Rating data
Figure 2-1 Model code explanation
Table 2-1 Commander SK, 1 phase, 100 to 120Vac ±10%, 48 to 62Hz units
*No dynamic braking available with Commander SK size A 110V drive.
Table 2-2 Commander SK, 1 phase, 200 to 240Vac ±10%, 48 to 62Hz units
Table 2-3 Commander SK, 1 and 3 phase, 200 to 240Vac ±10%, 48 to 62Hz units
SK A 1 2 XXXXX
Drive kilowatt rating: 00025 = 0.25kW
Drive voltage rating: 1 = 110V, 2 = 230V, 4 = 400V
Number of input phases: 1 = 1phase, 3 = 3phase, D = 1 and 3phase
Frame size
Model: Commander SK
Model
Number
Nominal motor
power
Input fuse
rating
Typical full
load input
current
100% RMS
output current
A
150% overload
current for 60s
A
Minimum
braking
resistor value
kW
hp
A
A
Heavy Duty
Ω
SKA1100025
0.25
0.33
10
7.5
1.7
2.55
N/A*
SKA1100037
0.37
0.5
15
11
2.2
3.3
SKB1100075
0.75
1.0
25
19.6
4.0
6.0
28
SKB1100110
1.1
1.5
32
24.0
5.2
7.8
Model
Number
Nominal motor
power
Input fuse
rating
Typical full
load input
current
100% RMS
output current
A
150% overload
current for 60s
A
Minimum
braking
resistor value
kW
hp
A
A
Heavy Duty
Ω
SKA1200025
0.25
0.33
6
4.3
1.7
2.55
68
SKA1200037
0.37
0.5
10
5.8
2.2
3.3
SKA1200055
0.55
0.75
10
8.1
3.0
4.5
SKA1200075
0.75
1.0
16
10.5
4.0
6.0
Model
Number
Nominal
motor power
Input fuse
rating
A
Typical full
load input
current
A
Maximum
continuous
input current
A
100% RMS
output
current
A
150% overload
current for 60s
A
Minimum
braking
resistor
value
Ω
kW
hp
1ph 3ph
1ph
3ph
1ph
3ph
Heavy Duty
SKBD200110
1.1
1.5
16
10
14.2
6.7
9.2
5.2
7.8
28
SKBD200150
1.5
2.0
20
16
17.4
8.7
12.6
7.0
10.5
28
SKCD200220
2.2
3.0
25
20
23.2
11.9
17.0
9.6
14.4
28
SKDD200300
3.0
3.0
25
16
23.6
12.5
16.6
12.6
18.9
20
SKD3200400
4.0
5.0
20
15.7
19.5
17.0
25.5
20
Summary of Contents for Commander SK