To stop a jog operation, perform one of the following:
Remove the jog command.
Press the
STOP
button on the keypad.
Activate Emergency Stop using the keypad programmable inputs.
Jog will recommence at the end of a restart delay if the jog command is still present. All other commands except the above, will be
ignored during jog operation.
7.5
Inside delta operation
Adaptive Control, Jog, Brake and PowerThrough functions are not supported with inside delta (six-wire) operation. If these
functions are programmed when the starter is connected inside delta the behaviour is as given below:
Table 7-5 Inside delta compatibility
Adaptive Control Start
The starter performs a constant current start.
Adaptive Control Stop
The starter performs a TVR soft stop if Pr
2I
Stop Time
is >0 secs. If Pr
2I
is set to 0 secs the
starter performs a coast to stop.
Jog
The starter issues a warning with the error message Unsupported Option.
Brake
The starter performs a coast to stop.
PowerThrough
The starter trips with the error message Lx-Tx Shorted.
For more information on PowerThrough, see Pr
15D
Shorted SCR Action
.
NOTE
When connected in inside delta, current imbalance is the only phase loss protection that is active during run. Do not
disable current imbalance protection (Pr
5C
) during inside delta operation.