1592031000 Univ-R4 GB - r1.1 - 2012.07.23                         Universal-R 

                                                                   15/20 

 

8.

 

BUTTONS AND THEIR FUNCTIONS  

8.1

 

SINGLE BUTTON FUNCTIONS 

Table 5: single button functions 

BUTTON 

FUNCTION 

 

Type Controller menu: keep this button pressed for at least 3 sec within 1 min after power on to enter the “Type Controller Menu” (tC). 
AUX output control: Switches the AUX relay output (if enabled as such).  

 

Manual Defrost: keep this button pressed for 3 s to start a manual defrost cycle. The defrost icon will illuminate. (Not possible if parameter tC 
= 1 or 7). 

 

Display current set point: after pressing and releasing this button, the set point will be displayed for 5 sec. This will not allow the set point to 
be altered. 
Changing set point value: keep this button pressed for at least 2 sec. Set point change mode is entered indicated by the small led’s 
flashing.  Change the set point using the UP and DOWN buttons. The new value can be stored either by pressing SET button (the instrument 
restores temperature display) or by waiting the exit time-out to expire (15 sec). 

 

(UP): to see the max stored temperature; in programming mode it browses the parameter codes or increases the displayed value. 

 

(DOWN): to see the min stored temperature; in programming mode it browses the parameter codes or decreases the displayed value. 
Keep press 3sec just after powering on the device (and within the first 60sec) to start automatic probe recognising. 

 

Keep pressed 2 sec to switch the instrument off when the parameter onF 1

.

 

 

8.2

 

BUTTON COMBINATION FUNCTIONS 

Table 6: button combination functions 

COMBINATION 

FUNCTION 

 

 

 

Lock & unlock the keyboard: keeping both buttons pressed for 3 sec will lock or unlock the keyboard. The display 
will flash PoF or Pon for a few seconds to confirm locking or unlocking respectively. 

 

+

 

 

 

Enter programming mode: keep both buttons pressed for 3 sec, release them and then press them again for 8 sec. 
The first label of Pr2 level will be displayed. 

 

+

 

 

 

Exit programming mode: press together to return to normal display. 

9.

 

PROGRAMMING MODE  

9.1

 

USER PROGRAMMING LEVEL – PR1 

To enter programming level Pr1 (user programming level), keep both SET and DOWN buttons pressed for 3 sec. The first parameter 
label  will  appear.  Browse parameter list by using the UP or DOWN keys. Press SET to see a parameter’s current value and UP or 
DOWN keys to alter its value. Press SET to confirm change (the display will blink for 3 sec and then the next parameter will appear) or 
by waiting for the menu timeout to expire (15 sec). If no parameter is available for changes in Pr1 level, a noP label will be show. 
 

9.1

 

PROTECTED PROGRAMMING LEVEL – PR2 (ALL VISIBLE PARAMETERS CAN BE FOUND HERE) 

First enter Pr1 level (as described above) then with any parameter label displayed keep both SET and DOWN buttons pressed for 8 
sec.  The  first parameter label will appear. Browse parameter list by using the UP or DOWN keys. Press SET to see a parameter’s 
current value and UP or DOWN keys to alter its value. Press SET to confirm change (the display will blink for 3 sec and then the next 
parameter will appear) or by waiting for the menu timeout to expire (15 sec).  
From  Pr2  level  it  is  also  possible  to  add  or  remove  any  parameter  to  /  from  Pr1  by  pressing  both  SET  & DOWN while its label is 
displayed.  Accessibility of any particular parameter via Pr1 level is confirmed by the alarm LED lighting up while its label is displayed 
 
WARNING:  if  no  button  is  pressed  for  15  sec,  any modified value will be stored into memory and the controller will return to the normal 
display mode. 
 

Summary of Contents for Dixell Universal-R

Page 1: ...UNIVERSAL R ...

Page 2: ...dedicated button during a fixed time interval at start up NEW FRONT FASCIA DESIGN Display with illuminated icons to indicate loads alarms status indications Six buttons give direct access to main functions and menu DOUBLE EVAPORATOR DEFROST FUNCTION A new feature allows defrost control of twin evaporators The 4th AUX relay and probe 3 Pb3 control defrost of the second evaporator Only when both hav...

Page 3: ...FEATURES OF THE UNIVERSAL R ___________________________________________________16 11 THERMOSTAT OVERRIDE not available when parameter tC 1 or 7 ______________________________16 12 DEFROST TYPES _________________________________________________________________________16 13 EVAPORATOR FAN CONTROL only when parameter tC 5 or 6 __________________________________16 14 SPECIAL APPLICATIONS DEAD BAND CON...

Page 4: ...he wires for probes electrical loads and the power supply are separated and far enough away to each other without crossing or intertwining In case of applications in industrial environments the use of mains filters our mod DIXL930 in parallel with inductive loads could be useful Heating applications Do not exceed 105 C with the NTC probes supplied For higher temperatures up to a maximum of 150 C u...

Page 5: ...r auto recognition to work 3 If 1 minute expires before you have completed quick set up either turn OFF ON power to start set up again or enter parameter as per the instructions and adjust your parameter settings manually see Section 9 Table 1 parameter tC settings Parameter tC Type of Control Required probes 1 On Off thermostat Cooling x 1 2 Off cycle defrost timed x 1 3 Electrical Hot Gas defros...

