Visit our website at Emerson.com/AVENTICS
10 V
20 mA
5 V
10 mA
3. Analog Setpoint - Outlet Pressure
CAUTION:
Outlet pressures above the maximum outlet pressure (PMR) are not controlled by the valve, i.e. the max.
outlet pressure is limited to the PMR.
In order to avoid damaging the sensor,
the supply pressure must always be less than the maximum inlet pressure
defined above
(see table).
The span can be set to max. 100% of the maximum outlet pressure (PMR). It can only be decreased.
Setpoint offset
The pressure setpoint zero can be changed via the DaS program. Switch to "Custom" in the "Setpoint setting" section.
The zero range is max. ±50 %.
Setpoint span
The span of the output pressure can be changed via the DaS program. Switch to "Custom" in the "Setpoint setting"
section. The span is between 10 and 100%.
Offset adjustment
Fac
tor
y s
etting
SHUT-OFF
Max. outlet
pressure
PMR
+50 % PMR
20mA
4
12 mA
0
50 mV
0.1 mA
4.08 mA
0
-50 % PMR
10 V
20 mA
0
Span adjustment
Max. outlet
pressure (PMR)
Max. outlet
pressure 0.5 PMR
Fac
tor
y s
etting
: 100 %
50 % s
etting
SHUT-OFF
20mA
4
0
50 mV
0.1 mA
4.08 mA
0
Max. Outlet Pressure PMR
Max. Inlet Pressure
50 psi
90 psi
100 psi
140 psi
150 psi
190 psi
1 bar
4 bar
3 bar
6 bar
6 bar
9 bar
10 bar
13 bar
12 bar
15 bar
15 bar
18 bar
Sentronic
D
INSTALLATION
MANUAL