is lower than dtP for all ddP time This is useful to start defrost when a low the...

Page 5: ...om temperature If rPb nP the regulation is performed with real value of rPA rP3 Regulation probe 3 nP P1 P2 P3 P4 P6 third probe used to regulate room temperature with rPd rAb Aur LoE HiE rP4 Regulation probe 4 nP P1 P2 P3 P4 P6 fourth probe used to regulate room temperature with rPd rAb Aur LoE HiE rPd Temperature Regulation Strategy rPA rAb Aur LoE HiE rPA temperature detected by the probe set i...

Page 6: ...saving nt second map enabling cLn clean function dEn defrost off CP1 compressor 1 safety CP2 compressor 2 safety d1d Time interval delay for digital input alarm 0 255 min Time interval to calculate the number of the pressure switch activation when i1F PAL If I1F EAL or bAL external alarms d1d parameter defines the time delay between the detection and the successive signalling of the alarm If i1F d...

Page 7: ...N LIG This function allows to turn ON and OFF the light relay by using the digital input as external switch 14 8 REMOTE ON OFF ONF This function allows to switch ON and OFF the instrument 14 9 FHU NOT USED This function allows to change the kind of regulation from cooling to heating and viceversa 14 10 ENERGY SAVING INPUT ES The Energy Saving function allows to change the set point value as the re...

Page 8: ...AL tEr Pr2 Probe for temperature alarm ALC Ab Pr1 Temperature alarm configuration relative absolute Label M1 M2 M3 M4 Menù Parameter description ALU 10 10 10 10 Pr1 High temperature alarm setting ALL 30 30 30 30 Pr1 Low temperature alarm setting AHy 1 0 Pr2 Differential for temperature alarm ALd 15 15 15 15 Pr1 Temperature alarm delay rA2 nP Pr2 Probe for temperature alarm 2 A2U 150 150 150 150 Pr...

Page 9: ...tion LCL y Pr2 Light on during cleaning mode FCL y Pr2 Fan on during cleaning mode MAP 1 M Pr2 Map selection MP1 1 M Pr2 Map selection loaded by digital input Adr 1 Pr1 Modbus address br 96 Pr2 Baud Rate selection for ModBus 9600 or 19200 EMU nu Pr2 Emulation previous version 2V8 3V8 4V2 rEL 5 4 Pr2 Release code firmware only read SrL Pr2 Sub release firmware only read Ptb Pr2 Map EEPROM ID Pr2 32...

Reviews: