ANDERSON GREENWOOD

 5910C PRESSURE/VACUUM RELIEF VALVE WITH INTEGRATED 

FLAME ARRESTER (ATEX APPROVED)

SPECIAL CONDITIONS FOR SAFE USE (CONTINUED)

All 5910C deflagration elements are rated 
for short time burning, tBT not to exceed one 
minute in accordance with EN ISO 16852:2016. 
These burn times were determined at 
atmospheric pressure. If there are operating 
conditions which can lead to a stabilized 
burning event, additional safety measures are 
required. The devices shall be equipped with 
temperature sensors in the hood such that 
the atmospheric side of the flame cell can be 
monitored. These temperature sensors are 
installed into the system in such a way that 
they trigger the initiation of measures for 
the elimination of the stabilized burning (for 
example, emergency functions like switching-
off the system, inerting or similar). These 
measures must occur within half of the time 
for which the flame arrester is short-time burn 
proof (0.5 x tBT). See Figure 03 for warning 
label showing burn rating, tBT. This requires 
that measures must be able to be taken within 
30 seconds. 

Threaded instrumentation ports, with standard 
1/2 NPT threads, are integrated into each hood. 
Other instrumentation port thread sizes can be 
requested. 

If the user requests the addition of temperature 
sensors by Emerson, they will either be 
installed and shipped threaded into the 
appropriate instrumentation port in the 
flame arrester hood or shipped separately 
with the flame arrester. To install the 
temperature sensors that have been shipped 
separately, simply remove any protective 
packaging from the temperature sensors 
and thread the temperature sensors into the 
appropriate threaded instrumentation ports 
in the flame arrester hood making sure to 
follow temperature sensor manufacturer’s 
instructions, particularly for wiring.

The temperature sensor shall be installed on 
the downstream or unprotected (“hot”) side of 
the flame arrester. For end of line deflagration 
flame arresters this is the atmospheric side 
of the flame arrester and the only location 
available. If the temperature sensor is shipped 
separately, the user shall be responsible 
for installing the temperature sensor in the 
appropriate instrumentation port in the hood of 
the flame arrester.

If a temperature sensor is not requested with 
the flame arrester then the end user shall be 
responsible for installation of the temperature 
sensor on the unprotected (“hot”) side of 
flame arrester. This is the side of the flame 
arrester closest to the source of ignition 

TABLE 5. TEMPERATURE SENSOR SAFETY SPECIFICATIONS

TECHNICAL DATA

THERMOCOUPLE

Design Type

Standard with Thermowell

Standard without Thermowell

Model

185 03J1

Code 0185 thermocouple (IEC 584 
Class 1) without thermowell

Manufacturer

Emerson Rosemount

Emerson Rosemount

EC-type approval certificate

FM12ATEX0065X
ATEX:  EN 60079-0:2012+A11:2013; 
EN 60079-1: 2014

FM12ATEX0065X
ATEX:  EN 60079-0:2012+A11:2013; 
EN 60079-1: 2014

Temperature sensor design

Type-K thermocouple

Type-K thermocouple

Type of ignition protection

II 2 G Ex d IIC T6...
T1 Gb, T6(–50°C ≤ Ta ≤ + 40°C), T5...
T1 (–50 °C ≤ Ta ≤ + 60°C)

II 2 G Ex d IIC T6...
T1 Gb, T6(–50°C ≤ Ta ≤ + 40°C), T5...
T1 (–50°C ≤ Ta ≤ + 60°C)

Protection type  
(connection head)

Rosemount Aluminum
Explosion proof, 2-wire, 3-wire, 
4-wire type A, 4-Wire type as 
specified by customer.
Intrinsically safe option is available

Rosemount Aluminum
Explosion proof, 2-wire, 3-wire, 
4-wire type A, 4-Wire type as 
specified by customer.
Intrinsically safe option is available.

Measuring probe 
(measuring insert)

1/2 NPT or optional M24 x1.5. 
Intended for installation into 
thermowell.

Probe length varies by flame arrester 
size. Adjustable insertion length.

Connection thread

1/2 NPT. Intended for installation  
into thermowell.

1/2 NPT. Intended for installation 
without thermowell.

Transmitter

Optional by customer request.

Optional by customer request.

Intended application

In-line flame arresters and 
detonation arresters

End-of-line flame arresters. 
Free-vent style.

Model

TC 10-2 (for additional Thermowell)

TC10-H (threaded for direct insertion 
without thermowell)

Manufacturer

WIKA

WIKA

EC-type approval certificate

ATEX and IECEx certifications

ATEX and IECEx certifications

Temperature sensor design

Type-K thermocouple

Type-K thermocouple

Type of ignition protection

II 2 G Ex d IIC T6...
T1 Gb, T6(–50°C ≤ Ta ≤ + 40°C), T5...
T1 (–50°C ≤ Ta ≤ + 60°C)

II 2 G Ex d IIC T6...
T1 Gb, T6(–50°C ≤ Ta ≤ + 40°C), T5...
T1 (–50°C ≤ Ta ≤ + 60°C)

Protection type  
(connection head)

Explosion proof, 2-wire, 3-wire, 
4-wire type A, 4-Wire type as 
specified by customer.
Intrinsically safe option is available.

