background image

18

19

Maintenance

Refrigerant Exchange

Qualifi ed refrigerants and oils were indicated on page 8.

 It 

is not necessary to replace the refrigerant with a new one  
unless contamination due to an error such as topping up 
the system with an incorrect refrigerant is suspected. To 
verify correct refrigerant composition, a sample can be 
taken for chemical analysis. A check can be made during 
shut down by comparing the refrigerant temperature and 
pressure using precision measurements at a location in 
the system where liquid and vapor phases are present and 
when the temperatures have been stable.

In the event that the refrigerant needs replacing, the charge 
should be recovered using a suitable recovery machine.

When R22 in a system with mineral oil is to be replaced 
with R407C or R404A, the oil must also be changed. 
Please refer to Technical Information “Refrigerant 
changeover from HCFC to HFC Refrigerants”.

Replacing Compressor

Rotalock valves should be re-torqued periodically to 
ensure that leak tightness is maintained. All gaskets and 

fi ttings should be inspected for signs of leaks and repaired 

if necessary. Electrical connections should be checked for 
tightness. All wires should be clamped securely and routed 
away from hot surfaces to prevent damage from vibration 
and heat.

Some minor repairs like sensor replacement can be done while 
the compressor is still under pressure. To replace components 
that are under pressure, shut down the compressor, wait 15 
seconds, and turn off all power. Close the service valves, recover 
the refrigerant and change the faulty component. Evacuate the 
compressor only, open the service valves, and recharge the same 
quantity of refrigerant that was recovered.

Change the accumulator after replacing a compressor with 

a burned out motor. The accumulator oil return orifi ce or 

screen may be plugged with debris or may become plugged. 
This will result in starvation of oil to the new compressor and 
a second failure.

In the case of a motor burnout, the majority of contaminated 
oil will be removed with the compressor. The rest of the oil 

is  cleaned  through  the  use  of  suction  and  liquid  line  fi lter 

The maximum pressure for leak testing should be no 

higher than 22.5 bar(g).

Use only dry nitrogen or dry air for system pressure 

testing. DO NOT USE other industrial gases. 

If using dry air do not include the compressor in the 

pressure test – isolate it fi rst. Never add refrigerant to the 

test gas (as leak indicator).

System Evacuation and Dehydration

Before the installation is put into operation, remove the 

holding charge then evacuate with a vacuum pump. 

Proper evacuation reduces residual moisture to 50 ppm. 

The installation of adequately sized access valves at the 

furthest point from the compressor in the suction and 

liquid lines is advisable. To achieve undisturbed operation, 

the compressor valves are closed and the system is 

evacuated down to 0.3 mbar / 0.225 Torr. Pressure must 

be measured using a vacuum pressure (Torr) gauge on the 

access valves and not on the vacuum pump; this serves to 

avoid incorrect measurements resulting from the pressure 

gradient along the connecting lines to the pump. Then the 

compressor must be evacuated. Due to the factory holding 

charge of dry air, the compressor is under pressure (about 

1-2.5 bar), this is to indicate the compressor does not leak.

 

Preliminary Check

Discuss installation details with the installer. If possible, 

obtain drawings, wiring diagrams, etc. It is ideal to use a 

checklist but always check the following:

• 

Visual check of the electrics, wiring, fuses etc.

• 

Visua

l check of the plant for leaks, loose fi ttings such 

as TXV bulbs etc.

• 

Compressor oil level

• 

Calibration of HP and LP switches and any pressure 
actuated valves

• 

Check setting and operation of all safety features and 
protection devices

• 

All valves in the correct running position

• 

Pressure and compound gauges fi tted

• 

Correctly charged with refrigerant

• 

Compressor electrical isolator location & position

Never install a system in the fi eld and leave it unattended 

when it has no charge, a holding charge, or with the service 
valves closed without securely electrically locking out the 
system. This will prevent unauthorized personnel from 
accidentally operating the system and potentially ruining 

the compressor by operating with no refrigerant fl ow.

Do not start the compressor while the system is in 

a vacuum.

Refrigerant Charging

PC Board should be powered to close EXV before 
charging. The system should be liquid-charged through 
the liquid-receiver shut-off valve or through a valve in the 

liquid line. The use of a fi lter drier in the charging line is 

highly recommended. Because scrolls have discharge 
check valves, systems should be liquid-charged on both 
the high and low sides simultaneously to ensure that a 
positive refrigerant pressure is present in the compressor 
before it runs.

