Modbus Module User Guide
7
Issue 1
www.controltechniques.com
5.1
Modbus register
Table 5-1 Modbus register
Register
Address
Type
Description
Digistart
CS
Digistart IS
Remote
Keypad
40002
Single
1 = Start
Command
write
2 = Stop
3 = Reset
4 = Quick stop (coast to stop)
5 = Forced communication trip
6 = Start using Parameter Set 1
3
7 = Start using Parameter Set 2
3
40003
Multiple
Bit
Description
Starter
read
0 to 3
1 = Ready
status
2 = Starting
3 = Running
4 = Stopping (including braking)
5 = Restart delay (including Temperature
check)
6 = Tripped
7 = Program mode
8 = Jog forward
9 = Jog reverse
4
1 = Positive phase sequence (only valid if bit
6 = 1)
5
1 = Current exceeds full load current
6
0 = Uninitialised
1 = Initialised
7
0 = Communications are OK
1 = Communications device fault
40004
Trip Code
Multiple
read
See Trip Code table
40005
1
Motor current
Multiple
read
Average 3 phase motor current (A)
40006
Motor
temperature
Multiple
read
Motor 1 temperature (thermal model)
40007
Multiple
Bit
Description
Product type
read
0 to 2
Product parameter list version
and version
3 to 7
4 = Digistart CS
8 = Digistart IS
40008
Serial protocol
version
Multiple
read
40009
2
Parameter
management
Single
write and
multiple
read
Pr
1A
Motor Full Load Current
to Digistart IS maximum
register address (starter software dependent)
1
For Digistart IS models IS-0076B and smaller this value will be 10 times greater than the value displayed on the keypad.
2
See the relevant soft starter literature for a complete parameter list. The first product parameter is always allocated to register 40009.
The last product parameter is allocated to register 40XXX, where XXX = 008 plus total number of available parameters in the product.
3
Ensure that the programmable input is not set to Motor Set Select before using this function.
NOTE
If Pr
3A
Input A Function
is set to motor set select, this will cause a conflict with motor set selection via serial
communications.