background image

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

500 Series 

570/560 Surge Protective Device 

Installation, Operation and Maintenance Manual

 

Courtesy of NationalSwitchgear.com

Summary of Contents for 500 Series

Page 1: ...500 Series 570 560 Surge Protective Device Installation Operation and Maintenance Manual Courtesy of NationalSwitchgear com ...

Page 2: ...ons 5 Voltage Protection Rating 5 Circuit Ampacity Limitations 5 System Grounding and Bonding 5 Grounding Electrode 6 Neutral Connection 6 Parallel Connection Wire Diagram 6 INSTALLATION INSTRUCTIONS Product Installation 7 Suggested Circuit Breaker and Wire Size Chart 8 Dimensional Information Chart 8 Suggested Circuit Breaker and Wire Size Motorola R56 Approved Models 9 Dimensional Information Mo...

Page 3: ... solid state motor drives etc For interconnected electronicloads suchasby wayofdatacabling transientsurge suppression should also be applied to the interconnecting wiring data cables Environment Unit is designed for operation indoors in ambient temperatures of 40ºC 40ºF to 60ºC 140ºF with a relative humidity of 0 to 95 non condensing The unit is provided in an industrial use enclosure which is dus...

Page 4: ...uvent être utilisés pour mettre en garde contre des pratiques dangereuses qui peuvent entraîner des dommages matériels seulement Units that include the ACTIVE SURGE MONITOR option 3 1 2 3 4 5 6 7 8 9 10 11 12 13 MODEL NUMBER CONFIGURATION Model _ _ _ _ _ _ _ _ _ _ _ _ _ 11 Enclosure N Caseless open style G Type 4 metal H Type 4X Stainless Steel J Type 4X Plastic F Type 12 Flushmount metal 12 UL 14...

Page 5: ...Installation Operation and Maintenance Manual IO 70100 Rev 3 7 15 CONFIGURATION VOLTAGE CHART 4 Courtesy of NationalSwitchgear com ...

Page 6: ...ational Electric Code 2008 Edition NEC 285 21 Connections NEC 285 23 Type 1 SPD s Shall be installed in accordance with 285 35 A and B A Installation Type 1 SPD s shall be installed as follows 1 Type 1 SPD s shall be permitted to be connected to the supply side of the service disconnect as permitted in 230 82 4 or 2 Type 1 SPD s shall be permitted to be connected in Type 2 locations as specified i...

Page 7: ... power conductors in the same raceway conduit When metallic raceways are used adequate electrical continuity must be maintained at all raceway connections particularly raceway terminations to the electrical enclosures The use of isolating bushings or other means to interrupt a metallic conduit run is a potential safety hazard and is not recommended Grounding Electrode Surge protective devices do n...

Page 8: ...sing 3 8 mounting hardware 4 Connect black wires line or phase marked L1 A L2 B or L3 C the white wire neutral marked N and the green wire ground marked G of the SPD using the wire range listed below To yield the best performance of the SPD within the electrical distribution system keep all conductors as short as possible and avoid sharp bends 5 Connection to the unit s summary alarm contacts shal...

Page 9: ... Compression Lug N 16 406 12 305 17 25 438 9 5 241 35 lb 15 9 kg Rotary Disconnect R 16 406 16 406 17 25 438 10 254 45 lb 20 4 kg 160kA 250kA Compression Lug N Rotary Disconnect R 20 508 16 406 21 25 540 10 254 55 lb 24 9 kg 300kA 375kA Compression Lug N Rotary Disconnect R 20 508 20 508 21 25 540 14 356 85 lb 38 6 kg 500kA Compression Lug N Rotary Disconnect R 20 508 24 610 21 25 540 18 457 95 lb...

Page 10: ...ble Range 15A 175A Suggested Size 80A Connection Wire Allowable Range 14 2 O Suggested Size 4 Motorola R56 Approved Models Model Number R56 Type Weight 570SA16FNRJ1S Type 1 MOV SAD Hybrid 28 lb 12 7 kg 570YA16FNRJ1S Type 1 MOV SAD Hybrid 32 lb 14 5 kg 560SA16FNRJ1S Type 2 MOV Only 24 lb 10 9 kg 560YA16FNRJ1S Type 2 MOV Only 28 lb 12 7 kg 9 Courtesy of NationalSwitchgear com ...

Page 11: ...0 This status does not indicate that the unit is in need of repair Active Surge Monitor Optional A web based monitoring device allowing real time power quality measurements logged events statistical summaries and premium power protection Understanding the severity type and timing of the event allows you to analyze trends and ultimately better manage your electrical system See IO 70109 for further ...

Page 12: ...varyfromsitetosite Inspectionsforfailedsurgemodulesusingavailable diagnosticsshouldbedoneroutinely weeklyor monthly Emerson Network Power Surge Protection 100 Emerson Parkway Binghamton NY 13905 800 288 6169 Phone U S Canada Only 607 721 8840 Outside U S 607 722 8713 FAX United States of America Emerson Network Power European Headquarters Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piov...

Reviews: