background image

MS-P522

-GB-R2

GENERAL

• ASinterface connections are  suitable for direct control of solenoid valves and spool valves with DIN 46244 (three 6.3 x 0.8 mm spade

terminals) or ISO 4400, plug coils with maximum power ratings of 

7,2 W

 at 24 V DC (-15 or 

-10%

, +10%).

• Solenoid valves and spool valves can be directly integrated into the ASinterface bus.
• Electrical connection by vampire connections designed for standard flat yellow and black ASinterface cables.
• Compact design (comparable to a standard connector).
• Available with or without an additional M12 connector for one or two input/return of information sensors.

COMMUNICATION AND SPECIFICATION

Protocol

ASinterface

Transmission medium

: flat black cable: 24V DC power via 2 conductors. On connecting to the power supply

unit, 

observe polarity

, blue : - , brown : +

: flat yellow cable : data via 2 conductors

Bus topology

: backbone or tree

Maximum number of connectors

: 31 slaves

Number of outputs per connector

: 1 solenoid valve or spool valve per connector

Maximum length of bus cable

: 100 m (300 m with repeater)

I/O refresh time

: 5 ms max.

Connector addressing (subscribers)

: by ASinterface master via configuration software, or by pocket unit

Compatible PLCs

: SIEMENS, SCHNEIDER, IFM

ASinterface gateways: Profibus - DP, Interbus-S, DeviceNet, Worldfip/FIPIO

ELECTRICAL SPECIFICATION

ASinterface data voltage

: 31,5 V

Power voltage (black cable)

: 24 V DC  (

-5%

, +10%)

Maximum ripple

: 10%

Max. connector power

7,2 W (0.3A)

Yellow cable connector consumption

: <150 mA

24 V power connection

: vampire connection for ASinterface cable (black cable)

I/O network connection

: vampire connection for ASinterface cable (yellow cable)

Connection of inputs

: M12 5 pin female connectors, 

power supply of inputs through black cable

Trigger level of one input

: 0,36 mA

Signaling

: 2 LEDs :  1 for ASinterface and 1 for coil

Ambient temperature

: -10°C to 

+60°C

Protection

: IP65, provided connectors and covers are correctly in place (see accessories)

CHOICE OF EQUIPMENT

CONNECTORS

FOR ASinterface CONNECTIONS

at spool valves and solenoid valves

3 x DIN 46244 or ISO 4400 spade terminals

Series

881

NTERFACE

N˚ 21301

Connector type

CODES

ASinterface connector

ASinterface connector

with DIN 46244 plug

(DIN 43650 industrial standard)

ASinterface connector

with ISO 4400 plug

(DIN 43650 Form A)

no input

with M12 input

(Version A)

with M12 input

(Version B)

881 00 277

881 00 337

881 00 408

881 00 278

881 00 339

881 00 409

ACCESSORIES

M12 five male pins connectors for inputs (sensor return):
- with Pg7 90° 

elbow mono 

input cable for one 4 to 6 mm diameter cable, code: 

881 61 927

- with Pg7 

straight mono

 cable input for one 4 to 6 mm diameter cable,

code: 

881 00 330

- with straight 

duo

 cable input for two 3 to 5 mm diameter cables,

code: 

881 00 253

Thermoretractable ends (set of 10 pieces),

code: 

881 57 927

for IP65 protection at the end of the connection lines

Ce

rt

if

-

C

ertified

-

Z

e

rt

ifik

at

-

N˚21301

NTERFACE

These connectors are 

non

 rotatable.

(Version A)

(Version B)

Adaptation

on

coil

on

solenoid valves

CM22

189

CM5

ASCO

CM25-CM30(5W)

190-192

CM6/FT - JMX

ASCO

CMXX/F (1,7W)

*

(

*

) Connector used with low power coil, consumption 1,7 W

NOTE: These connectors are not compatible with POSIFLOW solenoid valves

Summary of Contents for ASCO 881 Series

Page 1: ...Puissance maxi sur connecteur 7 2 W 0 3A Consommation du connecteur sur câble jaune 150 mA Raccordement de l alimentation 24 V prises vampires pour câble ASinterface câble noir Raccordement du réseau IN OUT prises vampires pour câble ASinterface câble jaune Raccordement des entrées par socle M12 à 5 broches femelles alimentation des entrées par câble noir Seuil de commutation d une entrée 0 36 mA ...

Page 2: ...00 mA Intensité de charge par entrée 2 4 mA Seuil de commutation d une entrée 0 36 mA Niveau logique pour les entrées Haut 10 30V CC Bas 30 2 5V CC MS P522 Schéma de raccordement des entrées Repérage vu coté vissage du connecteur mâle capteurs à 2 fils capteurs à 3 fils ex magnéto résistif 1 2 4 3 5 IN x Captr x GND IN x IN x 1 24V 24V IN x 1 Captr x 1 GND 24V 24V Captr x Captr x 1 Adressage des s...

Page 3: ...pères gravés sur la partie supérieure câble noir 1 sous l inscription POWER câble jaune 2 sous l inscription ASinterface Remonter le couvercle sur le connecteur fig 4 en respectant le sens de montage largeur différente des pattes latérales Exercer une pression suffisante pour assurer la connexion sur les 4 prises vampires et clipser à fond le couvercle Serrer la vis tout en maintenant une pression...

Page 4: ... vampire connection for ASinterface cable black cable I O network connection vampire connection for ASinterface cable yellow cable Connection of inputs M12 5 pin female connectors power supply of inputs through black cable Trigger level of one input 0 36 mA Signaling 2 LEDs 1 for ASinterface and 1 for coil Ambient temperature 10 C to 60 C Protection IP65 provided connectors and covers are correctl...

Page 5: ...network is configured with an ASinterface coupler integratedinthePLC thefollowingASCO JOUCOMATICASinterface connector identificationcodesapply I O code ID code ASCO JOUCOMATIC connector identification code 11 or BH 15 ASinterface connectors are non rotatable MS P522 1 5 female pins M12 base for input 2 Yellow cable ASinterface 3 Black cable power supply Connector D0 D1 D2 D3 No input Output coil N...

Page 6: ...nnectors with M12 inputs are available in two versions A and B with M12 orientation through 180 to fit any product configuration It is recommended to connect the wiring before mounting on the coil CONNECTION Before connection determine the mounting direction of the connector on the product coil on the basis of the position of the earth connection The connector is supplied with the cover pre mounte...

Reviews: