11
© 2015 Emerson Climate Technologies, Inc.
AE4-1387 R7
Model
Type
Pressure
Control
R-404A/
R-507
R-134a
R-22
R-407A/
R-448A/R-449A
R-407C
ZS*KAE
Low
8 PSIG min.
4 PSIG min. 17 PSIG min.
6 PSIG min.
1in Hg min.
High
450 PSIG
max.
340 PSIG
max.
425 PSIG
max.
428 PSIG max.
425 PSIG
max.
Table 5 – Pressure Control Settings
Table 6 – Recommended Oil Charges by Model Family
Model Family
Initial Recharge
Frame Size
ZS09-19KAE
25
19
53
ZS21-33KAE
42
34
63
Refrigerant
Extended
Medium Temp
(-30 F to 25 F)
Medium Temp
(0 F to 25 F)
High Temp
(25 F to 45 F)
R-22
X
X
R-407C
X
X
R-404A
X
X
R-134a
X
X
R-407A
X
Table 7 – FFAP Condensing Unit Operating Envelopes
Voltage
60 Hertz Rating
50 Hertz Rating
Code
Rating
Min.
Max.
Rating
Min.
Max.
C
208/230-3
187
253
200-3
180
220
D
460-3
414
506
380/420-3
342
462
E
575-3
518
633
500-3
450
550
V
208/230-1
197
253
200-1
180
220
V*
208/230-1
187
253
200-1
180
220
5
200/230-3
180
253
200/220-3
180
242
7
380-3
342
418
X
X
X
J
265-1
239
292
220/240-1
198
264
R
X
X
X
220/240-3
180
264
Table 8 – Voltage Ranges (Typical)
The typical voltage range is (+/-) 10 % from rated voltage with the exemption of the 208/230 dual rated **V
models which are -5% +10% (197 min to 253 max voltage)from nominal as shown in the above table. The
following ZS**KAE models are now approved to operate within the full (+/-)10% range with a minimal voltage of
187 and a maximum voltage of 253 (ZS09,11,13,15,19, 21, 26KAE-PFV). The following models are not qualified