background image

Type ACE95jr

4

E0620

the National Fire Codes of the National 

Fire Protection Agency or by other 

applicable codes) to prevent service 

conditions from exceeding those limits.
Additionally, physical damage to the 

tank blanketing system could result in 

personal injury and property damage 

due to escaping accumulated gas. 

To avoid such injury and damage, 

install the tank blanketing valve in a 

safe location.

This Type ACE95jr tank blanketing valve was 

assembled and preset to the customer specified 

pressure and setpoint. The control pressure range of 

the valve is stamped on the nameplate fastened to the 

upper actuator case. The gas blanketing setpoint is the 

only adjustable feature on this unit.

1. 

Get a qualified personnel when installing, operating, 

and maintaining valves. Before installing, inspect 

the valve and tubing for any shipment damage or 

foreign material that may have collected. Make 

certain the body interior is clean and the pipelines 

are free of foreign material. Apply pipe compound 

only to the male pipe threads with a screwed 

body or use suitable line gaskets and good bolting 

practices with a flanged body.

2.  Inspect the nameplate on the upper actuator 

case. It displays the model number, serial number, 

a blanketing gas supply pressure range, the 

maximum inlet pressure, set pressure and C

V

 

value. These must agree with the system that you 

are blanketing. The serial number will be needed 

in any communication with your local Sales Office.

3.  Clean the gas blanketing supply lines of all dirt 

and foreign material before connecting them to the 

Type ACE95jr tank blanketing valve.

4.  The valve must be mounted so the actuator 

case is horizontal, as shown in Figure 3. The 

valve should be mounted above the tank. Three 

connections are required: a) blanketing gas supply 

to valve, b) valve outlet to tank and c) sensing line 

to tank.

BLANKETING GAS 

SUPPLY LINE

LINE STRAINER

SHUTOFF 

VALVE

TYPE 252

INLET

FILTER

SHUTOFF 

VALVE

TYPE ACE95jr

SHUTOFF 

VALVE

SENSING

LINE

EMERGENCY 

TANK VENT

BLANKETING GAS 

TO TANK

TANK VENT

TANK

LIQUID

BLANKETING GAS/VAPOR SPACE

Figure 3.

 Type ACE95jr Tank Blanketing Valve Installation

Summary of Contents for ACE95jr

Page 1: ...y unqualified personnel may result in improper adjustment and unsafe operation Either condition may result in equipment damage or personal injury Use qualified personnel when installing operating and maintaining the Type ACE95jr Tank Blanketing Valve Scope of the Manual This Instruction Manual provides installation startup and maintenance procedures for the Type ACE95jr tank blanketing valve See F...

Page 2: ...Valve Sizing 110 of rated Cv Cv 0 2 use Cv 0 22 Cv 0 4 use Cv 0 44 IEC Sizing Coefficients Xt 0 655 Fd 0 86 Fl 0 89 Temperature Capabilities 1 Nitrile NBR 20 to 180 F 29 to 82 C Fluorocarbon FKM 0 to 212 F 18 to 100 C Ethylenepropylene EPDM FDA 20 to 212 F 29 to 100 C Perfluoroelastomer FFKM 20 to 212 F 29 to 100 C Approximate Weight with all accessories 30 lbs 14 kg 1 The pressure temperature lim...

Page 3: ... on these components therefore the outlet control pressure of the unit is not affected by fluctuating inlet pressure Installation WARNING Personal injury equipment damage or leakage due to escaping accumulated gas or bursting of pressure containing parts may result if this gas blanketing system is over pressured or installed where service conditions could exceed the limits given in the Specificati...

Page 4: ...f foreign material Apply pipe compound only to the male pipe threads with a screwed body or use suitable line gaskets and good bolting practices with a flanged body 2 Inspect the nameplate on the upper actuator case It displays the model number serial number a blanketing gas supply pressure range the maximum inlet pressure set pressure and CV value These must agree with the system that you are bla...

Page 5: ...e contact Emerson for alternate methods of installation A single array manifold is available for such situations Gauges and Shutoff Valves Inlet gas shutoff valves are desirable for servicing If this Type ACE95jr tank blanketing valve was not ordered with an inlet pressure gauge it is advisable to install a gauge between the inlet shutoff valve and the blanketing valve Note Safety considerations m...

Page 6: ...pe Adhesive Loctite 222 Be certain that nameplates are updated to accurately indicate any field changes in equipment materials service conditions or pressure settings Monthly Maintenance 1 Visually inspect the unit to ensure tight connections tight seals and safe operation 2 Observe the blanketing pressure 3 Inspect the inlet pressure for the proper pressure stamped on the valve nameplate Annual M...

Page 7: ...essure range Valve information is on the nameplate attached to the upper actuator case When performing disassembly or re assembly operations refer to Figure 6 for key numbers unless otherwise directed Disassembly WARNING To avoid personal injury resulting from sudden release of pressure isolate the valve from all pressure and cautiously release trapped pressure from the valve before attempting dis...

Page 8: ...ppet from the piston and remove the rolling diaphragm key 38 Assembly When assembling the Type ACE95jr tank blanketing valve clean all parts inspect for unusual wear lightly lubricate all O rings and the groove that locates the rolling diaphragm bead See Figure 6 Cage Sub Assembly 1 Install the internal O rings key 16 into the body key 18 2 Place the rolling diaphragm key 38 over the threaded port...

Page 9: ...screws key 55 with lock washers key 54 Tighten all uniformly 4 Place an O ring key 14 into the groove of the diaphragm bolt key 15 5 Build the diaphragm sub assembly with the diaphragm key 11 and two diaphragm plates keys 10 and 48 Fasten the plates together with the diaphragm bolt key 15 and the diaphragm retaining nut key 13 Apply Loctite 222 to the diaphragm bolt Note In cases where the pressur...

Page 10: ... ring 2 required Nitrile NBR 1F115306992 Ethylenepropylene EPDM FDA 1F1153X0062 Fluorocarbon FKM 1F1153X0022 Perfluoroelastomber FFKM 1F1153X0032 18 Body CV 0 2 1 2 NPT GC052930X02 NPS 1 2 DN 15 CL150 RF GC052930X02 1 NPT GC052930X02 NPS 1 DN 25 CL150 RF GC052930X02 NPS 1 2 x 1 DN 15 x 25 CL150 RF GC052930X02 NPS 1 DN 25 Sanitary Flange GC052930X02 1 2 x 1 NPT GC052930X02 Body CV 0 4 1 2 NPT GC052...

Page 11: ...0 32 27 55 54 162 L1 L1 L1 T T L1 L1 L1 L1 T APPLY LUBRICANT OR SEALANT 1 T THREAD LOCKER L1 GENERAL PURPOSE POLYTETRAFLUOROETHYLENE PTFE OR LITHIUM GREASE MAIN VALVE DETAIL 1 Lubricants must be selected such that they meet the temperature requirements Figure 6 Type ACE95jr Tank Blanketing Valve Assembly ...

Page 12: ...ark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are presented for informational purposes only and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability All sales a...

Reviews: