Digital I/O state
This screen shows the current status of the digital inputs and outputs.
Digital I/O State
Inputs: 0110000
Outputs: 0000100
The top line of the screen shows the start, stop, reset and programmable inputs (A and B, then inputs on the I/O expansion card (if
fitted).
The bottom line of the screen shows programmable output A, the fixed Run output, programmable outputs B and C, then the outputs
on the expansion card (if fitted).
Temperature Sensors State
This screen shows the state of the motor thermistors and RTD/PT100s.
Temp Sensors State
Thermistor: O
RTD/PT100s:OOOOOOO
S = Shrt H=Hot C=Cld O=Opn
RTD/PT100s B to G are only available if the RTD/PT100 and Ground Fault expansion card is fitted.
8.9.4
Logs menu
The Logs Menu provides information on events, trips and starter performance.
To open the Logs Menu, press the
M
button, then scroll to Logs and press
M
again.
Trip log
The Trip Log stores details of the eight most recent trips, including the date and time the trip happened. Trip 1 is the most recent
and trip 8 is the oldest stored trip.
To open the Trip Log:
1. Open the Logs Menu.
2. Scroll to Trip Log and press
M
.
3. Use the and buttons to select a trip to view, and press
M
to display details.
To close the log and return to the main display, press
repeatedly.
Event log
The Event Log stores time-stamped details of the starter's 99 most recent events (actions, warnings and trips), including the date
and time of the event. Event 1 is the most recent and event 99 is the oldest stored event.
To open the Event Log:
1. Open the Logs Menu.
2. Scroll to Event Log and press
M
.
3. Use the and buttons to select an event to view, and press
M
to display details.
To close the log and return to the main display, press
repeatedly.
8.9.5
Performance counters
The performance counters store statistics on the starter's operation:
Hours run (lifetime and since counter last reset)
Number of starts (lifetime and since counter last reset)
Motor kWh (lifetime and since counter last reset)
Number of times the thermal model has been reset
The resettable counters (hours run, starts and motor kWh) can only be reset if the Adjustment Lock (Pr
15C
) is set to Read & Write.
To view the counters:
1. Open the Programming Menu and select Counters.
2. Use the and buttons to scroll through the counters. Press
M
to view details.
3. To reset a counter, press
M
then press
M
to confirm the action.
To return to the previous level, press
.
NOTE
The reset counters function is protected by the access code.