Explosion proof, 2-wire, 3-wire, 
4-wire type A, 4-Wire type as 
specified by customer.
Intrinsically safe option is available.

Measuring probe 
(measuring insert)

Spring loaded plate. Probe allows 
use of transmitter. Length varies by 
flame arrester size.

Probe length varies by flame arrester 
size. Adjustable insertion length.

Connection thread

1/2 NPT or optional M24 x1.5. 
Intended for installation  
into thermowell.

1/2 NPT. Intended for installation 
without thermowell.

Transmitter

Optional by customer request.

Optional by customer request.

Intended application

In-line flame arresters and 
detonation arresters.

End-of-line flame arresters. 
Free-vent style.

Summary of Contents for ANDERSON GREENWOOD 5910C

Page 1: ...nwood and our customer The Anderson Greenwood 5910C Pressure and vacuum relief valves with flame arrester assembly have not been tested by Anderson Greenwood under all possible operational conditions and Anderson Greenwood does not have all the data relative to your application The information in this instruction manual is not all inclusive and does not and cannot take into account all unique situ...

Page 2: ...ation valve and flame arrester is installed vertically on the roof of low pressure storage tanks anaerobic digesters and gas holders The 5910C Series unit relieves pressure directly to the atmosphere A weatherhood and mesh screen protects the valve pressure pallet and guideposts flame element assembly from contamination nesting animals weather etc In breathing ambient air relieves vacuum pressure ...

Page 3: ...ace on top of compensating weight and or pallet Secure with grip ring If setting is less than 2 WC weight will be pre loaded on the pallet d Variable setting each lead weight is calibrated from 1 WC increment Increments of WC and 1 2 WC may be supplied on special order Those weights necessary for the initial specified setting will be tagged separately from any extra weight provided Remove the pack...

Page 4: ...the pallets seat rings and guide posts When using silicone grease inspect valves at least weekly Extra attention must be given to inspection of the Flame Cell Assembly to ensure clear and consistent flow 2 To replace pallet insert proceed as follows a Remove weatherhood and or cover s and flame element assemblies and then pallet assembly b Remove nut from base of pallet stem Remove retainer plate ...

Page 5: ...etermine the maintenance interval the user should check the element in the first few months of operation to find how quickly particulate accumulates in the cells 8 After cleaning thoroughly inspect the element for damage If damaged replace it 5 Seat ring repair a Seat may be ground or ground and lapped in place to improve seal Use a lapping plate and medium valve grinding compound applying light p...

Page 6: ... 10 Insert Retainer 13 Screen Pressure 14 Hood 16 Cover 17 Gasket 19 Spacer Ring 21 Name Plate 22 Warning Label 24 Grip Ring 25 Stud FIGURE 4 CONSTRUCTION AND ASSEMBLY DETAIL 26 Nut 28 Nut 30 Screw Cap Hex 31 Screw Cap Hex 34 Screw Cap Hex 35 Pallet Stem 37 Insert Retainer 38 Pallet 39 O ring 40 Washer 42 Washer 43 Shroud 44 Drain 45 Standoff 46 Element Assembly Pressure 47 Element Assembly Vacuum...

Page 7: ...2 DEF LU D N A BC b tBT 1 min Ex Gp IIA T0 60 C Warning label for 5910C without short time burn protection Warning label for 5910C with short time burn protection WARNING PLATE INFORMATION EXPLAINED WARNING PLATE FIELD MARKING DEF DEF Deflagration LU D N A Suitable for End of Line use only BC b Short time burn 1 minute c no burn time Ex Gp IIA Suitable for MESG 0 94 mm T0 60 C Maximum Operational ...

Page 8: ...t to the source of ignition TABLE 5 TEMPERATURE SENSOR SAFETY SPECIFICATIONS TECHNICAL DATA THERMOCOUPLE Design Type Standard with Thermowell Standard without Thermowell Model 185 03J1 Code 0185 thermocouple IEC 584 Class 1 without thermowell Manufacturer Emerson Rosemount Emerson Rosemount EC type approval certificate FM12ATEX0065X ATEX EN 60079 0 2012 A11 2013 EN 60079 1 2014 FM12ATEX0065X ATEX ...

Page 9: ...n of measures against stabilized burning Note that a rise in temperature measured by the temperature sensor can indicate to the user deflagration and or detonation events have occurred as well This should be used as a trigger to investigate what conditions have lead to ignition of flammable vapors to inspect the flame arrester for damage and to initiate appropriate corrective actions relative to p...