background image

12

13

High Pressure and Low Pressure Cut-out 
Settings

A high-pressure control with a maximum cut-out setting 
of 28 bar(g) is required. The high-pressure cut-out should 
have a manual reset feature for the highest level of system 
protection.

The low-pressure cut-out should be set as high as 
possible in all applications. For medium temperature 
applications the normal minimum is 2.5 bar(g) which 
corresponds to -10

o

C  with  R22  and  -16˚C  with  R404A. 

For low temperature applications the minimum cut-
out setting should not be lower than 0.3 bar(g) for  a  
compressor using R404A, and  should not be lower than 
0.1 bar(g) for a compressor using R22. The cut-out point 
of the LP switch must be set using an accurate suction 
pressure gauge rather than the scale on the switch which 
is provided for rough setting only.

Warning

Copeland Scroll Fusion compressor should NEVER be 
allowed to run in a vacuum.

The low-pressure cut-out should have a manual reset 
feature for the highest level of system protection.

Liquid Solenoid Valve

A liquid line solenoid valve is effective in keeping liquid 
out of the low side when the system cycles on the 
thermostat. The solenoid should be installed close to 
the expansion valve to keep the main volume of the 
liquid line on the high side of the system during off 
periods. All solenoid valves leak slightly and may not 
be 100% effective in keeping liquid in the high side 
during extended shutdown periods which can occur in 
cold rooms used for storing seasonal products. In most 
cases, opening and closing the solenoid valve when 
the compressor starts and stops provides adequate 
protection from liquid migration to the compressor 
crankcase.

Liquid Line Insulation

Copeland Scroll™ Fusion compressors have many 
characteristics found on two-stage piston compressors, 
among them, a cold liquid line after the heat exchanger. 
The cold liquid is very important for improving the system 

capacity  and  effi ciency,  and  any  increase  in  liquid  line 

temperature after the heat exchanger is a system loss. 

The liquid line should therefore be insulated with 
tightly-fitted closed cell foam.

 The wall thickness of 

the insulation should be at least 10 mm for medium 
temperature applications and >15 mm for low 
temperature applications.  In some low temperature 
applications, an uninsulated liquid line could even cause 
ice formation, and in humid environments condensation 
will occur. The line connecting the receiver to the inlet of 
the heat exchanger does not require insulation.

Pumpdown Cycle

Pumpdown cycles are widely applied in systems with 
reciprocating compressors. Copeland Scroll Fusion 
compressors have inherently superior liquid handling 
capability, so a pumpdown at each thermostat cycle is 
not recommended. A pumpdown cycle before defrost 
will be helpful in reducing the defrost time. Copeland 
Scroll Fusion

 compressors are fi tted with a spring loaded 

low-leak check valve under the discharge service valve, so 
an external check valve should not be necessary. When 

pumpdown fi nishes, the compressor will stop and contain 

a very large volume of high pressure gas in the top cap 
area. This refrigerant will quickly leak back to suction and 

will cause a signifi cant pressure rise that could reset the 

low pressure switch. The control circuit should not allow 
the compressor to restart; restart should only occur 
when the thermostat closes.

Figure 8.

 Schematic Diagram

High Pressure and Low Pressure switches must be fi tted

 

by 

the system manufacturer and connected to the pressure 
ports shown in the compressor outline drawing on 
Figure 6. HP and LP cut-out switches must be electrically 
connected as shown in the wiring diagram on Figure 10. 

Electrical Installation

The compressor is supplied with a wiring diagram 
inside the terminal box cover as shown in Figure 
10. Fuses and circuit breakers must be installed in 
accordance with local electrical regulations. The 
terminal box has an IP54 rating.  

Electrical Shock

Conductor Cables! Electrical Shock! Shut Off Power 
before High potential testing

The compressor and accessories are tested for leakage to 
ground before shipping. 

Disconnect the control board 

PWR and DEMAND connections to avoid any risk of 
damage during high potential testing.

Three-phase Motors

All compressors can be started direct on line only.

