CONTENTS

Photovoltaic (PV) modular SPDs 

Technical data sheet: F01271EN_01 

Updated:  

Created: 31/10/2017

Cat. No(s): 4 141 55/56/85/86

  1. DESCRIPTION, INSTALLATION

1.1   Description

Type 2 SPDs for photovoltaic (PV) installations with voltages which may 

reach a maximum voltage (Uocmax) of 1200 VDC (irrespective of the 

local environmental, temperature, sunlight conditions, etc).

 Specifically designed to protect the DC part of PV installations (PV 

panels and inverters) 

- based on the use of non-polarised panels (panels which do not require 

their active conductors to be earthed)*

- without an energy storage system (e.g. batteries, etc)

  Equipped with replacement plug-in modules with LED indicators (red 

LED: modules need to be replaced).

* equipped with status feedback

1.2   Installation

SPDs must not be installed in locations where there is a risk of fire or 

explosion without special precautions. They must be disconnected 

before checking the installation insulation resistance.

Connections as per section 4.5 and 4.6: SPD connected to the mains 

supply and to the protective conductor (PE) using as short a connection 

as possible (<  50 cm).

Electromagnetic compatibility rules: avoid loops, fix the cables firmly 

against the exposed metal conductive parts. 

Compulsory connection of the earth terminal on the SPD to the 

protective conductor (PE) in the distribution board.

Equipotentiality rules: interconnection of the exposed conductive parts 

of the equipment and the protective conductor (PE) in the distribution 

board, which is itself connected to the earth terminal of the SPD (see 4.6).

  2. RANGE

Cat. No.

Description

Reference voltage

4 141 55

Base + Cartridges  

(4 141 85 x3)

600 VDC

4 141 56

Base + Cartridges  

(4 141 86 x3)

1000 VDC

4 141 85

Replacement cartridge

600 VDC

4 141 86

Replacement cartridge

1000 VDC

  3. DIMENSIONS

  4. POSITIONING, CONNECTION

4.1   Fixing

. On EN 60715 or DIN 35 symmetrical rail

4.2   Operating position

. Vertical            Horizontal                Side

4.3   Power supply

. 4 141 55/56:

 via the top

CONTENTS Page

1.  Description, installation . . . . . . . . . . . . . . . . . . 1

2.  Range  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3.  Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

4.  Positioning, connection . . . . . . . . . . . . . . . . . . 1

5.  General characteristics . . . . . . . . . . . . . . . . . . . 3

6.  Legrand recommendations  . . . . . . . . . . . . . . 4

7.  Conformity  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

8.  Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

       4 141 55/56                                                        4 141 85/86

Summary of Contents for 4 141 55

Page 1: ...ction 4 5 and 4 6 SPD connected to the mains supply and to the protective conductor PE using as short a connection as possible 50 cm Electromagnetic compatibility rules avoid loops fix the cables firmly against the exposed metal conductive parts Compulsory connection of the earth terminal on the SPD to the protective conductor PE in the distribution board Equipotentiality rules interconnection of ...

Page 2: ...also recommended close to the panels see section 4 5 and 4 6 Connection IP20 protected terminals with wired device Cage terminals with quick release captive screws Terminals fitted with flaps preventing a cable being placed under the terminal with the terminal partly open or closed Terminal depth 14 mm Connection cross sections and lengths to be stripped Permitted conductors Flexible Rigid 4 to 25...

Page 3: ...vel Up at In 5 kA 1 9 kV 3 2 kV Max operating current Iscpv 50 A 2 125 A 2 Max line current IL 40 A Residual current at Ucpv Ipe 1 mA Response time 25 ns Max terminal capacity flexible wire with cable ends rigid wire 25 35 mm Number of ports 1 Location category Indoor Installation method Permanent Number of modules 3 Protection index IP 20 IK 04 Pollution level 2 Operating temperature 25 C to 60 C...

Page 4: ... equipment room in which the main LV distribution board is installed 3 When a PV installation is protected by lightning conductors it is advisable to create an isolated lightning protection system isolated LPS as described in standard NF EN 62305 maintaining adequate separation distances between the metal structures of the panels and the LPS lightning conductors and downcomers 6 LEGRAND RECOMMENDA...

Reviews: