background image

NetSure

 DC/DC Converter Module 

User Manual, UM1C48241500 (Revision E, July 20, 2015) 

Spec. No: 1C48241500 

 

Code: UM1C48241500 

Model No: C48/24-1500 

 

Revision E, July 20, 2015 

2

 

 

Storage Ambient Temperature Range:  -40°C to +70°C 
(-40°F to +158°F). 

 

Humidity:  This converter module is capable of operating 
in an ambient relative humidity range of 0 to 90%, non-
condensing. 

 

Altitude:  The maximum operating ambient temperature 
should be derated by 3°C per 1000 feet at an elevation of 
6,000 feet. 

 

Ventilation Requirements:  The converter module is fan 
cooled and utilizes front to back forced ventilation. 

 

Audible Noise:  With a single converter module installed 
and operating, the audible noise measured in front of 
converter at a 0.6m distance from a horizontal line from 
the middle of converter does not exceed 50 dBA with a 
temperature of 25°C. 

 

Over Voltage Category:  II. 

 

Power Distribution System:  TN/TT/IT. 

Note:

  The converter module is recommended to be used in an 

environment with Pollution of Degree 2 or less.  Pollution 
Degree 2 applies where there is only non-conductive 
pollution that might temporarily become conductive due 
to occasional condensation (such as the office 
environment). 

Compliance Information 

 

Safety Compliance:  This unit meets the requirements of 
UL 60950-1, Standard for Information Technology 
Equipment, and is UL Recognized as a power supply for 
use in Telephone, Electronic Data Processing or 
Information Processing Equipment. 

 

EMC:  This unit meets EN300 386 V1.51, Class A, other 
than Telecom centers. 

 

EFT:  This unit meets EN61000-4-4, EFT will be fulfilled for 
DC terminals at 4KV (CM) with criteria B and signal line at 
1KV (CM) with criteria B. 

 

ESD:  This unit meets EN61000-4-2; requirements are 
6KV contact and 8KV air for criteria B and 8KV/15KV for 
criteria C. 

 

Radiated Electrical Fields:  This unit meets EN61000-4-3.  
10V/m in the frequency range 80MHZ-1GHz and 
1.4-2GHz with criteria A will be fulfilled. 

 

Power Frequency Magnetic Field:  This unit meets 
EN61000-4-8.  30A/m magnetic field at 50Hz will be 
fulfilled for criteria A. 

 

Radiated Emission:  For electrical field, meets EN55022 
Class A between 150KHZ-30MHZ.  For a standalone 
converter the levels are 6db below the class A limits. 

 

Climatic Environment: 

a.

 

Transportation:  Meets ETS 300 019-1-2, Class 2.3. 

b.

 

Storage and Handling:  Meets ETS 300 019-1-1, Class 
1.2. 

c.

 

Operation:  Meets ETS 300 019-1-3, Class3.2. 

d.

 

Transportation, Storage and Handling, Operation:  
Meets Telcordia GR-63-Core, Chapter 4. 

 

GR-3108 Class 2 Compliant 

Standard Features 

 

Type of Power Conversion Circuit:  High Frequency. 

 

Input Voltage Protection: 

a.

 

Fusing:  A non-user replaceable fuse is located in the 
positive input lead of each DC-DC converter module. 

b.

 

High and Low Input Voltage Inhibit:  The converter 
shuts down at low or high input voltage. 

1.

 

Low Voltage Disable Point:  -40.0 Vdc ±0.5 Vdc; 
hysteretic at least 3 Vdc for restart. 

2.

 

High Voltage Disable Point:  59.5 Vdc ±0.5 Vdc; 
hysteretic at least 2 Vdc for start. 

 

Output Protection: 

a.

 

Overvoltage Protection:  When output voltage goes 
above a preset value (30.5±0.5V, not to exceed 31V 
for more than 150ms), the converter shuts down.  
Software settable HVSD level (from controller) 
27V-30V. 

b.

 

Power Limit:  Output power is limited to 1500W. 

c.

 

Over Temperature Protection:  The operation of a 
DC-DC converter module will automatically shut 
down and lock out if the internal temperature of the 
module exceeds a predetermined value.  Operation 
will automatically resume after the over-
temperature condition is corrected. 

 

Series Paralleling Output FET:  A series paralleling output 
FET is provided in each DC-DC converter module.  This 
allows the Modules to be paralleled for redundancy. 

