TI_Unit_CO2_Stream_04_EN_Rev00 

Ident number 3293976 (P/N 900-0010-00/Rev00) 

3/3

 

  Mount the deflector and tighten it manually to 1-5 Nm 

(Figures 11 & 12)

  The changeover valve must be fully open during unit operation (spindle out 

Figures 13 & 15

). 

  Mount the spindle cap and check the presence of the copper gasket 

(Figure 14)

  

  

  

 

Figure 11            Figure 12 

 

 

      Figure 13 

 

              Figure 14 

 

 

Figure 15 

Spindle protective cap 

Spindle "open" / "closed" 

Seal gland 

40 Nm 

25 Nm 

15 Nm 

Table 2

: Torques on the changeover valve in Nm 

NOTE:  For  information  on  the  maintenance  and  lifetime  of  the  PRV,  please  refer  to  the  unit  application 
guidelines. 