AGL_Ref_ST_ZO_E_Rev00 

 

21 

Start-up & operation 

 

WARNING 
Diesel  effect!

 

System  explosion!

  The  mixture  of  air  and  oil  at  high 

temperature can lead to an explosion. Avoid operating with air. 

 

 

IMPORTANT 
Oil  dilution!  Bearing  malfunction!

  It  is  important  to  ensure  that  new

 

compressors are not subjected to liquid abuse. Turn the crankcase heater on 
12 hours before starting the compressor. 

5.1  Strength-pressure test 

 

WARNING 
High  pressure!  Personal  injuries!

  Consider  personal  safety  requirements 

and refer to test pressures prior to test. 

 

 

IMPORTANT 
System  contamination!  Bearing  malfunction!

  Use  only  dry  nitrogen  for 

pressure testing. DO NOT USE other industrial gases. 

5.1.1  Compressor strength-pressure test 

The compressor has been strength-tested in the Emerson factory. Therefore, it is not necessary for 
the system manufacturer/installer to strength-test the compressor again. 

Scroll  compressors  are  divided  into  two  pressure  zones.  The  compressor  high-side  and  low-side 
maximum allowable pressures PS have to be respected at all times. 

5.1.2  System strength-pressure test 

A strength-pressure test of individual sections of the entire system is permitted. Once the compressor 
is isolated, the rest of the system can be tested with the required pressure values. 

The strength-pressure test can also be conducted with the compressor connected, but in that case 
the two pressure zones of the scroll compressor need to be respected: 

  System high-pressure section: 

o

 

Define the system high-

side PS ≤ compressor high-side PS. 

o

 

Isolate the high- and low-pressure sections of the system by closing valves, solenoid valves, 
expansion valves or by other means. 

o

 

Use  the  internal  check  valve  of the  compressor  on  the  discharge  side  or  add  an  external 
check valve. T

o protect the compressor internal check valve, observe a maximum pressure 

delta of 

≤ 25 bar between the high-pressure side and the low-pressure side.

 

o

 

Activate the check valve with a fast pressure increase. Once the check valve is activated, 
the pressure increase can be slowed down. 

o

 

At this stage the system test pressure of 1.1 x system high-side PS can be applied for a short 
time. 

o

  During the system test, make sure the pressure inside the compressor does not exceed the 

maximum PS value, which corresponds to the compressor low-pressure PS. 

  System low-pressure section: 

o

  Define the system low-

side PS ≤ compressor low-side PS. 

o

  The system test pressure of 1.1 x system low-side PS can be applied for a short time. 

5.2  Compressor tightness test 

 

WARNING 
High  pressure!  Personal  injuries!

  Consider  personal  safety  requirements 

and refer to test pressures prior to test. 

 

 

IMPORTANT 
System contamination! Bearing malfunction!

 Use only dry inert gases (for 

example nitrogen) for leak testing. DO NOT USE other industrial gases. 

 

The compressor has been leak-pressure tested in the Emerson factory. 

Never add refrigerant to the test gas (as leak indicator). 

Summary of Contents for COPELAND ZO18AG

Page 1: ...Copeland Scroll Compressors for R744 Refrigeration Applications ZO18AG to ZO46AG ZOV18AG to ZOV38AG Application Guidelines ...

Page 2: ...es 8 2 6 5 Design features 9 2 7 Dimensions 10 3 Installation 11 3 1 Compressor and drive handling 11 3 1 1 Transport and storage 11 3 1 2 Positioning and securing 11 3 1 3 Installation location 11 3 2 Compressor mounting parts 12 3 3 Shut off valves and adaptors 12 3 4 Pressure safety controls 13 3 4 1 Pressure relief valves 13 3 4 2 High pressure protection 13 3 4 3 Low pressure protection 13 3 ...

Page 3: ...rocedure 22 5 6 Run in time 23 5 7 Initial start up 23 5 8 Rotation direction 23 5 9 Start and stop routine 23 5 10 Starting sound 23 5 11 Deep vacuum operation 24 5 12 Shell temperature 24 5 13 Pumpdown cycle 24 5 14 Minimum run time 24 5 15 Shut off sound 24 5 16 Oil level 24 6 Maintenance repair 25 6 1 Qualification of workers 25 6 2 Disassembling system components 25 6 3 Provisions of legislat...