Page 6: ...ycle Defrost Controller Parameter tC 3 Forced defrost controller time initiated time terminated Parameter tC 4 Forced defrost controller time initiated temperature terminated Parameter tC 5 Forced defrost controller time initiated temperature terminated with evaporator fan delay after defrost Parameter tC 6 Double evaporator applications Parameter tC 7 Heating applications ...

Page 7: ...C 2 F 2 0 C 2 F 2 0 C 2 F 2 0 C 2 F 2 0 C 2 F Minimum Set Point limit 55 C to Set Point 67 F to Set Point 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F Maximum Set Point limit Set Point to 150 C Set Point to 302 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F Anti short cycle delay 0 to 50 min 1 1 1 1 1 1 0 Second c...

Page 8: ... Thermostat probe calibration 12 0 to 12 0 C 21 to 21 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F Evaporator probe presence 0 evaporator probe not present 1 evaporator probe present 1 1 1 Evaporator probe calibration 12 0 to 12 0 C 21 to 21 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F Third probe presence 0 third probe not present 1 third probe present 1 1 1 1 1 1 Third probe calibr...

Page 9: ...tart regulation with door open alarm 0 No 1 Yes 0 0 0 0 0 0 0 Low temperature alarm of condenser 55 to 150 C 67 to 302 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F High temperature alarm of condenser 55 to 150 C 67 to 302 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F Differential for temperature condenser alarm recovery 0 1 to 25 5 C 1 to 45 F 5 C 5 F 5 C 5 F 5 C 5 F 5 C 5 F...

Page 10: ...temperature decreases and reaches set point minus differential the regulation output is activated and then turned off when the temperature reaches the set point value again Minimum set point limit 55 C to SET or 67 F to SET sets the lower limit of set point adjustment Maximum set point limit SET to 150 C or SET to 302 F sets the upper limit of set point adjustment Anti short cycle delay 0 to 50min...

Page 11: ...or second defrost 0 to 255min when P3P 0 not evaporator probe timed defrost it sets the defrost duration when P3P 1 defrost end based on temperature it sets the maximum length for defrost Note The P3 probe will be automatically set as second evaporator probe by the tC parameter Second termination temperature 55 to 50 C or 67 to 122 F sets the temperature measured by the second evaporator probe P3 ...

Page 12: ...ith label D I 2 Pb3 Input operates as digital input 1 present the third input the one signed with label D I 2 Pb3 Input operates as third probe Third probe calibration 12 0 to 12 0 C or 21 to 21 F adjustment for third probe named Evap 2 on the label offset Display resolution 0 with decimal point 1 without decimal point Temperature measurement unit 0 Celsius 1 Fahrenheit Warning If you alter the se...

Page 13: ...ed by closing the circuit 1 the digital input is activated by opening the circuit Time interval delay for digital input 1 alarm 0 to 255min it defines the time delay between the detection and the subsequent signalling of the alarm Time interval delay for digital input 2 alarm 0 to 255min it defines the time delay between the detection and the subsequent signalling of the alarm Compressor and fan s...

Page 14: ...ture alarm of the condenser is active 0 the compressor keeps on working if a low temperature alarm at the condenser is active 1 the compressor is switched off while the low temperature alarm is active The regulation will restart after elapsing AC delay time Temperature set point change during the Energy Saving cycle 30 0 to 30 0 C or 54 to 54 F sets the deviation from the normal set point during t...

Page 15: ...yboard The display will flash PoF or Pon for a few seconds to confirm locking or unlocking respectively Enter programming mode keep both buttons pressed for 3 sec release them and then press them again for 8 sec The first label of Pr2 level will be displayed Exit programming mode press together to return to normal display 9 PROGRAMMING MODE 9 1 USER PROGRAMMING LEVEL PR1 To enter programming level...

Page 16: ...it degrees FLASHING Programming mode 11 THERMOSTAT OVERRIDE not available when parameter tC 1 or 7 For rapid chilling or freezing the thermostat can be overridden by pressing the UP button until the icon lights up The compressor will run in continuous mode irrespective of temperature for the time period set in parameter CCt Normal operation will then resume automatically The cycle can also be term...

Page 17: ... re start if parameter rrd 1 EA Alternating with room temperature Generic external alarm Alarm output ON Other outputs unchanged bAL Alternating with room temperature Serious external alarm Alarm output ON Other outputs OFF 15 1 MUTING ALARM BUZZER RELAY The alarm buzzer can be muted by pressing any button The controller will briefly show the reset rES label Parameter tbA defines how the alarm rel...

Page 18: ...ectly measure the average room temperature Place the defrost termination probe among the evaporator fins in the coldest place where most ice is formed far from heaters or from the warmest place during defrost to prevent premature defrost termination 20 TECHNICAL DATA Housing Self extinguishing ABS Size Frontal 32x74 mm depth 70 mm Mounting Panel mounting in a 71x29 mm panel cut out Frontal protect...

Page 19: ...d resistance value Change probe type or alter parameter PbC Fit evaporator probe or alter parameter tC Display flashing EE Data corruption Check for electrical spikes and interference Fit filters DIXL930 DIXL932 Ensure probe cables are separated from power cables Re check all parameter settings Replace controller if still not working Display flashing dA Door has been left open too long Shut the do...