Chapter 2 Instruction For Pre-installation 5
Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual
Table 2-1 Minimum clearance space for maintenance(unit: mm)
Location
CR025
CR035
Front
600
600
Rear
600
600
Note: the space is used for regular maintenance, such as replacing filter, fan, electrode humidifier and so on
Note
Contact Emerson for special application.
2.3 Environmental Requirements
2.3.1 Operation Environment
See Table 2-2 for details.
Table 2-2 Operation environment requirement
Item
Requirement
Ambient temperature
Indoor
18°C ~ 40°C
Outdoor
-20°C ~ +45°C, if a low temperature kit is configured, the lowest outdoor
operation temperature is -34°C
Protection level (indoor unit)
IP20
Altitude
< 1000m. Above that, please contact Emerson Network Power Co., Ltd.
Operation voltage range
(380 ~ 415)V ± 10%, 3N ~ 50Hz
2.3.2 Storage Environment
See Table 2-3 for details.
Table 2-3 Storage environment requirement
Item
Requirement
Storage environment
Indoor, clean (without dust)
Ambient humidity
< 95%RH
Ambient temperature
-33°C ~ +70°C
Storage time
Total transportation and storage time should not exceed six months. Otherwise, the performance
needs to be re-calibrated
2.4 Movement, Unpacking And Inspection
2.4.1 Transportation And Movement
Railroad transportation and shipping are the recommended means of transportation. If truck transportation is
unavoidable, choose roads that are less bumpy to protect the equipment.
The CRV+ air cooled AC unit is heavy (see Table 3-1 for the weight). It is recommended to use mechanical
handbarrow such as an electric forklift to unload and move the equipment to the place closest to the installation site.
If a forklift is used, insert the tines of the forklift below the pallet, as shown in Figure 2-2. Align the tines with the
center of gravity to prevent the equipment from falling over.