Charging quantity can be determined by referring to system 
discharge and suction pressures. Another very useful 
parameter is the liquid line temperature which has been 
listed in the Fusion Catalogue. At a measured condensing 
temperature and an evaporating temperature, the liquid line 
temperature should be around Emerson‘s recommendation 
value 5K tolerance.

The majority of the charge should be placed in the high side 

of the system to prevent bearing washout during fi rst-time 

start on the assembly line or on site.

Do not operate with a restricted suction. Do not operate 

with the low-pressure cut-out bridged. Do not operate 

compressor without enough system charge to maintain at 

least 0.3 bar suction pressure. Allowing pressure to drop 

below 0.3 bar for more than a few seconds may overheat 

scrolls and cause early drive bearing damage. If the suction 

pressure is low on startup, and top up of the refrigerant 

charge is required, it is preferable to bleed liquid slowly 

into the suction line of a running compressor than to risk 

overheating by vapour charging.

The system should be liquid-charged through the liquid-

receiver shut-off valve or through a valve in the liquid 

line. The use of a fi lter drier in the charging line is highly 

recommended. The majority of the charge should be 

placed in the high side of the system to prevent bearing 

washout during fi rst-time start on the assembly line.

Initial Startup 

It is important to ensure that new compressors are not 

subjected to liquid abuse. Turn the crankcase heater on 12 

hours before starting the compressor.

.

Warning

Warning

Warning

driers.  A  100%  activated  alumina  suction  line  fi lter  drier  is 

recommended but must be removed after 72 hours. It is highly 
recommended that the suction accumulator be replaced if the 
system contains one. This is because the accumulator oil-return 

orifi ce or screen may be plugged with debris or may become 

plugged shortly after a compressor failure. This will result in 
starvation of oil to the replacement compressor and a second 
failure. When a single compressor or tandem is exchanged in 

the fi eld, it is possible that a major portion of the oil may still 

be in the system. While this may not affect the reliability of the 
replacement compressor, the extra oil will add to rotor drag 
and increase power usage.

Lubrication and Oil Removal

Do not mix up ester oils with mineral oil and/or alkyl 
benzene when used with chlorine-free (HFC) refrigerants. 
The compressor is supplied with an initial oil charge. 
The standard oil charge for use with refrigerants R404A 
is a polyolester (POE) lubricant Emkarate RL 32 3MAF. 

In the fi eld, the oil level could be topped up with Mobil 

EAL Arctic 22 CC if 3MAF is not available. The standard 
mineral oil for R22 is Karamay 32BYMO. Therefore it is 

recommended that a properly sized fi lter drier is installed 

in all POE systems. This will maintain the moisture level in 
the oil to less than 50 ppm. 

If the moisture content of the oil in a refrigeration system 
reaches unacceptably high levels, corrosion and copper 
plating may occur. The system should be evacuated down to 
0.3 mbar or lower. If there is uncertainty as to the moisture 
content in the system, an oil sample should be taken 
and tested for moisture. Sight glass/moisture indicators 
currently available can be used with the HFC refrigerants 
and lubricants; however, the moisture indicator will just 
show the moisture content of the refrigerant. The actual 
moisture level of POE would be higher than what the sight 
glass indicates.

Oil Additives

Although Emerson Climate Technologies cannot 
comment on any specific product, from our own testing 
and past experience, we do not recommend the use of 
any additives to reduce compressor bearing losses or for 
any other purpose. Furthermore, the long term chemical 
stability of any additive in the presence of refrigerant, low 
and high temperatures, and materials commonly found in 
refrigeration systems is complex and difficult to evaluate 
without rigorously controlled chemical laboratory testing. 

Warning

Warning

Warning

Warning

Warning

Summary of Contents for Copeland Scroll QF115L

Page 1: ...Copeland Scroll TM Fusion Compressor For Refrigeration Applications User Manual User Manual ...

Page 2: ...Semi Hermetic Technology Emersonrealizedanincreasingneedforaversatile reliable quiet lightweight serviceablecompressorfortheColdRoom market and set out to develop a solution for this need In the development process the company brought together 70 years of semi hermetic compressor expertise and 25 years of leadership in scroll technology What came out of this endeavor is the newly designed Copeland...

Page 3: ...ical personnel Caution Make sure that the compressor is upright and there are no collisions or tilting during transit Use only refrigerants and oils approved by Emerson Make sure that the supply power voltage frequency and phase are exactly as per the specifications on the compressor nameplate The dry air inside the compressor should be evacuated before installation The compressor comes charged wi...

Page 4: ...26 4 30 4 36 9 MOC1 TWD 50 Hz A 24 25 27 32 33 25 LRA2 80 80 80 105 105 105 Motor Speed 50Hz rpm 2 900 Crankcase Heater Power W 60 Voltage V 220 Oil Charge Initial L 2 66 Recharge 2 54 Service Valves Suction in 1 1 8 Discharge 1 Dimensions Length mm 675 Width 355 Height 389 Base Mounting Length mm 350 Width 200 Bolt M10 Weight Net kg 130 Gross 140 Notes 1 MOC Maximum Operating Current 2 LRA Locked...

Page 5: ...d up with Mobile EAL Arctic 22 CC if 3MAF is not available Do not mix ester oils with mineral oil and or alkyl benzene when using chlorine free HFC refrigerants See nameplate for original oil charge in litres A field recharge is from 50 100 ml less than the original charge Oilmustbedrainedfromboththehighandlowsidesof the compressor whenever oil is changed One disadvantage of POE is that it is far ...

Page 6: ... 18NPTF 5 Nut oil out fitting M16 6 Connector DLT VIT VOT optical OLS DPS 7 Connector EXV oil temperature sensor 8 Screw grounding M5 9 Connector optional 10 Nut oil in fitting M16 11 Liquid out 3 4 12 Liquid in 3 4 13 DLT sensor 14 Vapor out temperature sensor 15 Nut EVI fitting M20 16 EXV Coil 17 Vapor in temperature sensor 18 Optical oil level sensor 7 8 14UNF 19 Built in oil screen M20 20 Oil ...

Page 7: ...nd connected to the pressure ports shown in the compressor outline drawing on Figure 6 HP and LP cut out switches must be electrically connected as shown in the wiring diagram on Figure 10 Electrical Installation The compressor is supplied with a wiring diagram inside the terminal box cover as shown in Figure 10 Fuses and circuit breakers must be installed in accordance with local electrical regul...

Page 8: ...ion Figure 11 CoreSense Wiring and Joints Step 1 Connect Compressor Motor Wires Step 3 Connect CCC Terminal Wires Step 4 Connect Alarm Terminal Wires Step 2 Connect PWR Terminal Wires Figure 12 CoreSense Recommended Wiring Sequence L H G F D B E C A J I 4 3 2 1 K ...

Page 9: ... The control module will stop the compressor display a fault code and close the alarm relay After a time delay the compressor will restart High discharge temperature alarms indicate a serious system problem and corrective action must be taken to avoid long term compressor damage and possible product loss Oil stored in compressor high side oil tank keeps same pressure and temperature as discharge g...

Page 10: ...um Refrigerant Charging PC Board should be powered to close EXV before charging The system should be liquid charged through the liquid receiver shut off valve or through a valve in the liquid line The use of a filter drier in the charging line is highly recommended Because scrolls have discharge check valves systems should be liquid charged on both the high and low sides simultaneously to ensure t...

Page 11: ...l not work so compressor must stop 1 FLASH Motor overheat Fault Compressor shutdown and automatic reset after 10 min delay 2 FLASH High discharge temperature Fault Compressor shutdown and automatic reset after 10 min delay 3 FLASH Low oil level Fault Compressor shutdown and automatic reset after 5 min delay 4 FLASH Low Oil Differential Pressure HP LP Fault Compressor shutdown and automatic reset a...

Page 12: ...5 50 mm 54 60 Rotalock Nut for Oil Out Tube 5 9 22 mm 25 30 Rotalock Nut for Oil In Tube 10 9 22 mm 25 30 Nuts of Tube Oil Pulsation 9 22 mm 25 30 EVI Rotalock Nut 15 11 24 mm 40 50 Pressure Differential Sensor Mechanical Part Lower Cover 1 12 1 100 110 Terminal Box Cover Screws 13 Cross Screwdriver H3 6 1 2 Screw CoreSense Connect to Terminal Box 14 H3 6 1 2 CoreSense Terminal Connectors 30 Volta...

Page 13: ...chnologies India Ltd Plot No 23 Rajiv Gandhi Infotech Park Phase II Hinjewadi Pune 411 057 Maharashtra India Tel 9120 2553 4988 Fax 9120 2553 6350 Indonesia PT Emerson Indonesia BSD Taman Tekno 8 Jl Tekno Widya Blok H10 No 2 3 Tangerang Selatan 15314 Indonesia Tel 6221 2666244 Fax 6221 2666245 Japan Emerson Japan Ltd Shin yokohama Tosho Building No 3 9 5 Shin Yokohama Kohoku ku Yokohama 222 0033 J...

Reviews: