Installation, Operation and Maintenance Manual 

IO-70100   Rev 3   7-15

 

 

MONITORING FEATURES

 

External Status Indicators (Standard) — 
These indicators provide a summary of the 
status of the surge SPD module. For normal 
conditions, the green “OK” LED is illuminated 
and the red “Service” LED is extinguished. If 
the surge SPD module requires replacement, 
the green “OK” LED is turned off and the red 
“Service” LED illuminated.

 

Summary Alarm Contact (Standard) — Two 
sets of summary alarm Form C relay contacts 
(2 N.O. and 2 N.C.) are provided for remote 
indication of the failed surge SPD module. 
Contacts are rated 5 amps at 250 VAC 
maximum with a power factor of 1.0.   Access 
to the contacts is provided via contact 
terminals located on the printed circuit board 
mounted on the inside of the unit’s cover.

 

Audible Alarm (when included) — If the 
surge SPD module requires replacement, an 
audible alarm is activated to draw attention 
to the fact that repair service is required to 
restore the system to normal operation. An 
audible alarm disable is provided to silence 
the alarm. The system will automatically reset 
itself after repair. The audible alarm switch 
and “Service” LED can be tested by activating 
the “Test” switch on the system monitor 
panel.

 

Single/Dual Surge Counter (when 
included) – The surge counters are provided 
for transient voltage surge monitoring. The 
counter totalizes line surges monitored since 
the last time the counter was reset. The 
circuit counts all surges that deviate from the 
line sine wave. The factory setting is 30% over 
nominal line voltage. Other settings include 
50%, 70%, and 100%. 
“Test” Feature (when included) — The SPD 
Test feature will perform a self check of every 
individual fuse link within the SPD to 
determine the % of remaining protection. 

If 

any 2 Red indicators are on at the same time 
during the test, the unit is functioning at 
<100%. This status does not indicate that the 
unit is in need of repair. 

Active Surge Monitor (Optional) —

  

A web-

based monitoring device allowing real time power 
quality measurements, logged events, statistical 
summaries and premium power protection. 
Understanding the severity, type and timing of the 
event allows you to analyze trends and ultimately 

better manage your electrical system. (See IO-
70109 for further information)

 

 

TROUBLESHOOTING/SERVICING 

MAINTENANCE

 

Troubleshooting —

 

If status failure indication occurs or summary 
alarm contacts have changed state, a 
qualified electrician shall first determine if the 
systems voltage and proper phasing exists.

 

If the SPD remains in an alarm condition 
once the electrician is satisfied that the 
electrical system and its connections are 
normal, the unit should be repaired.

 

At this point consult the factory, having 
available the following information: 

 

Model number and serial number detailed 
on the units’ data label

 (located on the 

front of the enclosure)

.

 

 

Nature of problem –

 (including condition of 

all status indicators and alarms).

 

Servicing

 

The  Emerson Network Power 570/560  Series 
comes with a ten year parts and five year 
labor warranty. For servicing assistance, 
contact your local Sales Representative or 
Emerson Network Power, Surge Protection at 
800-288-6169 or 607-721-8840.

 

DANGER!   ONLY 

QUALIFIED 

PERSONNEL SHOULD INSTALL OR SERVICE 

THIS SYSTEM. ELECTRICAL SAFETY PRE-

CAUTIONS MUST BE FOLLOWED WHEN 

INSTALLING OR SERVICING THIS 

EQUIPMENT. TO PREVENT RISK OF 

ELECTRICAL SHOCK, TURN OFF AND LOCK 

OUT ALL POWER SOURCES TO THE UNIT 

BEFORE MAKING ELECTRICAL 

CONNECTIONS OR SERVICING. 

DANGER!  SEULEMENT LE PERSONNEL 

QUALIFIÉ DOIT INSTALLER OU MAINTENIR 
CE SYSTÈME.  DES PRÉCAUTIONS DE 

SÉCURITÉ EN ÉLECTRICITÉ DOIVENT ÊTRE 

SUIVIS LORS DE L'INSTALLATION OU DE LA 

MAINTENANCE DE CET EQUIPEMENT.  

POUR EVITER TOUT RISQUE DE CHOC 

ÉLECTRIQUE, DÉBRANCHEZ ET VEROUILLER 

TOUTES LES SOURCES D’ ALIMENTATION DE 
CET EQUIPEMENT AVANT DE LE BRANCHER 

OU LE MAINTENIR.

 

(continued) 

10

Courtesy of NationalSwitchgear.com

Summary of Contents for 500 Series

Page 1: ...500 Series 570 560 Surge Protective Device Installation Operation and Maintenance Manual Courtesy of NationalSwitchgear com ...