Page 4: ...AGL_Ref_ST_ZO_E_Rev00 Appendix1 Tightening torques 32 DISCLAIMER 32 ...

Page 5: ......

Page 6: ...o the corresponding provisions of legislation The Material Safety Datasheet MSDS for R744 shall be considered when working with this type of refrigerant please check this document provided by the gas supplier These instructions should be retained throughout the lifetime of the compressor You are strongly advised to follow these safety instructions 1 1 Icon explanation WARNING This icon indicates i...

Page 7: ...e current Danger of electric shock This product can cause both AC and DC earth leakage current To protect against both kinds of leakage current it is recommended to use an AC DC sensitive RCD on the power supply side WARNING High voltage Danger of electric shock and or system breakdown Disconnect and lock out power before servicing Allow drive components to electrically discharge before servicing ...

Page 8: ...liquid sub cooling 0 K Table 1 ZO V AG compressor capacity for LT applications 2 2 Matched pairs of compressor and drive The ZOV AG compressors with motor code X are offered as matched pairs with the EVM EVH drive designed in accordance with EN 60335 1 The matched pairs have been designed for maximum efficiency and reliability The drive will power the compressor control the compressor running spee...

Page 9: ...AG 4X9 EVM 344016 E20EFN 4 06 8 65 13 20 17 45 ZOV25AG 4X9 EVH 344016 R21BEN 4 06 8 65 13 20 17 45 ZOV25AG 4X9 EVH 344012 R21BEN 4 06 8 65 13 20 17 45 ZOV38AG 4X9 EVM 344016 E20EFN 6 27 13 15 20 10 27 00 ZOV38AG 4X9 EVM 344023 E20EFN 6 27 13 15 20 10 27 00 ZOV38AG 4X9 EVH 344023 R21BEN 6 27 13 15 20 10 27 00 ZOV38AG 4X9 EVH 344016 R21BEN 6 27 13 15 20 10 27 00 Evaporating temperature 35 C condensi...

Page 10: ...essor layouts and details ZO V AG compressors are available in the following BOM version BOM Suction and discharge connections T Box Mounting parts Sight glass Schraeder valve 592 Rotalock IP54 IP2X Without Yes Yes Table 4 BOM designation Please refer to the Emerson price list for more details 2 6 Application considerations 2 6 1 Qualified refrigerant and oil Qualified refrigerant R744 CO2 Copelan...

Page 11: ...count 2 6 2 Application limits CAUTION Inadequate lubrication Compressor breakdown The superheat at the compressor suction inlet must always be sufficient to ensure that no refrigerant droplets enter the compressor For a typical evaporator expansion valve configuration a minimum stable superheat of at least 20 K is required ZOV AG compressors operating envelopes depend on the running speed The env...

Page 12: ...the envelope should be respected The qualified application envelopes will change with the compressor speed At all operating conditions the minimum and maximum speed limits according to Figure 5 have to be respected With changing operating conditions the speed limits have to be determined by linear interpolation between the limits given in Figure 5 also see speed limits animation in Select software...

Page 13: ...olume LP side Internal free volume HP side PED Class ZO AG 60 bar g 45 bar g 50 C 2 8 l 0 34 l 1 ZOV AG 60 bar g 45 bar g 50 C 3 3 l 0 34 l 1 Table 6 Maximum allowable pressures PS TS internal free volume and PED category 2 6 4 Admissible temperature and relative humidity ranges ZO V AG compressors must comply with the ambient temperature and humidity ranges specified in Table 7 below both for sto...

Page 14: ...y of oil to the bearing system throughout the operating speed range of 1500 to 6000 rpm The motor in the variable speed scroll is a three phase brushless permanent magnet BPM design coupled with a rotor embedded with high energy magnets The input voltage is a series of DC pulses spaced in time to create an alternating current frequency ZO V AG compressors use a shutdown valve located in the discha...

Page 15: ...essor A B C D E F ZO18AG to ZO46AG 415 8 mm 390 2 mm 209 9 mm 67 4 mm 83 2 mm 285 8 mm Table 8 Dimensions of the ZO AG Figure 10 External dimensions of the ZOV AG Compressor A B C D E F ZOV18AG to ZOV38AG 385 8 mm 360 1 mm 179 9 mm 67 4 mm 83 2 mm 255 8 mm Table 9 Dimensions of the ZOV AG ...

Page 16: ...p NOTE The compressor is pre charged with dry air to avoid any moisture contamination 3 1 2 Positioning and securing IMPORTANT Handling damage Compressor malfunction Only use the lifting eyes whenever the compressor requires positioning Using discharge or suction connections for lifting may cause damage or leaks The compressor should be kept vertical during handling The discharge connection plug s...

Page 17: ... system System breakdown It is recommended to periodically re torque all pipe and fixing connections to the original settings after the system has been put into operation Torque settings of system valves and adaptors with Rotalock connections might decrease significantly after some time in operation Recurring temperature changes vibration and other influencing parameters can lead to expansion and ...

Page 18: ... open the drive will not operate NOTE For detailed specifications and instructions to connect the high pressure limiter to the drive please refer to the EVM EVH User Manual 3 4 3 Low pressure protection CAUTION Operation outside the application envelope Compressor breakdown A low pressure protection shall be fitted in the suction line to stop the compressor when it operates outside the envelope li...

Page 19: ... Fig 15 16 Avoid having the assembly heater inclined Fig 17 Close the lock and tighten the screw torque 2 3 Nm The excess clamp bracket may be trimmed Sharp edges must not come into contact with wires The presence of the heater shall be made evident by the posting of caution signs or markings at appropriate locations Figure 14 Figure 15 Figure 16 Figure 17 Electrical connection Connect the crankca...

Page 20: ... the compressor The stability of the refrigerant can also be affected particularly if traces of contaminant are present The problems listed under the first 2 points frequently occur simultaneously particularly since the chemical reaction speed approximately doubles with every 10 C temperature rise This directly leads to chemical reactions of the oil with the refrigerant and the compounds extracted...

Page 21: ...aximum 45 cm from the compressor for the most effective operation The further the muffler is placed from the compressor within these ranges the more effective Choose a muffler with a length of 10 to 15 cm 3 9 Sound and vibrations Vibrations during compressor operation can cause cracks which could lead to refrigerant leakage This situation must be avoided by the system manufacturer installer To thi...

Page 22: ... the oil reservoir to the compressor This value will give satisfactory results while 1 4 bar can be regarded as a minimum required value Figure 20 TraxOil OM4 and OM5 3 11 Suction line accumulator Due to Copeland scroll s inherent ability to handle liquid refrigerant for example in flooded start and defrost cycle operation an accumulator is not required in most systems To determine if a suction li...

Page 23: ...e correctly connected and that the supply voltage phases and frequency match the drive nameplate data Wiring should remain physically separated to minimize the introduction of electrical noise Before connecting the compressor ensure the supply voltage the phases and the frequency match the nameplate data For safety reasons Emerson recommends that the electrical installation be executed in complian...

Page 24: ...city failure or loss of terminal performance Precautions are required to prevent striking or bending of pins Bent or damaged pins may result in loss of hermeticity and or terminal performance Ensure correct connection of cables to the compressor terminal Fusite to avoid local overheating of Fusite pins which might lead to refrigerant leaks Cable glands have an influence on the protection class of ...

Page 25: ...f fuses has to be made according to EN 60269 1 or EN 60204 1 and drive maximum operating current MOC Not installing fuses before the compressor or selecting inappropriate fuses may result in compressor failure A conventional inherent internal line break motor protection Klixon is provided 4 8 Off cycle power consumption The drive will consume approximately 10 Watts from the drive power input line ...

Page 26: ...that case the two pressure zones of the scroll compressor need to be respected System high pressure section o Define the system high side PS compressor high side PS o Isolate the high and low pressure sections of the system by closing valves solenoid valves expansion valves or by other means o Use the internal check valve of the compressor on the discharge side or add an external check valve To pr...

Page 27: ...ut always check the following visual check of the electrics wiring fuses etc visual check of the plant for leaks loose fittings such as TXV bulbs etc compressor oil level calibration of HP LP switches and any pressure actuated valves check setting and operation of all safety features and protection devices all valves in the correct running position pressure and compound gauges fitted correctly cha...

Page 28: ...ion when the system is installed and operated Observing that suction pressure drops and discharge pressure rises when the compressor is energized allows verification of proper rotation direction There is no negative impact on durability caused by operating three phase Copeland scroll compressors in the reversed direction for a short period of time under one hour but oil may be lost Oil loss can be...

Page 29: ...eresis of the low pressure control differential has to be reviewed since a relatively large volume of gas will re expand from the high side of the compressor into the low side after shutdown For pressure control setting never set the low pressure limiter to shut off outside of the operating envelope To prevent the compressor from running into problems during such faults as loss of charge or partia...

Page 30: ...pressed air or oxygen shall not be used for purging refrigerant systems 3 Disassemble components 4 Drain recover and dispose of compressor oil as appropriate 6 3 Provisions of legislation leak check requirements According to EN 378 4 systems with a refrigerant charge of 3 kg or more shall be subject to tightness inspection at least on an annual basis The owner operator shall keep an updated logboo...

Page 31: ...al loading of the scrolls A minimum suction pressure specified in the published operating envelope must be maintained during charging Allowing the suction pressure to drop below that value may overheat the scrolls and cause early drive bearing and moving parts damage Never install a system in the field and leave it unattended when it has no charge a holding charge or with the service valves closed...

Page 32: ...gh hygroscopicity of the PAG oil To determine the actual moisture content of the lubricant samples have to be taken from the system and analysed 6 7 Oil additives Although Emerson cannot comment on any specific product from our own testing and past experience we do not recommend the use of any additives to reduce compressor bearing losses or for any other purpose Furthermore the long term chemical...

Page 33: ...ture sensor and high pressure switch Drive cooling For air cooled drives make sure that the airflow is not obstructed EMI filter Check all the wiring and check for loose or burned contacts on the board Compressor Make sure the compressor is running within the envelope Check the winding resistances from the compressor motor and the cables between compressor and drive Check for loose or burned conta...

Page 34: ...ly sized undersized discharge line can increase discharge pressure This is also true for an undersized condenser Correct the component selection as needed Check the fan motor make sure it is running properly in the right direction Check the condenser if dirt has been accumulated it will clog the airflow clean as necessary High discharge pressure is also caused by an overcharged system and high amb...

Page 35: ...ly sized Oil pump out due to high cycling rate A high cycling rate will pump oil into the system and lead to lubrication failure Oil leaves the compressor at start up and the short running time is insufficient to return the oil to the compressor via the suction side Try to limit the number of cycles to maximum 10 per hour Low gas velocity System gas velocity changes depending on temperature and lo...

Page 36: ... legislation and regulations 9 References Please visit www climate emerson com en gb for free download of Application Guidelines and Technical Information Performance and technical data The latest version of Copeland Select software with performance data and technical data is available from the webpage www climate emerson com en gb Spare parts and accessories An online version of the Emerson spare...

Page 37: ... this publication are presented for informational purposes only and are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability 2 Emerson Climate Technologies GmbH and or its affiliates collectively Emerson as applicable reserve the right to modify the design or specifications of such products at any time ...

Page 38: ...n com POLAND Szturmowa 2 PL 02678 Warsaw Tel 48 22 458 92 05 Fax 48 22 458 92 55 poland sales emerson com MIDDLE EAST AFRICA PO Box 26382 Jebel Ali Free Zone South Dubai UAE Tel 971 4 811 81 00 Fax 971 4 886 54 65 mea sales emerson com ASIA PACIFIC Suite 2503 8 25 F Exchange Tower 33 Wang Chiu Road Kowloon Bay Kowloon Hong Kong Tel 852 2866 3108 Fax 852 2520 6227 CZECH REPUBLIC Hajkova 22 CZ 133 0...

Reviews: