C6.1.10/0118-0318/E
36
Appendix 3: Parameter list level 1 (Pr1)
Legend
L1 = Parameter in Level 1 (without password)
L2 = Parameter in Level 2 (with password = 3 2 1)
N.V. = Parameter not accessible
NOTE: When changing parameter C05 (LS) a reset of the controller (interruption of power supply) is required.
Parameters
Description
Range
ZXDI
ZXDE
ZXDI
C07
rEF
Refrigerant selection for regulation
R404A (0-404) - R507 (1-507) -
R134a (2-134) - R22 (3-R22) -
R407C (4-07C) - R407A (5-07A) -
R407F (6-07F)
– R448A (7-48A) -
R449A (8-49A) - R410A (9-410)
L1
C16
StC
Digital compressor setpoint
LS to US; C03 to C04
L1
C17
Pbd
Proportional band for compressor regulation
0.1 to 9.9 bar; 0.1 to 99.9 PSI;
1 to 999 KPA; 0.1°C to 25.5°C
L1
C21
tdG
Cycle time for digital compressor
10 to 40 sec
L1
C24
PMi
Minimum capacity for digital compressor
0 to PMA; 0 to C25
L1
C25
PMA
Maximum capacity for digital compressor
PMi to 100; C24 to 100
L1
D29
LPA
Low-pressure alarm value
0 to 15 bar
L1
E39
FSP
Condenser temperature setpoint when fan
setpoint modulation is disabled
-40°C to 110°C
L1
E46
Fbd
Regulation band of variable fan
0.1°C to 25.5°C
L1
N01
Min
Current minute
0 to 59
L1
N02
Hr
Current hour
0 to 23
L1
N03
MdY
Date of month
1 to 31
L1
N04
Mon
Month
1 to 12
L1
N05
YEr
Year
0 to 99
L1
T18
PAS
Access to Pr2 level
[0÷999]
L1
Table 25: Parameters level 1