High Precision
The 4320 is shipped with a default 1% of span accuracy. The high precision option is set at the factory and ships with
0.4% of span accuracy. Reporting must also be enabled in the configuration.
Field Communicator
Select
Online, Configure, Manual Setup, Device,
then
Reporting Precision
to verify or make changes to reporting precision.
Refer to the Configure menu tree shown in figure 22.
AMS Wireless Configurator or AMS Device Manager
Go to
Configure
,
Manual Setup
, then select
Device Variable Properties
from the Device tab to verify or make changes to
Reporting Precision, as shown in figure 25.
Scaled Position
By default the 4320 provides a percent of span, however, a second scaled position value can be configured and sent to
gateway as a reported value. This feature enables reporting in other values.
Field Communicator
Configure
,
Manual Setup
,
Device
,
Device Variable Properties
,
Scaled Position Properties
to verify or makes changes to the
scaled position. Refer to the Configure menu tree shown in figure 22.
AMS Wireless Configurator or AMS Device Manager
Go to
Configure
,
Manual Setup
, then select
Device Variable Properties
from the Device tab to access Scaled Position
Properties, as shown in figure 25.
Figure 25. Device Variable Properties
DEVICE TAB
REPORTING PRECISION
SCALED POSITION
DEVICE VARIABLE PROPERTIES