Page 2: ...ons 5 Voltage Protection Rating 5 Circuit Ampacity Limitations 5 System Grounding and Bonding 5 Grounding Electrode 6 Neutral Connection 6 Parallel Connection Wire Diagram 6 INSTALLATION INSTRUCTIONS Product Installation 7 Suggested Circuit Breaker and Wire Size Chart 8 Dimensional Information Chart 8 Suggested Circuit Breaker and Wire Size Motorola R56 Approved Models 9 Dimensional Information Mo...

Page 3: ... solid state motor drives etc For interconnected electronicloads suchasby wayofdatacabling transientsurge suppression should also be applied to the interconnecting wiring data cables Environment Unit is designed for operation indoors in ambient temperatures of 40ºC 40ºF to 60ºC 140ºF with a relative humidity of 0 to 95 non condensing The unit is provided in an industrial use enclosure which is dus...

Page 4: ...uvent être utilisés pour mettre en garde contre des pratiques dangereuses qui peuvent entraîner des dommages matériels seulement Units that include the ACTIVE SURGE MONITOR option 3 1 2 3 4 5 6 7 8 9 10 11 12 13 MODEL NUMBER CONFIGURATION Model _ _ _ _ _ _ _ _ _ _ _ _ _ 11 Enclosure N Caseless open style G Type 4 metal H Type 4X Stainless Steel J Type 4X Plastic F Type 12 Flushmount metal 12 UL 14...

Page 5: ...Installation Operation and Maintenance Manual IO 70100 Rev 3 7 15 CONFIGURATION VOLTAGE CHART 4 Courtesy of NationalSwitchgear com ...

Page 6: ...ational Electric Code 2008 Edition NEC 285 21 Connections NEC 285 23 Type 1 SPD s Shall be installed in accordance with 285 35 A and B A Installation Type 1 SPD s shall be installed as follows 1 Type 1 SPD s shall be permitted to be connected to the supply side of the service disconnect as permitted in 230 82 4 or 2 Type 1 SPD s shall be permitted to be connected in Type 2 locations as specified i...

Page 7: ... power conductors in the same raceway conduit When metallic raceways are used adequate electrical continuity must be maintained at all raceway connections particularly raceway terminations to the electrical enclosures The use of isolating bushings or other means to interrupt a metallic conduit run is a potential safety hazard and is not recommended Grounding Electrode Surge protective devices do n...

Page 8: ...sing 3 8 mounting hardware 4 Connect black wires line or phase marked L1 A L2 B or L3 C the white wire neutral marked N and the green wire ground marked G of the SPD using the wire range listed below To yield the best performance of the SPD within the electrical distribution system keep all conductors as short as possible and avoid sharp bends 5 Connection to the unit s summary alarm contacts shal...

Page 9: ... Compression Lug N 16 406 12 305 17 25 438 9 5 241 35 lb 15 9 kg Rotary Disconnect R 16 406 16 406 17 25 438 10 254 45 lb 20 4 kg 160kA 250kA Compression Lug N Rotary Disconnect R 20 508 16 406 21 25 540 10 254 55 lb 24 9 kg 300kA 375kA Compression Lug N Rotary Disconnect R 20 508 20 508 21 25 540 14 356 85 lb 38 6 kg 500kA Compression Lug N Rotary Disconnect R 20 508 24 610 21 25 540 18 457 95 lb...

Page 10: ...ble Range 15A 175A Suggested Size 80A Connection Wire Allowable Range 14 2 O Suggested Size 4 Motorola R56 Approved Models Model Number R56 Type Weight 570SA16FNRJ1S Type 1 MOV SAD Hybrid 28 lb 12 7 kg 570YA16FNRJ1S Type 1 MOV SAD Hybrid 32 lb 14 5 kg 560SA16FNRJ1S Type 2 MOV Only 24 lb 10 9 kg 560YA16FNRJ1S Type 2 MOV Only 28 lb 12 7 kg 9 Courtesy of NationalSwitchgear com ...

Page 11: ...0 This status does not indicate that the unit is in need of repair Active Surge Monitor Optional A web based monitoring device allowing real time power quality measurements logged events statistical summaries and premium power protection Understanding the severity type and timing of the event allows you to analyze trends and ultimately better manage your electrical system See IO 70109 for further ...

Page 12: ...varyfromsitetosite Inspectionsforfailedsurgemodulesusingavailable diagnosticsshouldbedoneroutinely weeklyor monthly Emerson Network Power Surge Protection 100 Emerson Parkway Binghamton NY 13905 800 288 6169 Phone U S Canada Only 607 721 8840 Outside U S 607 722 8713 FAX United States of America Emerson Network Power European Headquarters Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piov...

Reviews: