Instruction Manual
D103621X012
4320
January 2018
33
Manual Setup
Follow the prompts on the Field Communicator to view or edit
Wireless
,
Device
,
Limit Switch Configuration
,
Mapping
,
Fault Behavior
,
Local User Interface
,
Power Module
, and
Event Configuration.
D
Wireless
Network ID (dec)
—displays the current Network ID setting.
Join Device to Network
—enter the Network ID (up to 5‐digits) and the Join Key (4 sets of 8 hexadecimal digits). The Join
Key is used for encrypting the data on the wireless network. The Network ID and the Join Key are the same for all
devices connected to a gateway.
Note
The Network ID is shipped with a default value of 1229 and the Join Key with a default value of all zeros. These must be changed
prior to use.
When the gateway is configured in an advanced security mode each device is required to have an individual join key.
D
Broadcast Information
Tailor Burst Configuration
—automatically selects an appropriate burst configuration for your application based on your
input.
Note
Configure the Device Structure (Configure > Manual Setup > Device > Structure) prior to running Tailor Burst Configuration for best
burst configuration results.
Set all Burst Messages to Default
—select
Set all Burst Messages to Default
to automatically configure all burst messages to
default values, as shown below. The Dynamic Variable defaults to a setting that is consistent with the published
variables. This is recommended for initial configuration, and to recover from a bad configuration.
On/Off Control
Message 0:
Selected Device Variables
- On, Windowed, 8 second triggered update, 1 minute default
Message 1:
Additional Device Status
- On, OnChange, 1 minute triggered update, 1 hour default, Delayed Triggering
Message 2:
Discrete Variables
- On, OnChange, 8 second triggered update, 1 minute default
Sensor Sample Rate:
8 seconds for a battery powered device. (50 milliseconds for external power)
Snap-Acting Control
Message 0:
Selected Device Variables
- On, Windowed, 16 second triggered update, 1 minute default
Message 1:
Additional Device Status
- On, OnChange, 1 minute triggered update, 1 hour default, Delayed Triggering
Message 2:
Discrete Variables
- On, OnChange, 1 minute triggered update, 10 minute default
Sensor Sample Rate:
1 second for a battery powered device. (50 milliseconds for external power)