LEGRAND 4 141 55 Technical Data Sheet Download Page 3

3/4

CONTENTS

Photovoltaic (PV) modular SPDs

Technical data sheet: F01271EN_01 

Updated:  

Created: 31/10/2017

Cat. No(s): 4 141 55/56/85/86

  4. POSITIONING, CONNECTION (continued)

4.7   Replacing plug-in modules

Recommendation:

The installation must not be switched back on (DC/AC) without the 

plug-in modules fitted.

4.8   Status feedback

A signalling accessory is included for feedback of the SPD status.

  5. GENERAL CHARACTERISTICS

Marking on the front (plug-in modules)

. By indelible pad printing

Marking on the front (base) and markings on the side (base and 

plug-in modules)

. By laser

Characteristics

Cat. Nos.

4 141 55

4 141 85

4 141 56

4 141 86

Reference voltage (Uocstc)

600 V(DC)

1000 V(DC)

Max. voltage (Ucpv)

720 V(DC)

1200 V(DC)

SPD type

Type 2

Number of protected poles

2

Protection mode

(1)

Nominal current (In: 8/20 wave)

20 kA

Max. discharge capacity  

(Imax: 8/20 wave)

40 kA

Protection level (Up) at In (20 kA)

2.5 kV

4 kV

Protection level (Up) at In (5 kA)

1.9 kV

3.2 kV

Max. operating current (Iscpv)

50 A 

(2)

125 A 

(2)

Max. line current (I

L

)

40 A

Residual current at Ucpv (Ipe)

< 1 mA

Response time

25 ns

Max. terminal capacity (flexible 

wire with cable ends/rigid wire)

25/35 mm²

Number of ports

1

Location category

Indoor

Installation method

Permanent

Number of modules 

3

Protection index

IP 20/IK 04

Pollution level

2

Operating temperature 

-25°C to +60°C

Storage temperature

-25°C to +60°C

(1)

 Y protection mode: +/- protection, +/earth and -/earth.

(2)

 Maximum current that the PV SPD can withstand in the event of end 

of life due to a short-circuit without adding any external protection, 

irrespective of the local environmental, temperature, sunlight conditions, 

etc. This value must always be greater than the max. short-circuit current of 

the PV generator (1.25 Iscstc).

Materials

. Base:

     Fibreglass reinforced (10%) polycarbonate (PC)

     Self-extinguishing: 850°/30 s

     Colour: RAL 7035 light grey

. Plug-in module:

     Fibreglass reinforced (30%) polybutylene terephthalate (PBT)

     Self-extinguishing: 960°/30 s

     Colour: RAL 7035 light grey

Max. current

Rated voltage

Plug-in module characteristics

Cat. No.

Summary of Contents for 4 141 55

Page 1: ...ction 4 5 and 4 6 SPD connected to the mains supply and to the protective conductor PE using as short a connection as possible 50 cm Electromagnetic compatibility rules avoid loops fix the cables firmly against the exposed metal conductive parts Compulsory connection of the earth terminal on the SPD to the protective conductor PE in the distribution board Equipotentiality rules interconnection of ...

Page 2: ...also recommended close to the panels see section 4 5 and 4 6 Connection IP20 protected terminals with wired device Cage terminals with quick release captive screws Terminals fitted with flaps preventing a cable being placed under the terminal with the terminal partly open or closed Terminal depth 14 mm Connection cross sections and lengths to be stripped Permitted conductors Flexible Rigid 4 to 25...

Page 3: ...vel Up at In 5 kA 1 9 kV 3 2 kV Max operating current Iscpv 50 A 2 125 A 2 Max line current IL 40 A Residual current at Ucpv Ipe 1 mA Response time 25 ns Max terminal capacity flexible wire with cable ends rigid wire 25 35 mm Number of ports 1 Location category Indoor Installation method Permanent Number of modules 3 Protection index IP 20 IK 04 Pollution level 2 Operating temperature 25 C to 60 C...

Page 4: ... equipment room in which the main LV distribution board is installed 3 When a PV installation is protected by lightning conductors it is advisable to create an isolated lightning protection system isolated LPS as described in standard NF EN 62305 maintaining adequate separation distances between the metal structures of the panels and the LPS lightning conductors and downcomers 6 LEGRAND RECOMMENDA...