 

Hot Swappable:  The converter module is designed to be 
plug-and-play.  The converter module can be inserted or 
removed from a live DC power system with no damage.  
When the converter module is plugged into the system, 
the sub-system output voltage will not be affected. 

Summary of Contents for 1C48241500

Page 1: ...NetSure DC DC Converter Module User Manual UM1C48241500 Revision E July 20 2015 Specification Number 1C48241500 Model Number C48 24 1500 ...

Page 2: ...NetSure DC DC Converter Module User Manual UM1C48241500 Revision E July 20 2015 Spec No 1C48241500 Code UM1C48241500 Model No C48 24 1500 Revision E July 20 2015 This page is intentionally blank ...

Page 3: ...E July 20 2015 i Table of Contents Admonishments Used in this Document ii Static Warning iii Introduction 1 Overview 1 Specifications 1 Operation 4 Local Indicators 4 Converter High Voltage Shutdown and Lockout Restart 4 Converter Current Limit 4 Installing Converter Modules 5 Troubleshooting and Repair 5 Troubleshooting 5 Replacement Procedures 7 ...

Page 4: ...erate injury if not avoided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT Alerts the reader to an action that must be avoided in order to protect equipment software data or service ISO ALERT Alerts the reader to an action that must be performed in order ...

Page 5: ...810600 have a built in one megohm resistor no external resistor is necessary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing static sensitive components Handle equipment containing static sensitive components only by the edges that do not have connector pads 4 After removing equipment contai...

Page 6: ...NetSure DC DC Converter Module User Manual UM1C48241500 Revision E July 20 2015 Spec No 1C48241500 Code UM1C48241500 Model No C48 24 1500 Revision E July 20 2015 iv This page is intentionally blank ...

Page 7: ...mum load output voltage 24V c Wideband noise is 20mV rms between 25HZ 20kHz test according to ETS300132 d Output noise according to Telcordia GR 947 CORE 38 dBrnC between 5 100 of the maximum load output voltage 24V Ripple Attenuation Ripple attenuation is better than 24dB input to output and f 360Hz DC Input Ratings Voltage Nominal 48 volts DC Nameplate Rating 41 to 58 5 Vdc 39 5A max Inrush Curr...

Page 8: ...0MHZ 1GHz and 1 4 2GHz with criteria A will be fulfilled Power Frequency Magnetic Field This unit meets EN61000 4 8 30A m magnetic field at 50Hz will be fulfilled for criteria A Radiated Emission For electrical field meets EN55022 Class A between 150KHZ 30MHZ For a standalone converter the levels are 6db below the class A limits Climatic Environment a Transportation Meets ETS 300 019 1 2 Class 2 3...

Page 9: ...restored Monitoring Function The converter module has a built in advanced DSP Digital Signal Processor that monitors and controls the operation of the converter module The DSP also communicates with the associated system Controller in real time through the CAN bus Table 2 lists the different commands and information exchanged between the converter module and the Controller External Alarm Provided ...

Page 10: ... limit set point of 30 amps If one or more converters are removed or fail it will take several seconds for the individual set points to the remaining converters to be reset In the example given if one converter is removed the current limit set point will drop to 120 amps 30 amps times four remaining converters until the controller can send updated set points to the remaining converters This takes ...

Page 11: ...nting slot without sliding it in completely 3 Loosen the captive screw on the module s handle Pull the handle down out from the module s front panel this will also retract the latch mechanism See Figure 2 4 Push the module completely into the shelf 5 Push the handle up into the module s front panel This will lock the module securely to the shelf Tighten the captive screw on the handle 6 Repeat the...

Page 12: ...ated in the shelf If this does not correct the fault replace the converter module Converter module not inserted into the slot completely Remove and properly insert the converter module Converter module over temperature protection which could be caused by 1 Fan rotor blocked 1 Remove any object that may be blocking the fan 2 Ventilation blocked inlet or outlet 2 Remove any object that may be blocki...

Page 13: ... easily disabled notify the appropriate personnel to disregard any alarms associated with this system while this procedure is performed 2 Loosen the captive screw on the module s handle Pull the handle down out from the module s front panel this will also retract the latch mechanism See Figure 2 3 Grasp the handle and pull firmly to remove the module from the shelf 4 Place the replacement converte...

Page 14: ... is subject to change without notice and may not be suitable for all applications While every precaution has been taken to ensure the accuracy and completeness of this document Emerson Network Power Energy Systems North America Inc assumes no responsibility and disclaims all liability for damages result ing from use of this information or for any errors or omissions Refer to other local practices ...