Control Board Connection

The control board, which is mounted in the terminal 
box, monitors the compressor sensors, protects the 
compressor, drives the electronic expansion valve and 
displays useful information in a seven segment display. 
Three red LEDs indicate the status of the CCC (compressor 
contractor coil), Alarm and a relay which is connected 
to the black terminal block. The board is powered via 
a transformer with a nominal output of 16 VAC. When 
correctly wired and powered up the board goes through 

a  self  checking  routine  and  displays  a  fl ashing  0.  If  the 

display is blank, check the power supply on the PWR, the 
transparent fuse, the transformer input and output, and the 
white fuse. The transparent fuse (250 V 2A) protects the 
transformer and other on-board electronic components. 
The white fuse (250 V 1A) protects the system control 
circuit and the on-board relays from external short circuits.

Wiring Diagram and Wiring Instruction

 

The position of the 4-Bit Dip Switch in the terminal box and 
the recommended wiring diagrams are shown in Figures 9 
and 10.

Warning

CoreSense™ Diagnostics

The CoreSense Diagnostics module in the terminal box 

monitors several sensors and protects the compressor 

from the following malfunctions:

• 

Reverse rotation by oil differential pressure switch

• 

Compressor not pumping by oil differential pressure 

switch

• 

High discharge temperature by discharge port 

temperature sensor

• 

High oil temperature by oil temperature sensor

• 

Low oil level by optical oil level sensor

• 

Motor overheat by embedded four thermistors

• 

High pressure – cut-out to be connected by system 
manufacturer or installer

• 

Low pressure – cut-out to be connected by system 
manufacturer or installer

Warning

Fusion Control Box Wiring Standard

According to Figure 11, there are 4 joints at the bottom 
of the control box. Each joint has dedicated wires to be 
assembled. Table 1 explains the function, requirement and 
connection method of each joint and wires inside. Wire C, 
D and G have been pre-wired in factory. C (Black) and D 
(Orange) are for compressor start/stop feedback input, 
connecting to “Demand” (Blue) connectors. G (Red) is wire 
of power input for Alarm Devices, connecting to “Alarm” 

Figure 9. 

CoreSense™ Diagnostics Board

TXV:

 Thermostatic Expansion Valve 

                     Fusion Standard BOM

VI:    

 Vapor Injection

EXV:

 Electronic Expansion Valve

Note:

 

Sight glass is provided and installed as standard ex-factory only in   

TWD models

(Orange) connector. The wire size for these three pre-
wirings is 18AWG.

Figure 12, on the other hand, shows the recommended 
wiring sequence for the control box.

CoreSense Diagnostics module is functioned to record 
latest 10 alarm histories. By pushing one button on the 
board, the user can check the alarm codes from latest 
to distant in sequence on LED display. The display starts 
from “H” and ends with “h”. When alarm code is blank, 
the display will show “0” instead.

Summary of Contents for Copeland Scroll QF115L

Page 1: ...Copeland Scroll TM Fusion Compressor For Refrigeration Applications User Manual User Manual ...

Page 2: ...Semi Hermetic Technology Emersonrealizedanincreasingneedforaversatile reliable quiet lightweight serviceablecompressorfortheColdRoom market and set out to develop a solution for this need In the development process the company brought together 70 years of semi hermetic compressor expertise and 25 years of leadership in scroll technology What came out of this endeavor is the newly designed Copeland...

Page 3: ...ical personnel Caution Make sure that the compressor is upright and there are no collisions or tilting during transit Use only refrigerants and oils approved by Emerson Make sure that the supply power voltage frequency and phase are exactly as per the specifications on the compressor nameplate The dry air inside the compressor should be evacuated before installation The compressor comes charged wi...

Page 4: ...26 4 30 4 36 9 MOC1 TWD 50 Hz A 24 25 27 32 33 25 LRA2 80 80 80 105 105 105 Motor Speed 50Hz rpm 2 900 Crankcase Heater Power W 60 Voltage V 220 Oil Charge Initial L 2 66 Recharge 2 54 Service Valves Suction in 1 1 8 Discharge 1 Dimensions Length mm 675 Width 355 Height 389 Base Mounting Length mm 350 Width 200 Bolt M10 Weight Net kg 130 Gross 140 Notes 1 MOC Maximum Operating Current 2 LRA Locked...

