Modbus Module User Guide
15
Issue 1
www.controltechniques.com
7.6.2
Programmable Parameters
The Remote Keypad offers the following programmable parameters:
Table 7-1 Programmable parameters
Parameter
Number
Description
Default
Setting
Adjustable Range
1
RS485 network
baud rate
4
(9600 baud)
2 = 2400 baud
3 = 4800 baud
4 = 9600 baud
5 = 19200 baud
6 = 38400 baud
2
RS485 network
satellite address
20
1 to 99
3
RS485 network
timeout
0 seconds
(= off)
0 to 100 seconds
4
RS485 network
protocol
1
(AP ASCII)
1 = AP ASCII protocol
2 = Modbus RTU protocol
5
Modbus protocol
parity
0
(no parity)
0 = no parity
1 = odd parity
2 = even parity
3 = 10-bit transmission
6
Motor FLC (A)
10
1 to 2868
7
Analog output
4 mA offset (%)
100
80 to 120
8
Start, Stop, Quick
stop function
disable
0
0 = Remote Keypad and Network start, stop, quick stop function enabled.
1 = Remote Keypad start, stop, quick stop function enabled. Network start, stop,
quick stop function disabled.
2
2 = Remote Keypad start, stop, quick stop function disabled. Network start, stop,
quick stop function enabled.
1
3 = Remote Keypad start, stop, quick stop function disabled. Network start, stop,
quick stop function disabled.
1,
2
9
Current
÷
10
0
0 = off (required for Digistart CS)
1 = on (not suitable for Digistart CS)
1
Remote Keypad Reset pushbutton is always enabled.
2
RS485 Network reset and forced communication trip functions are always enabled.
7.7
Troubleshooting
The Remote Keypad display and status indication LEDs can indicate abnormal operating and system conditions.
Table 7-2 Error codes
Display
Indication
Problem
Possible Solution
nEt
on display
A loss of communication has
been detected on the RS485
link to the network.
The Remote Keypad has an RS485 Network Timeout Protection setting (
Pr
3). This
error is reported when no communication occurs for longer than the timeout setting.
The system will become active as soon as communication is restored.
To clear
nEt
from the display, press the Data/Prog pushbutton momentarily or send
a Reset command from the network Master.
SP
flashing on
display
Soft starter is off and being
programmed from the serial
network.
Finish soft starter network programming procedure and exit Programming Mode.