© 2017 Emerson Climate Technologies, Inc.
11
AE4-1372 R4
SPECIFICATIONS
OMC CO2
Maximum Working Pressure (MWP)
1885 PSIG (130 Bar)
Solenoid min/max OPD
1/1450 PSIG
Supply Voltage
120 V or 220-240V, 50/60 Hz
Solenoid Coil
EMF
Current Consumption
0.15 Amp (120V), 0.07 Amp (220-240V)
Time Delay for Low Level Signal
10 seconds
Time Delay After Setpoint Recovery
5 seconds
Alarm Delay Time (Including Alarm Contact)
120 seconds
Alar Switch
SPDT
Alarm Contact Rating
10A @ 120VAC 50/60Hz, 5A @ 250VAC 50/60 Hz, 3A@ 30 VDC
Refrigerant Temperature
-40° to 180°F (-40°C to 82.2°C) Maximum
Ambient Temperature - Storage
-40° to 120°F (-40°C to 48.9°C) Maximum
Ambient Temperature - Intermittent Duty
-40° to 120°F (-40°C to 48.9°C) Maximum
Oil Supply Fitting
1/4" Male SAE
(Brass)
Figure 1 CO2 Low Temp. Subcritical DX System