background image

3

NBR

04-4744 - 112

04-4744 - 113

04-4744 - 114

04-4744 - 115

11115086

FKM

04-4744 - 116

04-4744 - 117

04-4744 - 118

04-4744 - 119

11115086

EPR

04-4744 - 906

04-4744 - 907

04-4744 - 908

04-4744 - 905

11115086

ANDERSON GREENWOOD

 SERIES 96A VACUUM BREAKER

INSTALLATION AND MAINTENANCE INSTRUCTIONS

2.2.5  Install new O-ring seat into seat ring 

following the sequence depicted in Figure 2.

2.2.6  Assemble seat plate bolt to guide tube. 

Place tube in “Vee” block, align holes and 
insert spring pin.

2.2.7  Assemble guide tube to seat plate in the 

reverse order from that described in 2.1.1. 
Torque locknut for snug fit. Make sure the 
retainer and O-ring are in place for a seal 
around bolt shank.

3 LEAK AND VACUUM SET VERIFICATION 
TESTING

3.1  Pressurize vacuum breaker to 150% of 

the positive working pressure.

3.2  Apply leak test solution around all bolts 

and sealing surfaces.

3.3  Reduce positive pressure to 10% of the 

positive working pressure and check for 
seat leaks using leak test solution. If seat 
leakage occurs the probable cause is 
the sponge seat not being cemented flat to 
the seat ring. If leakage is unacceptable, 
sponge seat must be replaced.

3.4  Reduce pressure to vacuum region and note 

negative pressure at which seat plate begins 
to lift. It should crack open, sufficiently to 
rattle slightly, at ½ oz (0.22 kpag).

4 SOFT GOODS REPAIR KIT

The kits listed below are available from stock. 
To order, specify the number indicated in 
the following table. To insure the purchase of 
correct soft goods kits, the order should specify 
the valve model number and serial number.

2.2.4  For non-lox clean valves, cement new 

sponge seat to seat ring using Resiweld 
Adhesive #7004, manufactured by H. B. 
Fuller Co. The adhesive is a two component 
epoxy base that will cure at room 
temperature. Blending ratio by weight or 
volume is one to one, “Part A” with “Part B”.
The seat ring and sponge seat should be 
cleaned with alcohol or other suitable 
solvent compatible with the elastomer, 
before cementing. Apply adhesive to seat 
ring sparingly and spread uniformly in 
thin layer, approximately .001 to .003 
(.025 to .076 mm) thick, with knife or 
spatula. Place sponge seat on seat ring 
and press in place, smoothing out all 
ripples. Avoid stretching the sponge seat. 
Remove any excess epoxy which may 
have squeezed out. Allow to cure at room 
temperature for 24 hours.
For lox clean valves, cement the seat to 
seat ring using Fluorelastomer Solution, 
PLV-2000 with accelerator #4, manufactured 
by Pelmor Laboratories Inc. This is a two 
component cement consisting of a base 
material and accelerator. It can be mixed 
by weight or volume. By weight, use 44 
parts base material to 6 parts accelerator. 
By volume, use ½ pint (0.24 liter) base 
material to 225 drops accelerator. Allow to 
cure for 24 hours at room temperature.

Note:

 PLV-2000 Fluorelastomer can 

be obtained in an aerospray can with 
the accelerator added, so no mixing is 
necessary.

2.2.8  Assemble guide rod to body in reverse 

order from that described in 2.1.2, torque 
bolt 18 - 24 ft·lb (24.4 -32.5 Nm).

2.2.9  Assemble internal parts and inlet screen 

in reverse order from that described 
in 2.1.0 and 2.1.1. Be careful not to 
damage the PTFE surface on the guide 
rod. Apply a light coat of lubricant to all 
threads before assembly.

TYPE 96A VACUUM BREAKER SOFT GOODS KIT (REFERENCE DOCUMENT 04-4744)

Material

Tank connection

4”

6”

8”

12”

16”

Summary of Contents for Anderson Greenwood 96A Series

Page 1: ...s pressurized Never make adjustments to or perform maintenance on the safety valve while in service unless the valve is isolated from the system pressure If not properly isolated from the system pressure the safety valve may inadvertently open resulting in serious injury Remove the safety valve prior to performing any pressure testing of the system The safety of lives and property often depends on...

Page 2: ... guide tube assembly being careful not to damage the sealing surfaces 2 1 1 To disassemble the seat plate guide tube assembly insert a 250 6 35 mm diameter or smaller rod through the cross drilled hole in tube to prevent it from rotating while removing the lower nut Remove the nut weight if used and spacer Remove retainer and O ring from seat plate bolt The guide tube may be removed from the seat ...

Page 3: ...non lox clean valves cement new sponge seat to seat ring using Resiweld Adhesive 7004 manufactured by H B Fuller Co The adhesive is a two component epoxy base that will cure at room temperature Blending ratio by weight or volume is one to one Part A with Part B The seat ring and sponge seat should be cleaned with alcohol or other suitable solvent compatible with the elastomer before cementing Appl...

Page 4: ...eat sponge 11 Plate seat 12 Screen inlet 13 Retainer seat ring 14 Bolt retainer 15 Ring seat 16 O ring Seat plate 17 O ring Seat ring 18 Cap outlet 19 Stud 20 Nut 21 Gasket 23 Weight ring 24 Spacer 25 Retainer O ring 26 O ring 27 Eyebolt ø 249 269 ø6 32 6 83 mm Cross drill hole ø 280 288 ø7 11 7 32 mm Cross drill hole See detail B See detail A Relief valve connection 150 FFSF Tank connection oz se...

Page 5: ...ing careful that no portion of the seat is stretched All adhesive that get squeezed out should be cleaned up with no traces left on the top face of the sponge seat ANDERSON GREENWOOD SERIES 96A VACUUM BREAKER INSTALLATION AND MAINTENANCE INSTRUCTIONS 2017 Emerson All rights reserved ...

Reviews: