0-20
: Current input 0 to 20mA (20mA full scale)
20-0
: Current input 20 to 0mA (0mA full scale)
4-20
: Current input 4 to 20mA with current loop loss (cL1) trip (20mA full scale)
20-4
: Current input 20 to 4mA with current loop loss (cL1) trip (4mA full scale)
4-.20
:Current input 4 to 20mA with no current loop loss (cL1) trip (20mA full scale)
20-.4
:Current input 20 to 4mA with no current loop loss (cL1) trip (4mA full scale)
VoLt
: 0 to 10V input
T1
0V common
T2
Analog input 1 (A1), either voltage or current (see Pr 16)
Voltage: Current input
0 to 10V / mA as parameter range
Parameter range
4-20, 20-4, 0-20, 20-0, 4-.20, 20-.4, VoLt
Scaling
Input range automatically scaled to Pr
01
Minimum set
speed
/ Pr
02
Maximum set speed
Input impedance
200
Ω
(current) / 100k
Ω
(voltage)
Resolution
0.1%
T3
+10V reference output
Maximum output current
5mA
T4
Analog input 2 (A2), either voltage or digital input
Voltage: Digital input
0 to +10V / 0 to +24V
Scaling (as voltage input)
Input range automatically scaled to Pr
01
Minimum set
speed
/ Pr
02
Maximum set speed
Resolution
0.1%
Input impedance
100k
Ω
(voltage) / 6k8 (digital input)
Normal threshold voltage (as digital input) +10V (positive logic only)
T5
Status relay - Drive ok (Normally open)
T6
Contact voltage rating
240Vac
30Vdc
Contact maximum current rating
2Aac 240V
4Adc 30V resistive load (2A 35Vdc for UL
requirements).
0.3Adc 30V inductive load (L/R=40ms)
Contact minimum recommended rating
12V 100mA
Contact isolation
1.5kVac (over voltage category II)
Operation of contact (drive ok - default
condition)
OPEN
AC supply removed from drive
AC supply applied to drive with drive in tripped condition
CLOSED
AC supply applied to drive with drive in a 'ready to run' or
'running' condition (not tripped)
Provide fuse or other over-current protection in status relay circuit.