Page 5: ...d up with Mobile EAL Arctic 22 CC if 3MAF is not available Do not mix ester oils with mineral oil and or alkyl benzene when using chlorine free HFC refrigerants See nameplate for original oil charge in litres A field recharge is from 50 100 ml less than the original charge Oilmustbedrainedfromboththehighandlowsidesof the compressor whenever oil is changed One disadvantage of POE is that it is far ...

Page 6: ... 18NPTF 5 Nut oil out fitting M16 6 Connector DLT VIT VOT optical OLS DPS 7 Connector EXV oil temperature sensor 8 Screw grounding M5 9 Connector optional 10 Nut oil in fitting M16 11 Liquid out 3 4 12 Liquid in 3 4 13 DLT sensor 14 Vapor out temperature sensor 15 Nut EVI fitting M20 16 EXV Coil 17 Vapor in temperature sensor 18 Optical oil level sensor 7 8 14UNF 19 Built in oil screen M20 20 Oil ...

Page 7: ...nd connected to the pressure ports shown in the compressor outline drawing on Figure 6 HP and LP cut out switches must be electrically connected as shown in the wiring diagram on Figure 10 Electrical Installation The compressor is supplied with a wiring diagram inside the terminal box cover as shown in Figure 10 Fuses and circuit breakers must be installed in accordance with local electrical regul...

Page 8: ...ion Figure 11 CoreSense Wiring and Joints Step 1 Connect Compressor Motor Wires Step 3 Connect CCC Terminal Wires Step 4 Connect Alarm Terminal Wires Step 2 Connect PWR Terminal Wires Figure 12 CoreSense Recommended Wiring Sequence L H G F D B E C A J I 4 3 2 1 K ...

Page 9: ... The control module will stop the compressor display a fault code and close the alarm relay After a time delay the compressor will restart High discharge temperature alarms indicate a serious system problem and corrective action must be taken to avoid long term compressor damage and possible product loss Oil stored in compressor high side oil tank keeps same pressure and temperature as discharge g...

Page 10: ...um Refrigerant Charging PC Board should be powered to close EXV before charging The system should be liquid charged through the liquid receiver shut off valve or through a valve in the liquid line The use of a filter drier in the charging line is highly recommended Because scrolls have discharge check valves systems should be liquid charged on both the high and low sides simultaneously to ensure t...

Page 11: ...l not work so compressor must stop 1 FLASH Motor overheat Fault Compressor shutdown and automatic reset after 10 min delay 2 FLASH High discharge temperature Fault Compressor shutdown and automatic reset after 10 min delay 3 FLASH Low oil level Fault Compressor shutdown and automatic reset after 5 min delay 4 FLASH Low Oil Differential Pressure HP LP Fault Compressor shutdown and automatic reset a...

Page 12: ...5 50 mm 54 60 Rotalock Nut for Oil Out Tube 5 9 22 mm 25 30 Rotalock Nut for Oil In Tube 10 9 22 mm 25 30 Nuts of Tube Oil Pulsation 9 22 mm 25 30 EVI Rotalock Nut 15 11 24 mm 40 50 Pressure Differential Sensor Mechanical Part Lower Cover 1 12 1 100 110 Terminal Box Cover Screws 13 Cross Screwdriver H3 6 1 2 Screw CoreSense Connect to Terminal Box 14 H3 6 1 2 CoreSense Terminal Connectors 30 Volta...

Page 13: ...chnologies India Ltd Plot No 23 Rajiv Gandhi Infotech Park Phase II Hinjewadi Pune 411 057 Maharashtra India Tel 9120 2553 4988 Fax 9120 2553 6350 Indonesia PT Emerson Indonesia BSD Taman Tekno 8 Jl Tekno Widya Blok H10 No 2 3 Tangerang Selatan 15314 Indonesia Tel 6221 2666244 Fax 6221 2666245 Japan Emerson Japan Ltd Shin yokohama Tosho Building No 3 9 5 Shin Yokohama Kohoku ku Yokohama 222 0033 J...

Reviews: