background image

8

© 2015 Emerson Climate Technologies, Inc.

AE4-1387 R7

through the compressor. This may leave the low side 

shell and suction line tubing pressurized. If a brazing 

torch is then applied to the low side, the pressurized 

refrigerant oil mixture could ignite as it escapes and 

contacts the brazing flame. It is important to check both 

the high and low sides with manifold gauges before 

unbrazing. In the case of an assembly line repair, 

remove the refrigerant from both the high and low sides. 

Instructions should be provided in appropriate product 

literatures and assembly areas.

High Potential (Hipot) Testing

Many of the Copeland brand compressors are 

configured with the motor below the compressor. As a 

result, when liquid refrigerant is within the compressor 

shell the motor can be immersed in liquid refrigerant to 

a greater extent than with compressors with the motor 

mounted above the compressor. When Copeland brand 

compressors are Hipot tested and liquid refrigerant is 

in the shell, they can show higher levels of leakage 

current than compressors with the motor on top because 

of the higher electrical conductivity of liquid refrigerant 

than refrigerant vapor and oil. This phenomenon 

can occur with any compressor when the motor is 

immersed in refrigerant. The level of current leakage 

does not present any safety issue. To lower the current 

leakage reading, the system should be operated for a 

brief period of time to redistribute the refrigerant to a 

more normal configuration and the system Hipot tested 

again. See bulletin 

AE4-1294

 for Megohm testing 

recommendations. Under no circumstances should 

the Hipot or Megohm test be performed while the 

compressor is under a vacuum.

SERVICE PROCEDURES 
Copeland Scroll

 

Functional Check

Refrigeration scroll compressors do not have internal 

suction valves. It is not necessary to perform functional 

compressor tests to check how low the compressor will 

pull suction pressure. This type of test may damage a 

scroll compressor. The following diagnostic procedure 

should be used to evaluate whether a Copeland Scroll 

compressor is functioning properly.

1.  Verify proper unit voltage.
2.  Normal motor winding continuity and short to 

ground checks will determine if the inherent 

overload motor protector has opened or if an 

internal short to ground has developed. If the 

protector has opened, the compressor must cool 

sufficiently to reset.

3.  With service gauges connected to suction 

and  discharge  pressure  fittings,  turn  on  the 

compressor. If suction pressure falls below 

normal levels, the system is either low on charge 

or there is a flow blockage.

4a. Single-Phase Compressors

If the suction pressure does not drop and the 

discharge pressure does not rise to normal levels 

the compressor is faulty.

4b. Three-Phase Compressors

If the suction pressure does not drop and the 

discharge pressure does not rise, reverse any two 

of the compressor power leads and reapply power 

to make sure the compressor was not wired to 

run in the reverse direction.

The compressor current draw must be compared to 

published compressor performance curves at the 

compressor operating conditions (pressures and 

voltages). Significant deviations (±15%) from

 

published 

values may indicate a faulty compressor. 

NOTICE

Note that the ZS09-19KAE-(TFD, TFE, TF7, TF5) three 

phase  motors  use  a  modified  "Scott-T"  connection 

and don't have equal resistance on all three windings. 

Two windings will have equal resistances and the third 

winding will be lower than the other two. See 

Figure 

A

. Carefully compare measured motor resistance 

values to the two different published resistance values 

for a given compressor model before replacing the 

compressor as being defective. Due to the nature of 

the Scott-T construction there is an inherent current 

imbalance in the motors that is much larger than what 

is seen in a standard 3-phase motor. Effectively you 

will have two terminals drawing similar currents while 

the third will draw a higher current. The current draw 

on the Scott –T motors as shown in the performance 

data and in the operating envelope (available online at 

www.emersonclimate.com under the Online Product 

Information link) comes from the 2 main windings. The 

larger ZS21-33KAE compressors have conventional 

three-phase motors with equal resistances in each 

winding. 

Summary of Contents for Copeland Scroll ZS KAE Series

Page 1: ...f Power Interruptions 7 Headmaster Refrigerant Selection Instructions 7 Rack Applications 7 Assembly Line Procedures Unbrazing System Components 7 High Potential Hipot Testing 7 Service Procedures Copeland Scroll Functional Check 8 New Installation 9 Field Service 9 Tables Figures Compressor Models and Approved Refrigerants Lubricants 10 Charge Limitations 10 Crankcase Heater 10 Conduit Ready Heat...

Page 2: ...ced on the user s safety Safey icons are explained below and safety instructions applicable to the products in this bulletin are grouped on Page 3 These instructions should be retained throughout the lifetime of the compessor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serio...

Page 3: ...t must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury or pr...

Page 4: ...ing inadequate lubrication and bearing wear Proper system design will minimize liquid flood back thereby ensuring maximum compressor life Superheat Requirements In order to assure that liquid refrigerant does not return to the compressor during the running cycle attention must be given to maintaining proper superheat at the compressor suction inlet Emerson recommends a minimum of 20 F 11 C superhe...

Page 5: ...cycling condition on the ZS09KAE through ZS33KAE models This phenomenon can be attributed to several factors 1 Location of low pressure control sensor If it is located right at the suction inlet of the compressor it will be more sensitive to pressure spikes 2 Actual low pressure setting Refer to our recommended setting in Table 5 If the differential pressure setting is too close this will increase...

Page 6: ...structions or notices should be provided by the Original Equipment Manufacturer Verification of proper rotation can be made by observing that the suction pressure drops and the discharge pressure rises when the compressor is energized Additionally if operated in reverse the compressor is noisier and its current draw is substantially reduced compared to tabulated values Although operation of scroll...

Page 7: ...Unbrazing System Components CAUTION If the refrigerant charge is removed from a scroll unit by bleeding the high side only it is sometimes possible for the scrolls to seal preventing pressure equalization 1105 for proper system evacuation procedures ZS KAE COMPRESSORS IN COPELAND CONDENSING UNITS The new FFAP Copeland condensing units will offer the latest technology utilizing the efficient ZS KAE...

Page 8: ...whether a Copeland Scroll compressor is functioning properly 1 Verify proper unit voltage 2 Normal motor winding continuity and short to ground checks will determine if the inherent overload motor protector has opened or if an internal short to ground has developed If the protector has opened the compressor must cool sufficiently to reset 3 With service gauges connected to suction and discharge pr...

Page 9: ...ned moving torch up and down and rotating around tube as necessary to heat tube evenly Add braze material to the joint while moving torch around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final resu...

Page 10: ...AE 4 5 R 22 R 404A R 507 R 134a R 407A R 407C R 448A R 449A POE Table 1 Compressor Models and Approved Refrigerants Lubricants See Emerson Climate Technologies Form 93 11 for a complete list of all Emerson approved lubricants Model Family Charge Limits ZS09 11 13 15 19KAE 8lbs ZS21 26 29 33KAE 10lbs Table 2 Charge Limitations Model Part No Volts Watts Length in ZS09 11 13 15 19KAE 018 0094 00 240 ...

Page 11: ...60 Hertz Rating 50 Hertz Rating Code Rating Min Max Rating Min Max C 208 230 3 187 253 200 3 180 220 D 460 3 414 506 380 420 3 342 462 E 575 3 518 633 500 3 450 550 V 208 230 1 197 253 200 1 180 220 V 208 230 1 187 253 200 1 180 220 5 200 230 3 180 253 200 220 3 180 242 7 380 3 342 418 X X X J 265 1 239 292 220 240 1 198 264 R X X X 220 240 3 180 264 Table 8 Voltage Ranges Typical The typical volt...

Page 12: ...orating Temp F Maximum Return Gas 65 F Maximum Return Gas 40 F Figure 1A ZS KAE Application Envelope for R 404A R 507 Extended Medium Temp 1 4 10 16 21 27 32 38 43 49 54 60 66 71 23 18 12 7 1 4 10 16 30 40 50 60 70 80 90 100 110 120 130 140 150 160 10 0 10 20 30 40 50 60 SH 20 F Condensing Temp C Evaporating Temp C Condensing Temp F Evaporating Temp F Figure 1B ZS KAE Application Envelope for R 22...

Page 13: ... 10 20 30 40 50 60 Minimum 20 F Superheat Required Condensing Temp C Evaporating Temp C Evaporating Temp F Condensing Temp F RG 65 F Figure 1D ZS KAE Application Envelope for R 407A 407C R 448A R 449A Extended Medium Temp 34 29 24 19 14 9 4 1 6 18 8 2 12 22 32 42 52 62 0 20 40 60 80 100 120 140 160 30 20 10 0 10 20 30 40 50 Evaporating Temp C Condensing Temp C Condensing Temp F Evaporating Temp F ...

Page 14: ...ndensing Unit Mounting 027 0262 00 30 35 Durometer Kit 527 0044 15 028 0188 15 Sleeve 028 0188 15 Sleeve 028 0188 15 Sleeve Gap Figure 2B ZS21KAE to ZS33KAE Refrigeration Scroll 63 Frame Condensing Unit Mounting 027 0186 00 35 45 Durometer Kit 527 0116 00 028 0188 15 Sleeve 028 0188 15 Sleeve 028 0188 16 Sleeve Gap ...

Page 15: ...4 Do not hang weights on tubing e g filter drier on suction tubing except after clamps or close to the header 5 Tube runs of less than 8 are not recommended 6 This dimension should be made as short as possible e g 2 or less but still insuring a proper braze joint 7 The above tubing recommendations are based on no elbow joints The use of continuous tubing is preferred Figure 4 Motor Terminal Fusite...

Page 16: ...ice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson product remains solely with the purchaser or end user Figure 5 Scroll Wiring Schematic Typical Solid State Timer Discharge Line Thermostat Compressor Contactor Coil Other Protective Devices if used System Operating Thermostat Fuse Opt...

Reviews: